XP16 − 2 to 5 Ton Heat Pump
SPECIFICATIONS
General
D t
Model No.
XP16−024
XP16−036
XP16−048
XP16−060
Data
Nominal Tonnage
2
3
4
5
Connections
(
t)
Liquid line (o.d.) − in.
3/8
3/8
3/8
3/8
(sweat)
Vapor line (o.d.) − in.
3/4
7/8
7/8
1−1/8
Refrigerant
1
R−410A charge furnished
7 lbs. 13 oz.
10 lbs. 4 oz.
15 lbs. 7 oz.
11 lbs. 7 oz.
Outdoor
C il
Net face area − sq. ft. Outer coil
13.22
18.67
24.5
24.93
Coil
Inner coil
12.65
18.0
23.64
24.14
Tube diameter − in.
5/16
5/16
5/16
5/16
No. of rows
2
2
2
2
Fins per inch
22
22
22
22
Outdoor
F
Diameter − in.
18
22
22
26
Fan
No. of blades
3
4
4
3
Motor hp
1/10
1/6
1/4
1/3
Cfm
2215
3150
3980
4380
Rpm
1040
844
836
850
Watts
145
215
305
280
Shipping Data −
lbs. 1 pkg.
219
265
309
345
ELECTRICAL DATA
Line voltage data − 60hz
4
208/230V−1ph
4
208/230V−1ph
4
208/230V−1ph
4
208/230V−1ph
2
Maximum overcurrent protection (amps)
20
35
45
60
3
Minimum circuit ampacity
14.0
22.0
28.2
33.9
Compressor
Rated load amps
10.25
16.67
21.15
25.87
p
Locked rotor amps
52
82
96
118
Power factor
0.98
0.99
0.99
0.99
Outdoor Coil
F
M t
Full load amps
1.1
1.1
1.7
1.8
Fan Motor
Locked rotor amps
2
2.1
3.1
2.9
OPTIONAL ACCESSORIES − must be ordered extra
ComfortSense
t
7000 Thermostat
Y0349
S
S
S
S
Outdoor Temperature Sensor
− for
ComfortSense
t
7000 Thermostat
X2658
S
S
S
S
Compressor Hard Start Kit −
Required
i
li
ti
ith l
th
230V
10J42
S
S
p
q
in applications with less than 230V
81J69
S
S
Compressor Low Ambient Cut−Off
45F08
S
S
S
S
Freezestat
3/8 in. tubing
93G35
S
S
S
S
5/8 in. tubing
50A93
S
S
S
S
Indoor Blower Speed Relay Kit
40K58
S
S
S
S
Indoor Blower Off Delay Relay
58M81
S
S
S
S
Low Ambient Kit
68M04
S
S
S
S
Mild Weather Kit
33M07
S
S
S
S
Monitor Kit − Service Light
76F53
S
S
S
S
Outdoor
Thermostat
Thermostat
56A87
S
S
S
S
Thermostat
Kit
Mounting Box
31461
S
S
S
S
Refrigerant
Line Sets
L15−41−20
L15−41−30
L15−41−40
L15−41−50
S
L15−65−30
L15−65−40
L15−65−50
S
S
Field Fabricate
S
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Refrigerant charge sufficient for 15 ft. length of refrigerant lines.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
4
Hard start kit is required in applications where the supply voltage is less than 230V.