![Lennox EL195UH040NE36B Скачать руководство пользователя страница 4](http://html.mh-extra.com/html/lennox/el195uh040ne36b/el195uh040ne36b_installation-instructions-and-use_1877378004.webp)
Page 4
In order to ensure proper unit operation in non-direct vent
applications, combustion and ventilation air supply must
be provided according to the current National Fuel Gas
Code or CSA-B149 standard.
Installation Locations
This furnace is CSA International certified for installation
clearances to combustible material as listed on the unit
nameplate and in the table in figure 12. Accessibility and
service clearances must take precedence over fire protec
-
tion clearances.
NOTE - For installation on combustible floors, the furnace
shall not be installed directly on carpeting, tile, or other
combustible material other than wood flooring.
For installation in a residential garage, the furnace must
be installed so that the burner(s) and the ignition source
are located no less than 18 inches (457 mm) above the
floor. The furnace must be located or protected to avoid
physical damage by vehicles. When a furnace is installed
in a public garage, hangar, or other building that has a
hazardous atmosphere, the furnace must be installed ac
-
cording to recommended good practice requirements and
current National Fuel Gas Code or CSA B149 standards.
NOTE - Furnace must be adjusted to obtain a temperature
rise within the range specified on the unit nameplate. Fail-
ure to do so may cause erratic limit operation and prema-
ture heat exchanger failure.
This EL195UHNE furnace must be installed so that its
electrical components are protected from water.
Installed in Combination with a Cooling Coil
When this furnace is used with cooling coils (figure 3), it
shall be installed in parallel with, or on the upstream side
of, cooling coils to avoid condensation in the heating com-
partment. With a parallel flow arrangement, a damper (or
other means to control the flow of air) must adequately
prevent chilled air from entering the furnace. If the damp-
er is manually operated, it must be equipped to prevent
operation of either the heating or the cooling unit, unless it
is in the full
HEAT
or
COOL
setting.
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Elec-
tric Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following ad-
dress:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit
must be installed according to the current regulations of
the Canadian Electrical Code Part I (CSA Standard C22.1)
and/or local codes.
Gas Unit
Heating Unit Installed Upstream of Cooling Coil
Gas Unit
Dampers
(open during heating operation only)
Dampers
(open during cooling operation only)
Heating Unit Installed Parallel to Air Handler Unit
Air Handler Unit
Cooling Coil
AIR FLOW
AIR FLOW
AIR FLOW
AIR FLOW
Figure 3
NOTE - This furnace is designed for a minimum contin-
uous return air temperature of 60°F (16°C) or an inter-
mittent operation down to 55°F (13°C) dry bulb for cases
where a night setback thermostat is used. Return air tem-
perature must not exceed 85°F (29°C) dry bulb.
The EL195UHNE furnace may be installed in alcoves,
closets, attics, basements, garages, crawl spaces and
utility rooms in the upflow or horizontal position. This fur
-
nace design has not been CSA certified for installation in
mobile homes, recreational vehicles, or outdoors.
Use of Furnace as Construction Heater
Lennox does not recommend the use of EL195UHNE
units as a construction heater during any phase of con-
struction. Very low return air temperatures, harmful vapors
and operation of the unit with clogged or misplaced filters
will damage the unit.
Units may be used for heating of buildings or structures
under construction, if the following conditions are met::
•
The vent system must be permanently installed per
these installation instructions.
•
A room thermostat must control the furnace. The
use of fixed jumpers that will provide continuous
heating is not allowed.
•
The return air duct must be provided and sealed to
the furnace.
•
Return air temperature range between 60°F (16°C)
and 80°F (27°C) must be maintained.
•
Air filters must be installed in the system and must
be maintained during construction.