background image

Page 21

VI-MAINTENANCE

At the beginning of each heating season, and to comply
with the 

Lennox Limited Warranty

, your system should be

checked by a licensed professional technician (or equiva­
lent) as follows:

NOTE - 

Burner inspection and service is not recommended

for annual furnace maintenance.

IMPORTANT

If a high­efficiency filter is being installed as part of
this system to ensure better indoor air quality, the fil­
ter must be properly sized. High­efficiency filters
have a higher static pressure drop than standard­ef­
ficiency glass/foam filters. If the pressure drop is too
great, system capacity and performance may be re­
duced. The pressure drop may also cause the limit to
trip more frequently during the winter and the indoor
coil to freeze in the summer, resulting in an increase
in the number of service calls.

Before using any filter with this system, check the
specifications provided by the filter manufacturer
against the data given in the appropriate Lennox
Product Specifications bulletin. Additional informa­
tion is provided in Service and Application Note
ACC­00­2 (August 2000).

WARNING

Fire Hazard. Use of aluminum wire with this
product may result in a fire, causing property dam­
age, severe injury or death. Use copper wire only
with this product.

CAUTION

Failure to use properly sized wiring and circuit
breaker may result in property damage. Size wiring
and circuit breaker(s) per Product Specifications
bulletin (EHB) and unit rating plate.

1- Check wiring for loose connections, voltage at indoor

unit and amperage of indoor motor

.

2- Inspect all gas pipe and connections for leaks

.

3- Check the cleanliness of filters and change if necessary

(monthly).

4- Check the cleanliness of blower assembly and clean

the housing, blower wheel and blower motor if neces­
sary

.

5- Inspect the combustion air inducer and clean if neces­

sary.

TABLE 13

Furnace

Cabinet Width

Filter Size

Side Return

Bottom Return

A - 14-1/2”

16 X 25 X 1 (1)

14 X 25 X 1 (1)

B - 17-1/2”

16 X 25 X 1 (1)

16 X 25 X 1 (1)

C - 21”

16 X 25 X 1 (1)

20 X 25 X 1 (1)

6- Evaluate the heat exchanger integrity by inspecting the

heat exchanger per the AHRI heat exchanger inspec­
tion procedure.  This procedure can be viewed at
www.ahrinet.org. See “Induced-draft Furnace Heat Ex­
changer Inspection Procedure”.

7- Ensure sufficient combustion air is available to the fur­

nace.  Fresh air grilles and louvers (on the unit and in the
room where the furnace is installed) must be properly
sized, open and unobstructed to provide combustion
air

.

8- Inspect the furnace venting system to make sure it is in

place, structurally sound, and without holes, corrosion,
or blockage. Vent system must be free and clear of ob­
structions and must slope upward away from the fur­
nace

.

 Vent system should be installed per the National

Fuel Gas Code

9- Inspect the furnace return air duct connection to ensure

the duct is sealed to the furnace. Check for air leaks on
supply and return ducts and seal where necessary

.

10- Check the condition of the furnace cabinet insulation

and repair if necessary.

11- Perform a complete combustion analysis during the fur­

nace inspection to ensure proper combustion and oper­
ation.  Consult Service Literature for proper combustion
values.

12- Verify operation of smoke detectors and CO detectors

and replace batteries as required.

Perform a general system test. Turn on the furnace to
check operating functions such as the start-up and shut-off
operation.
 1 - Check the operation of the ignition system, inspect

and clean flame sensor. Check microamps before and
after. Check controls and safety devices (gas valve,
flame sensor, temperature limits). Consult Service
Manual for proper operating range. Thermal Limits
should be checked by restricting airflow and not dis­
connecting the indoor blower. For additional details,
please see Service and Application Note H­04­9.

 2 - Verify that system total static pressure and airflow set­

tings are within specific operating parameters.

 3 - Clock gas meter to ensure that the unit is operating at

the specified firing rate. Check the supply pressure
and the manifold pressure. 

Not all gas valves are ad­

justable

.

 

Verify correct temperature rise.

Содержание EL180UH040NE36A

Страница 1: ...f local or state codes the guidelines and procedures outlined in this manual except where noted are recommended only and do not constitute code CAUTION As with any mechanical equipment contact with sh...

Страница 2: ...ta lbs 1 package 100 113 125 149 NOTE Filters and provisions for mounting are not furnished and must be field provided 1 Annual Fuel Utilization Efficiency based on DOE test procedures and according t...

Страница 3: ...3 1190 141 1030 86 930 73 835 55 0 10 1380 251 1165 150 990 95 890 89 790 65 0 20 1360 264 1115 158 950 99 840 78 730 68 0 30 1315 278 1090 171 910 110 790 89 660 61 0 40 1295 290 1070 182 865 122 740...

Страница 4: ...5 220 1425 160 2235 595 1945 382 1725 262 1590 202 1430 165 0 10 2175 639 1910 427 1685 287 1545 234 1400 176 2205 611 1915 397 1695 280 1550 218 1400 193 0 20 2145 658 1885 449 1635 309 1490 246 1325...

Страница 5: ...ludes integrated control interlock switch and transformer Blower Assembly Power Choke 4 and 5 Ton Only PARTS ARRANGEMENT Heat Exchanger Combustion Air Inducer Gas Valve Intake Air Elbow Access Panel I...

Страница 6: ...system consisting of an in tegrated control figure 3 with control terminal designa tions in tables 1 2 and 3 sensor and ignitor figure 6 The integrated control and ignitor work in combination to en su...

Страница 7: ...e Switch In 11 Rollout Switch In 12 Gas Valve Out TABLE 3 1 4 QUICK CONNECT TERMINALS 120HUM Humidifier 120VAC LINE 120VAC XFMR Transformer 120VAC CIRC Indoor blower 120VAC EAC Indoor air quality acce...

Страница 8: ...Open or Watchguard Mode Limit Switch Open longer than 3 minutes 8 Rollout Switch Open 9 Pressure Switch failed to close or opened during heat demand 10 Watchguard Pressure Switch opened 5 times durin...

Страница 9: ...air temperature once the heat demand is satisfied Note the supply air temperature at the instant the blower is de energized Adjust the fan off delay to achieve a supply air temperature between 90 110...

Страница 10: ...h unit model number See Lennox Repair Parts Handbook if limit switch must be replaced 7 Gas Valve Figure 6 The valve is internally redundant to assure safety shut off If the gas valve must be replaced...

Страница 11: ...ry make note of the tubing connections to the gas valve See figure 8 NOTE The switch is factory set and is not field adjustable It is a safety shut down control in the furnace and must not be by passe...

Страница 12: ...Page 12 FIGURE 8 Replacing the Pressure Switch or Tubing...

Страница 13: ...s correct then then there is a problem with the wiring between the jack plug and control If the reading is not correct the issue is the ignitor Meter set to ohms Test 3 Insert meter probes into the te...

Страница 14: ...shooting the Motor Troubleshooting the motor is an easy process Follow steps below 1 Shut off power to unit 2 Remove input plugs P48 and P49 from motor See figure 12 for troubleshooting procedure If c...

Страница 15: ...s fan 1 2 3 4 or 5 on input plug P49 If 24 volts is not present problem may be up stream of plug P49 Proceed to test 4 Multi Meter set to VAC 12 0 12 0 24 Multi Meter set to VAC Check for 24 volts acr...

Страница 16: ...read approximate ly the same resistance within an ohm 3 Check to see if the blower wheel spins freely FIGURE 15 Motor Test TABLE 8 Scale Measurement range in words ohms 2 M two megohm two million ohm...

Страница 17: ...it if service is to be performed 3 Remove the upper access panel 4 Move gas valve switch to OFF position Do not force See figure 17 5 Replace the upper access panel B Safety or Emergency Shutdown Disc...

Страница 18: ...he supply pressure tap See figure 16 Loosen the screw and connect a manometer to measure supply pressure See table10 for supply line pressure Tighten screw after measurements have been taken Manifold...

Страница 19: ...s a poor or partial ground Compare the readings to the table below If the read ings exceed the maximum shown in table 12 make re pairs before operating the furnace 2 In addition measure the AC voltage...

Страница 20: ...ply and return air plenums Insert manometer hose flush with inside edge of hole or insulation Seal around the hose with permagum Connect the zero end of the manometer to the discharge supply side of t...

Страница 21: ...X 1 1 16 X 25 X 1 1 C 21 16 X 25 X 1 1 20 X 25 X 1 1 6 Evaluate the heat exchanger integrity by inspecting the heat exchanger per the AHRI heat exchanger inspec tion procedure This procedure can be v...

Страница 22: ...gn matter Remove any blockage Figure 23 shows burner detail Replace gasket between burner plate and air fuel plenum then re install burner plate 10 To clean the combustion air inducer visually inspect...

Страница 23: ...BLY HEAT EXCHANGER REMOVAL FIGURE 23 Gas Valve Air Intake Assembly leave intact Heat Exchanger Air Gas Plenum Gasket Burner Burner Box Liner leave intact FIGURE 24 Remove 5 screws if necessary either...

Страница 24: ...ue 5 A92 integrated control energizes B6 combustion air inducer S18 combustion air pressure switch closes Once S18 closes a 15 second pre purge follows 6 A92 integrated control energizes R33 ignitor A...

Страница 25: ...rated control energizes B6 combustion air inducer S18 combustion air pressure switch closes Once S18 closes a 15 second pre purge follows 6 A92 integrated control energizes R33 ignitor A 20 second war...

Страница 26: ...VE ENERGIZED GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED FLASHES CODE 11 PRESSURE SWITCH CLOSED GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY Seq...

Страница 27: ...IMES FLAME SIGNAL 1 5 MICROAMPS OR GREATER YES YES YES ROLLOUT SWITCH CLOSED LED FLASHES CODE 8 ROLLOT SWITCH OPEN GAS VALVE POWER OFF COMBUSTION AIR INDUCER POWER ON INDOOR BLOWER ON SEQUENCE HOLDS U...

Страница 28: ...OSED LED SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 2 SECOND DELAY COOLING SPEED EAC TERM ENERGIZED COMP...

Страница 29: ...FAN SWITCHED TO COOL SPEED EAC TERM REMAINS ON THERMOSTAT OPENS MANUAL FAN SELECTION MADE AT THERMOSTAT CONTROL G ENERGIZES SYSTEM FAN AT FAN SPEED EAC TERM ENERGIZED NO YES YES NO SYSTEM FAN SWITCHE...

Отзывы: