Lennox EL180DFE Series Скачать руководство пользователя страница 13

Page 13

FIGURE 16

Common Venting Using Metal-Lined Masonry Chimney

4 in. (102 mm)

minimum

MIN. LENGTH -- AS

SHORT AS PRACTICAL

MAX. LENGTH

-- SEE NOTE

BELOW.

SEALED

PERMANENTLY

SEALED FIREPLACE

OPENING

EXTERIOR

CHIMNEY WITH

METAL

LINER

VENT CONNECTOR

NOTE 1 - Refer to the provided venting tables for installations.

OTHER

APPLIANCE

FURNACE

5 ft. (1.5 m)

minimum

DO NOT insulate the space between the liner and the
chimney wall with puffed mica or any other loose gran­
ular insulating material

IMPORTANT

SINGLE appliance venting of a fan‐assisted furnace
into a tile‐lined masonry chimney (interior or outside
wall) is PROHIBITED. The chimney must first be lined
with either type B1 vent or an insulated single wall
flexible vent lining system which has been sized ac­
cording to the provided venting tables and the vent
pipe manufacturer's instructions.

A fan-assisted furnace may be commonly vented into an
existing lined masonry chimney if the following conditions
are met:

S

  The chimney is currently serving at least one drafthood

equipped appliance

S

  The vent connectors and chimney are sized according

to the provided venting tables.

If type B1 double‐wall vent is used inside a chimney, no oth­
er appliance can be vented into the chimney. The outer wall
of type B1 vent pipe must not be exposed to flue products.

A type B1 vent or masonry chimney liner shall terminate
above the roof surface with a listed cap or a listed roof as­
sembly according to the terms of their respective listings
and the vent manufacturer's instructions.

When inspection reveals that an existing chimney is not
safe for the intended purpose, it shall be rebuilt to conform
to nationally recognized standards, lined or relined with
suitable materials, or replaced with a gas vent or chimney
suitable for venting EL180DFE series units. The chimney
passageway must be checked periodically to ensure that it
is clear and free of obstructions.

Do not install a manual damper, barometric draft regulator,
or flue restrictor between the furnace and the chimney.
Never connect a Category I appliance to a chimney that is
servicing a solid-fuel appliance. If a fireplace chimney flue
is used to vent this appliance, the fireplace opening must
be permanently sealed.
A type B or listed chimney lining system that passes
through an unused masonry chimney flue is not considered
to be exposed to the outdoors.

General Venting Requirements

Vent all EL180DFE furnaces according to these instruc­
tions:

 1 - Vent diameter recommendations and maximum allow­

able piping runs are found in the provided venting
tables.

 2 - In no case should the vent or vent connector diameter

be less than the diameter specified in the provided
venting tables.

 3 - The minimum vent capacity determined by the sizing

tables must be less than the low fire input rating and the
maximum vent capacity must be greater than the high
fire input rating.

 4 -

Single appliance vents -

 If the vertical vent or tile‐lined

chimney has a larger diameter or flow area than the
vent connector, use the 

vertical vent diameter

 to de­

termine the 

minimum vent capacity

 and the 

vent

connector diameter

 to determine the 

maximum vent

capacity

. The flow area of the vertical vent, however,

shall not exceed 7 times the flow area of the listed ap­
pliance categorized vent area, drafthood outlet area or
flue collar area unless designed according to approved
engineering methods.

 5 -

Multiple appliance vents -

 The flow area of the largest

section of vertical vent or chimney shall not exceed 7
times the smallest listed appliance categorized vent
area, drafthood outlet area or flue collar area unless de­
signed according to approved engineering methods.

 6 - The entire length of single wall metal vent connector

shall be readily accessible for inspection, cleaning,
and replacement.

 7 - Single appliance venting configurations with zero lat­

eral lengths (table 5) are assumed to have no elbows in
the vent system. For all other vent configurations, the
vent system is assumed to have two 90° elbows. For
each additional 90° elbow or equivalent (for example
two 45° elbows equal one 90° elbow) beyond two, the
maximum capacity listed in the venting table should be
reduced by 10% (0.90 x maximum listed capacity).

 8 - The common venting tables (6 and 7) were generated

using a maximum horizontal vent connector length of
1-1/2 feet (.46 m) for each inch (25 mm) of connector
diameter as follows:

Содержание EL180DFE Series

Страница 1: ...stallation and service must be performed by a licensed professional installer or equivalent service agency or the gas supplier CAUTION As with any mechanical equipment personal injury can result from...

Страница 2: ...4 705 19 1 4 489 6 5 8 168 Right 7 1 8 181 Left 5 3 8 137 Right 2 3 16 56 Left 33 838 19 7 16 494 9 16 14 B Supply Air Supply Air 9 16 14 9 16 14 3 1 8 79 9 16 14 9 16 14 19 7 16 494 EL180DF Model No...

Страница 3: ...nces Adequate clearance must be made around the air open ings into the vestibule area In order to ensure proper unit operation combustion and ventilation air supply must be provided according to the c...

Страница 4: ...maintained during construction D Air filters must be replaced upon construction comple tion D The input rate and temperature rise must be set per the furnace rating plate D One hundred percent 100 out...

Страница 5: ...cient air causes incomplete combustion which can result in carbon monoxide CAUTION Insufficient combustion air can cause headaches nausea dizziness or asphyxiation It will also cause excess water in t...

Страница 6: ...re 2 Air from Outside If air from outside is brought in for combustion and ventila tion the confined space must have two permanent open ings One opening shall be within 12 inches 305 mm of the top of...

Страница 7: ...e square inch 645 mm2 per 4 000 Btu 1 17 kW per hour of the total input rating of all equip ment in the enclosure CHIMNEY OR GAS VENT WATER HEATER OUTLET AIR VENTILATION LOUVERS Each end of attic INLE...

Страница 8: ...the furnace and the floor The base must be or dered separately See table 2 for opening size to cut in floor CAUTION The furnace and downflow combustible flooring base shall not be installed directly o...

Страница 9: ...adversely affect the operation of the safety con trol devices which could result in personal injury or death Install the EL180DFE gas furnace as shipped in the downflow position only Do not install t...

Страница 10: ...alled in a space serviced by an exhaust fan power exhaust fan or other device which may create a negative pressure in the space take care when sizing the inlet air opening The in let air opening must...

Страница 11: ...y other gas fueled appliance i e water heater or carbon monoxide producing device i e wood fireplace is installed When return air is drawn from a room a negative pressure is created in the room If a g...

Страница 12: ...n a lined masonry chimney is used to vent this furnace A chimney with one or more sides exposed to the outside of the structure is considered to be an exterior chimney An exterior masonry chimney that...

Страница 13: ...servicing a solid fuel appliance If a fireplace chimney flue is used to vent this appliance the fireplace opening must be permanently sealed A type B or listed chimney lining system that passes throug...

Страница 14: ...constructed of listed double wall type B vent material or material having equivalent insulation qualities 14 All venting pipe passing through floors walls and ceil ings must be installed with the list...

Страница 15: ...22 339 5 22 65 30 130 39 219 49 330 10 29 59 40 121 51 206 64 315 15 35 53 48 112 61 195 76 301 20 0 0 97 0 202 0 349 0 540 2 10 75 14 149 18 250 20 377 5 21 71 29 143 38 242 47 367 10 28 64 38 133 50...

Страница 16: ...1 21 50 33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 20 1 21 54 33 99 46 157 62 246 2 22 57 34 105 48 167 64 259 3 23 60 35 110 50 176 66 271 30 1 20 62 31 113 45 181...

Страница 17: ...properly step 3 return all doors widows exhaust fans fireplace damp ers and any other gas burning appliances to their pre vious mode of operation 7 If a venting problem is found during any of the prec...

Страница 18: ...0 32 56 985 27 89 873 24 72 791 22 39 728 20 61 677 19 17 635 17 98 600 17 00 2 50 8 2 067 52 502 4020 113 83 2760 78 15 2220 62 86 1900 53 80 1680 47 57 1520 43 04 1400 39 64 1300 36 81 1220 34 55 11...

Страница 19: ...the wires together Secure the excess wire to the existing harness to protect it from damage INTERIOR MAKE UP BOX INSTALLATION Right Side FIGURE 19 MAKE UP BOX Cut the two wire ties to extend power wi...

Страница 20: ...ground leg of the circuit connected to ground or the C terminal Generator Use Voltage Requirements The following requirements must be kept in mind when specifying a generator for use with this equipme...

Страница 21: ...Page 21 FIGURE 20 EL180DFE Schematic Wiring Diagram...

Страница 22: ...lame Sensed without gas valve energized 13 Low Line Voltage Notes Note 1 A Heartbeat is indicated by a Slow Flash 1 sec on 1 sec off repeating Note Error codes are indicated by a Rapid Flash the LED f...

Страница 23: ...er to the unit 4 This furnace is equipped with an ignition device which automatically lights the burners Do not try to light the burners by hand 5 Remove the access panel 6 Move switch on gas valve to...

Страница 24: ...f installed NOTE To obtain accurate reading shut off all other gas appliances connected to meter Supply Pressure Measurement A threaded plug on the inlet side of the gas valve provides access to the s...

Страница 25: ...o adjustment Flame Rollout Switches These manually reset switches are located on the burner box Pressure Switch The pressure switch is located in the heating compartment adjacent to the combustion air...

Страница 26: ...wer access panel 3 Disconnect existing speed tap at integrated control speed terminal NOTE Termination of any unused motor leads must be insulated 4 Place unused blower speed tap on integrated control...

Страница 27: ...ss and to make sure there is no blockage 2 Check unit for proper draft Electrical 1 Check all wiring for loose connections 2 Check for the correct voltage at the furnace furnace operating Correct volt...

Страница 28: ...by a licensed profes sional installer or equivalent service agency or gas supplier Cabinet Parts Heating access panel Blower access panel Top cap Control Panel Parts Transformer Integrated control Do...

Страница 29: ...sted Supply Line Pressure W C ________ 1 VENT EXHAUST PIPE Secure to Unit Elbows Secured to Pipe Vent Pipe Supported 2 Roof Flashing water tight 3 DUCT SYSTEM SUPPLY AIR DUCT Sealed Insulated if neces...

Страница 30: ...___ 5 COOLING MODE INDOOR BLOWER AMPS______ 3 TEMPERATURE DROP Return Duct Temperature _________ Supply Duct Temperature _ _______ 4 5 6 7 DRAIN LINE Leak Free THERMOSTAT Adjusted and Programmed Opera...

Отзывы: