background image

Page 30

DO NOT CHARGE UNIT

(Results of charging at low

temperatures not reliable)

START: Measure outdoor ambient temperature

USE WEIGH‐IN METHOD

Weigh‐in or remove refrigerant
based upon line length

1. Connect gauge set as illustrated in figure 14.

2. Confirm proper airflow across coil using figure 15.
3. Compare unit pressures with charging sticker,  

Normal

Operating Pressures

.

4. Set thermostat to call for heat (must have a cooling

load between 70‐80ºF (21-26ºC).

5. When heat demand is satisfied, set thermostat to call

for cooling.

6. Allow temperatures and pressures to stabilize.

7. Record outdoor ambient temperature:

AMBº =_________

8. Record liquid line temperature:

LIQº = __________

9. Subtract to determine approach (APPº):

LIQº_____ - AMBº _____ = APPº_____

10. Compare results with charging sticker on unit or at the

end of this manual.

64ºF and

BELOW

65ºF

and

ABOVE

 ABOVE or

BELOW

B

APPROACH TXV

If value is greater than shown (high
approach), add refrigerant; if less
than shown (liquid temperature too
close to ambient temperature, low
approach), remove refrigerant.

If refrigerant is added or
removed, retest to confirm
that unit is properly charged.

Figure 18. Using HFC-410A Approach (TXV) Charge Method

DO NOT CHARGE UNIT

(Results of charging at low

temperatures not reliable)

START: Measure outdoor ambient temperature

USE WEIGH‐IN METHOD

Weigh‐in or remove refrigerant
based upon line length

BLOCK OUTDOOR COIL: [sometimes necessary with lower
temperatures] Use cardboard or plastic sheet to restrict the airflow
through the outdoor coil to achieve pressures from 325-375 psig
(2240-2585 kPa).

 

Higher pressures are needed to check charge. Block

equal sections of air intake panels and move coverings sideways until
the liquid pressure is in the above noted ranges.

1. Connect gauge set as illustrated in figure 14.

2. Confirm proper airflow across coil using figure 15.
3. Compare unit pressures with charging sticker,

Normal Operating Pressures

.

4. Set thermostat to call for heat (must have a cooling

load between 70‐80ºF (21-26ºC)

5. Measure outdoor ambient temperature

6. When heat demand is satisfied, set thermostat to call

for cooling

7. Allow temperatures and pressures to stabilize.

NOTE - If necessary, block outdoor coil to maintain
325 - 375 psig.

8. Record liquid line temperature:

LIQº = ______

9. Measure liquid line pressure and use the value to

determine saturation temperature (see table 3):

SATº = ______

10. Subtract to determine subcooling (SCº):

SATº_____ - LIQº _____ = SCº _____

11. Compare results with applicable charging sticker

located on unit access panel or copy located at the
end of this manual. See table 3 for to determine
applicable charging information for specific model.

64ºF and

BELOW

65ºF

and

ABOVE

 ABOVE or

BELOW

C

CARDBOARD OR

PLASTIC SHEETS

SUBCOOLING TXV

If value is

MORE 

than

shown, remove
refrigerant.

MORE 

or

LESS

If value is 

LESS

than shown, add
refrigerant.

If refrigerant is
added or removed,
verify charge using
the 

Approach

Method

.

 

Figure 19. Using HFC-410A Subcooling (TXV) Charge Method

Содержание EL16XC1 Series

Страница 1: ...multiple power supplies TABLE OF CONTENTS Model Number Identification 2 Typical Serial Number Identification 2 Specifications 2 Electrical Data 3 Unit Dimensions 4 Unit Parts Arrangement 5 Operating...

Страница 2: ...de 08 2008 09 2009 10 2010 Month Code A January B February C March 05716 5 or 6 Digit Unique Number Location Code 19 Saltillo Mexico 58 Marshalltown IA 5 Specifications Model Numbers Unit Outdoor Fan...

Страница 3: ...C1 024 25 14 6 10 9 59 3 1 6 825 1 0 1 9 EL16XC1 030 25 17 0 12 8 67 8 1 6 825 1 0 1 9 EL16XC1 036 EL16XC1S036 30 18 0 13 6 79 0 1 6 825 1 0 1 9 EL16XC1 041 30 19 3 14 7 75 0 1 6 825 1 0 1 9 EL16XC1 0...

Страница 4: ...6XC1 030 39 991 30 1 2 775 35 889 13 7 8 352 7 3 4 197 3 1 4 83 27 1 8 689 3 5 8 92 4 1 2 114 20 5 8 524 EL16XC1 036 EL16XC1S036 31 787 30 1 2 775 35 889 13 7 8 352 7 3 4 197 3 1 4 83 27 1 8 689 3 5 8...

Страница 5: ...K1 1 CAPACITOR C12 CONTROL PANEL TYPICAL PLUMBING COPELAND COMPRESSOR DISCHARGE LINE HIGH TEMPERATURE SENSOR LIQUID LINE FILTER DRIER SINGLE FLOW DISCHARGE LINE HIGH TEMPERATURE SENSOR COMPRESSOR HARN...

Страница 6: ...risks rounding or breaking off the wrench or stripping the valve stem recess See the Lennox Service and Application Notes C 08 1 for further details and information IMPORTANT To prevent stripping of t...

Страница 7: ...6 7 8 9 10 11 12 1 12 TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriat...

Страница 8: ...e unit s sound level registered from the adjacent property not from the installation property Install the unit as far as possible from the property line When possible do not install the unit directly...

Страница 9: ...f two 2 degrees or two inches per five feet 50 mm per 1 5 m away from building structure MOUNTING SLAB BUILDING STRUCTURE GROUND LEVEL Outside Unit Placement Slab Mounting at Ground Level SAME FASTENE...

Страница 10: ...n the direction of prevailing winds NOTICE Roof Damage This system contains both refrigerant and oil Some rubber roofing material may absorb oil and cause the rubber to swell when it comes into contac...

Страница 11: ...E AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE WHILE INSTALLING PANEL PREFERRED ANGLE FOR INSTALLATION ANGLE MAY BE TOO EXTREME HOLD DOOR FIRMLY TO THE HINGED SIDE TO MAINTAIN FULLY ENGAGED TABS Det...

Страница 12: ...g torch while pressurized may result in ignition of the refrigerant and oil mixture check the high and low pressures before unbrazing WARNING When using a high pressure gas such as dry nitrogen to pre...

Страница 13: ...OR RAFTER AT 8 FEET 2 43 METERS INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE FLOOR JOIST OR ROOF RAFTER REFRIGERANT LINE SET INSTALLING HORIZONTAL RUNS NOTE Similar installation practices sh...

Страница 14: ...operations only in well ventilated areas Wear gloves and protective goggles or face shield to protect against burns Wash hands with soap and water after handling brazing alloys and flux IMPORTANT Con...

Страница 15: ...Y FROM SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CU...

Страница 16: ...ions for the next step in preparing the unit WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE w...

Страница 17: ...the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD INVERTED HCFC 22 CYLINDER CONTAINS CLEAN HCFC 22 TO BE USED FOR FLUSHING LIQUID LINE SERV...

Страница 18: ...EMBLY WITH BRASS NUT DISTRIBUTOR ASSEMBLY A Remove the field provided fitting that temporary reconnected the liquid line to the indoor unit s distributor assembly B Install one of the provided Teflon...

Страница 19: ...inder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into the l...

Страница 20: ...oor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F When th...

Страница 21: ...diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 24VAC TRANSFORMER Use the transformer provided with the furnace or air handler for low voltage...

Страница 22: ...PERATURE RATING MORE THAN 100 30 METERS 16 35 C MINIMUM WIRE NUTS BLACK 24V CONTROL WIRES YELLOW TIGHTEN WIRE TIE UNIT LOW VOLTAGE CONNECTIONS NOTE DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE...

Страница 23: ...cessary 6 Inspect contactor contacts for pitting or burn marks Replace as necessary 7 Check outdoor fan motor for worn bearings bushings Replace as necessary 8 Inspect and clean outdoor coils if neces...

Страница 24: ...m Fuse or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Discharge Pressure Suction...

Страница 25: ...Page 25 EL16XC1 SERIES Typical Field Wiring...

Страница 26: ...Page 26 Typical Factory Wiring...

Страница 27: ...supply at the disconnect switch The voltage must be within the range listed on the unit s nameplate If not do not start the equipment until you have consulted with the power company and the voltage co...

Страница 28: ...mperature of air entering indoor coil F INDOOR COIL DRY BULB DRY BULB WET BULB B TDrop 19 A Dry bulb Wet bulb F A 72 B 64 C 53 air flow air flow All temperatures are expressed in F 1 Determine the des...

Страница 29: ...t 4 6 m line set 3 8 9 5 mm 3 ounce per 5 85 g per 1 5 m If line length is greater than 15 ft 4 6 m add this amount If line length is less than 15 ft 4 6 m subtract this amount Refrigerant Charge per...

Страница 30: ...OOR COIL sometimes necessary with lower temperatures Use cardboard or plastic sheet to restrict the airflow through the outdoor coil to achieve pressures from 325 375 psig 2240 2585kPa Higher pressure...

Страница 31: ...than shown then REMOVE refrigerant If refrigerant is REMOVED retest to confirm that unit is properly charged MORE or LESS If refrigerant is ADDED retest to confirm that unit is properly charged ABOVE...

Отзывы: