10
COOLING MODE
HEATING MODE
HEATING MODE
COOLING MODE
MODELS
Hot water outlet
temperature (operation)
Hot water inlet
temperature (start)
EAR
Difference hot water
inlet/outlet
Air inlet temperature
0091 TO 0812S
1003 TO 1303S
MODELS
Inlet chilled
water temperature
Outlet chilled
water temperature
EAC / EAR
Air inlet temperature
0091 TO 0431S
1003 TO 1303S
0472 TO 0812S
STANDARD AXIAL FAN UNITS WITHOUT AIR DUCTS
Minimum : +20°C
Minimum : +10 °C
Maximum : +8°C
Minimum :+3°C
Maximum : +43°C
Maximum : +50°C
Maximum : +23°C
Minimum : -10°C (2)
Minimum : +20ºC
Minimum : +10ºC
Maximum : +8ºC
Minimum : +3ºC
Maximum : +43ºC
Maximum : +50ºC
Maximum : +23ºC
Minimum : -10ºC (2)
Minimum : +5°C
Minimum : +10 °C
Maximum : +46°C
Minimum : 0°C (1)
Maximum : +17°C
Maximum : +12°C
Minimum : +5ºC
Minimum : +8ºC
Maximum : +46°C
Minimum : 0°C (1)
Maximum : +17ºC
Maximum : +12ºC
Minimum : +5°C
Minimum : +9 °C
Maximum : +46°C
Minimum : 0°C (1)
Maximum : +17°C
Maximum : +12°C
OUTSIDE THESE VALUES, PLEASE CONSULT US
(2) With the option heating low ambient kit (-15ºC), it is possible the unit operation down to -15ºC
NOTE: With outdoor temperatures below +5°C, add glycol
(1) With the option cooling low ambient kit ( -15ºC), it is possible the unit operation down to -15ºC in EAC units.
NOTE: With outdoor temperatures below +5°C, add glycol.
Water outlet temperature
A
0091S to
0812S
1003S to
1303S
+9ºC
+7ºC
A
0091S to
0812S
1003S to
1303S
+9ºC
+7ºC
-10º
+12º
+44º
0º
A
+46º
ºC
Water outlet temperature
Air inlet temperature
ºC
+5º
-15º
+40º
-7º
OPTION
STD
-10º
+12º
+44º
0º
A
+46º
ºC
Water outlet temperature
Air inlet temperature
ºC
+5º
-15º
+40º
-7º
OPTION
STD
-1º
-10º
23º
20°
50°
42°
ºC
Water outlet temperature
ºC
-15º
STD
OPTION
Air inlet temperature
HEATING MODE
COOLING ONLY UNITS (EAC)
HEAT PUMP UNITS (EAR)
COOLING MODE
1.4.- OPERATION LIMITS
1.- GENERAL CHARACTERISTICS
STANDARD AXIAL FAN UNITS WITH AIR DUCTS
Available static pressure Pa
Maximum ambient temperature ºC
30
50
0091 to 0211S
40
43
AVAILABLE PRESSURE UP TO 50 Pa
(1) With the option heating low ambient kit (-15ºC), it is possible the unit operation down to -15ºC
30
50
0251 to 1303S
38
42
Available static pressure Pa
Minimum ambient temperature ºC (1)
30
50
0091 to 0211S
-6
-8
AVAILABLE PRESSURE UP TO 50 Pa
30
50
0251 to 1303S
-6
-8
Содержание EcoLean EAC0091S
Страница 1: ...INSTALLATION OPERATING MAINTENANCE MANUAL ECOLEAN EAC EAR English 1003...
Страница 2: ......
Страница 41: ......