eCO2Boost XS 3
13
Target discharge temperature T_dis[
℃
]
Ambient temperature T_amb[
℃
]
40
35
30
25
20
15
10
5
0
-5
Ev
ap
o
ra
ti
n
g
te
m
p
er
atu
re
T_e[
℃
]
5
9.86
9.86
9.45
8.78
8.11
7.43
6.76
6.50
6.50
6.50
0
9.86
9.86
9.45
8.78
8.11
7.43
6.76
6.50
6.50
6.50
-5
9.86
9.86
9.45
8.78
8.11
7.43
6.76
6.50
6.50
6.50
-10
9.00
9.00
9.00
8.78
8.11
7.43
6.76
6.50
6.50
6.50
-15
8.00
8.00
8.00
8.00
8.00
7.43
6.76
6.50
6.50
6.50
-20
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
-25
6.00
6.00
6.00
6.00
6.00
6.00
6.00
6.00
6.00
6.00
-30
5.50
5.50
5.50
5.50
5.50
5.50
5.50
5.50
5.50
5.50
-35
5.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
Target discharge temperature T_dis[
℃
]
Ambient temperature T_amb[
℃
]
40
35
30
25
20
15
10
5
0
-5
Ev
ap
o
ra
ti
n
g
te
m
p
er
atu
re
T_e[
℃
]
5
93.3
93.3
89.1
81.8
74.1
64.4
55.5
51.9
51.9
51.9
0
101.6
101.6
97.4
89.9
82.0
72.0
62.9
59.2
59.2
59.2
-5
110.5
110.5
106.1
98.5
90.4
80.2
70.9
67.1
67.1
67.1
-10
110.3
110.3
110.3
107.7
99.4
89.0
79.5
75.6
75.6
75.6
-15
107.6
107.6
107.6
107.6
107.6
98.4
88.7
84.7
84.7
84.7
-20
96.1
96.1
96.1
96.1
96.1
94.5
94.5
94.5
94.5
94.5
-25
98.3
98.3
98.3
98.3
98.3
96.8
96.8
96.8
96.8
96.8
-30
100.4
100.4
100.4
100.4
100.4
98.8
98.8
98.8
98.8
98.8
-35
102.2
102.2
102.2
102.2
102.2
100.7
100.7
100.7
100.7
100.7
1. High pressure target
2. Discharge temperature target
10.3. Check operation value
11.1. CDU parameters change process
ENTERING EACH CYCLE PARAMETER LIST (A, B, & C-PARAMETER)
1.
Press simultaneously 3 button :
▼
+
▲
+ right button (SET) for 3 secs from normal display
2.
”
CLA
” blinking on display (A-parameter)
3.
Press
▼
or
▲
if changing other individual parameter set as “
CLB
” or “
CHC
”
4.
Press right button (SET) if entering each loop parameter set (A00, A01,
…
)
5.
Press
▼
or
▲
if changing parameter set value
6.
Press only right button (SET) for 3 secs if going back to normal display
ENTERING
COMMON PARAMETER LIST (P-PARAMETER)
1.
Press only right button (SET) for 3 secs from normal display
2.
”P00” blinking on display (P-parameter)
3.
Press right button (SET) if moving other P-parameter (P01, P02,
…
)
4.
Press
▼
or
▲
if changing parameter set value
5.
Press only right button (SET) for 3 secs if going back to normal display
SET
Содержание eCO2Boost L
Страница 2: ...eCO2Boost XS 3 2 ...
Страница 4: ...eCO2Boost XS 3 4 2 Product diagram ...
Страница 16: ...eCO2Boost XS 3 16 13 Fault Tree Analysis 13 2 Too much cooling 13 1 No cooling ...