background image

Page 6

4 - 

Make wiring connections as follows:  

• 

Heaters equipped with circuit breakers – 

Connect 

field power supply wiring to circuit breaker(s).  

• 

Heaters equipped with terminal blocks – 

Con-

nect field power supply wiring to terminal block(s).  

• 

Heaters  equipped  with  fuses  (460V,  3-Phase, 

60Hz  and  575V,  3-Phase,  60Hz)  – 

Connect  field 

power supply wiring to fuse block. (An extension 

plate is provided for J-voltage units.) 

Unit Start-Up 

1 -  Replace the air handler access cover.
2 -  Restore power to the unit.
3 -  Set the thermostat heat anticipator to 0.4 amps.
4 -   Align the provided wiring diagram sticker with the 

air handler diagram on the blower housing. Remove 

the backing and affix the sticker to the housing.

5 -  Set the thermostat above room temperature.
6 -  Check the system for normal operation.
7 -  Set the thermostat to desired setting.

FIGURE 10. Installing Fuse Block and Transformer (575V only)

Air Handler Blower Speed Connections 

When using ECB27 heat section, adjust the blower speed 

according to the size of electric heat and air handler unit. 

The 

minimum blower setting

 for each air handler size 

with any heat sections in any application is 

HIGH

. See 

specific  air  handler  installation  instructions  for  blower 

speed adjustment procedure.

Typical Unit Applications 

Refer to figures 11 and 12 for typical field wiring for cooling 

and heat pump applications including an air handler with 

electric heat.

CIRCUIT 1

CIRCUIT

BREAKERS OR

TERMINAL

BLOCK

1

4

7

3

6

9

CB1

CIRCUIT

BREAKER

NOTE - USE COPPER CONDUCTORS ONLY

REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM

OVERCURRENT PROTECTION SIZE
NOTE - ALL REMAINING WIRES FACTORY

INSTALLED

LINE VOLTAGE FIELD

INSTALLED

CLASS 2 VOLTAGE FIELD

INSTALLED NEC/CEC

TO EXTERNAL LOAD 24VAC AT .50 AMP MAXIMUM

THERMOSTAT HEAT ANTICIPATION SETTING 0.4 AMP (ELECTRIC HEAT)

WHEN TWO

STAGE THERMOSTAT IS USED, CONNECT SECOND STAGE

NALS “R” AND “W2”

FACTORY

INSTALLED JUMPER

L3 CONNECTION USED ON (Y VOLTAGE) 3

PHASE ELECTRIC HEATERS

ONLY

FIGURE 11. Typical Field Wiring – Cooling Application with Electric Heat

Содержание ECB27 Series

Страница 1: ...ing Replace all parts and panels before operating Failure to do so can result in death or electrical shock Electric Heat Section The ECB27 series electric heat section provides field in stalled electr...

Страница 2: ...vided in the bag assembly Cabinet Modifications for 460 Volt 3 Ton Models Modifications are necessary when an ECB27 10F G 15F G voltage 460 volt electric heat section is installed in a 460 volt 3 ton...

Страница 3: ...plate for the specific size of electric heat section that you are installing Discard the unused piece of patch plate see figures 5 and 6 6 Secure the patch plate on the air handler access door IN DOW...

Страница 4: ...B ECB27 5CB ECB27 6CB ECB27 8CB ECB27 9CB ECB27 12 5CB ECB27 15CB ECB27 20CB ECB27 25CB ECB27 10CB 3 Ph ECB27 15CB 3 Ph ECB27 20CB 3 Ph ECB27 25CB 3 Ph SIDE OF UNIT DISCARD BREAK AT THIS POINT DISCARD...

Страница 5: ...ith 1 1 2 inch trade size 1 31 32 inch diameter conduit A conduit reducer washer has been provided if you are installing a smaller sized conduit For single point power supply refer to the nameplate on...

Страница 6: ...using ECB27 heat section adjust the blower speed according to the size of electric heat and air handler unit The minimum blower setting for each air handler size with any heat sections in any applicat...

Страница 7: ...PHASE ELECTRIC HEATERS ONLY STATS Y2 USED ONLY WHEN TWO SPEED COMPRESSOR IS USED HP21 COMMON USED ONLY ON SOME THERMOSTATS USING SERVICE LIGHT OPTION S54 WITH SOME ELECTRONIC THERMOSTATS MAY REQUIRE...

Страница 8: ...Page 8 Unit Field Wiring Diagrams FIGURE 13 Typical Unit Diagram Air Handlers with Constant Torque Motors P Voltage 208 230V 1 Phase 60Hz...

Страница 9: ...Page 9 FIGURE 14 Typical Unit Diagram Air Handlers with PSC Non Communicating Motors P Voltage 208 230V 1 Phase 60Hz...

Страница 10: ...Page 10 FIGURE 15 Typical Unit Diagram Air Handlers with Variable Speed Communicating Motors P Voltage 208 230V 1 Phase 60Hz...

Страница 11: ...Page 11 FIGURE 16 Typical Unit Diagram Air Handlers with Constant Torque Motors G Voltage 460V 3 phase 60Hz...

Страница 12: ...ECB27 5 CB P 538002 01 ECB27 6 CB P 538002 01 ECB27 8 CB P 538003 01 ECB27 9CB P 538004 01 ECB27 12 5CB P 538005 01 ECB27 15CB P 538005 01 ECB27 20CB P 538006 01 ECB27 25CB P 538010 01 ECB27 8 Y 53800...

Отзывы: