www.lennoxemea.com
e-MovAir-IOM-20.04-EN
4
INTRODUCTION
EMC DIRECTIVE COMPLIANCE
WARNING:
This equipment is a “B class” according EMC Directive. In an industrial environment, this device can
create radio electrical noise. In this case, the owner can be asked to take appropriated actions.
The units meet the following hardest environments standards:
• EN 61000-6-3: program for environment residential, commercial and light industry.
• EN 61000-6-2: immunity for industrial environments
This applies to all machine installed with nominal amps below <75A:
• The short-circuit rate Rsce=33 is defined in the EN61000-3-12 standard relative to the
harmonics readings on the supply network. The appliances compliant with the harmonic
current limits equivalent to Rsce=33 can be connected in whatever connection point of the
main supply system.
• The maximal allowable impedance of the main supply system Zmax=0.30 Ω for units C,D,E,E+
and Zmax=0.143Ω for units F,G,H is defined by EN 61000-3-11 standard relative to the voltage
variation, fluctuation and flicker readings. The connection to the supply is a conditional
connection submitted to the preliminary agreement of the power supply local provider.
The differences between the various machines are only related to the power of the compressors and
equipment that are associated. For conducted and radiated emission and immunity, these differences
do not alter the results.
F-GAS REGULATION
PLEASE READ THE SAFETY DATA SHEET OF THE REFRIGERANT BEFORE ANY INTERVENTION OR
INSTALLATION OF THE MACHINE.
Operators of refrigeration equipment’s must comply with the obligations defined in
• Regulation on Fluorinated greenhouse gases (F Gas)
• Regulation on substances that deplete the ozone layer
Non-compliance with these requirements is an offence and liable of financial penalties.
Moreover, in case of problem it is mandatory to prove to the insurance company that the equipment
complies with the F gas Regulation
WARRANTY
The warranty of the unit is subject to the warranty definitions as agreed upon in the order. It is expected
that the design and installation of the unit utilizes good working practices. The warranty will be legally
null and void if:
• Service and maintenance have not been executed in accordance with the regulations; repairs
have not been carried out by LENNOX personnel or have been implemented without prior
written permission by LENNOX.
• Modifications have been made to the equipment without prior written permission by LENNOX.
• Settings and protections have been modified without prior written permission by LENNOX.
• Non-original or other than the prescribed refrigerants or lubricants are used.
• The equipment has not been installed and/or connected in accordance with the installation
instructions.
• The equipment is being used improperly, incorrectly, negligently or not in accordance with
its nature and/or purpose.