(
P Q E
)
(
P Q E
)
6.3.1 Communication wiring between the indoor and outdoor
units
The indoor and outdoor units communicate via the RS485 serial port.
The communication wiring between the indoor and outdoor units should
connect one unit after another in a daisy chain from the outdoor unit to the
final indoor unit, and the shielded layer must be properly grounded, and a
build-out resistor must be added to the last indoor unit to enhance the stability
of the communication system (see Figure 6.6).
Incorrect wiring such as a star connection or a closed ring will cause instability
of the communication system and system control anomalies.
Use a three core shielded wire (greater than or equal to 0.75 mm
2
) for the
communication wiring between the indoor and outdoor units. Make sure the
wiring is connected correctly. The connecting lead for this communication
wire must come from the master outdoor unit.
All shielded wiring in the network are interconnected, and will eventually
connect to earth at the same point
" "
.
Only the last indoor unit requires adding the build-out resistor at P and Q.
(open)
Indoor and outdoor
units Communication
wire
Connecting the shielded layer of the shielded wire
(Connect the shielded end of the shielded wire to the electronic
controller box sheet metal " " here)
Signalling line between outdoor units
Outdoor unit
P
Q
Figure 6.6
The wired controller and the indoor unit can be connected in different manners,
depending on the forms of communication.
1) For a bidirectional communication mode:
w
Use 1 wired controller to control 1 indoor unit or 2 wired controllers
(one master and one slave controller) to control 1 indoor unit (see Figure 6.7);
w
Use 1 wired controller to control multiple indoor units or 2 wired controllers
(one master and one slave controller) to control multiple indoor units
(see Figure 6.8);
6.3.2 Communication wiring between the indoor unit and wired
controller
Matching resistors
8
FLA: Full Load Amps
Abbreviations:
MCA: Minimum Circuit Amps
kW: Rated motor output
MFA: Maximum Fuse Amps
IFM: Indoor Fan Motor
Table 6.1
Model
2.2-8.0kW
Power
supply
220-240V~50Hz
220-240V~50/60Hz
Communication wire between
Shielded
3×AWG16-AWG18
Shielded
AWG16-AWG20
Field fuses
15A
Phase
Volt and frequency
1-phase
Table 6.2 Indoor units electrical characteristics
Capacity
IFM
Hz
Volts
MCA
MFA
kW
FLA
2.8kW
2.2kW
50
50/60
220 - 240
15
0.49
0.55
0.55
0.55
0.85
1.4
1.4
15
4.5kW
15
5.6kW
15
7.1kW
15
8.0kW
15
15
Power supply
3.6kW
0.1
0.39
0.1
0.44
0.1
0.44
0.1
0.44
0.1
0.68
0.1
1.1
0.1
1.1
Power supply
Breakers with
current leakage
All-pole disconnection
device with leakage
protector
L N
Indoor unit
Pull box
Indoor unit
Indoor unit
Indoor unit
Pull box
Pull box
220-240V~50/60Hz
220-240V~50Hz
6.3 Communication Wiring
Refer to Table 6.1 for the specifications of the power cord and communication
wire. A wiring capacity that is too small will cause electrical wiring overheating,
and lead to accidents when the unit burns and becomes damaged.
Use only shielded wires for the communication wiring. Any other type of wires
may produce a signal interference that will cause the units to malfunction.
Do not carry out electrical works like welding with the power on.
Do not bind the refrigerant piping, power cords and communication wiring
together. When the power cord and communication wiring are parallel, the
distance between the two lines must be 300 mm or more in order to prevent
signal source interference.
Communication wiring must not form a closed loop.
:
Copper wire
Proper power wiring connections
Figure 6.3
Figure 6.4
+
Power cord
Insulation tube
Circular wiring
terminal
Figure 6.5
6.2 Electrical Wiring Specifications
Warning
indoor and outdoor units
Communication wire between
indoor unit and wired controller *
Refer to local laws and regulations when deciding on the dimen-
sions for the power cords and wiring. Get a professional to select
and install the wiring.
Indoor unit
* Please refer to the corresponding wired controller manual for the wired
controller wiring.
3. Select circuit breaker that having a contact separation in all poles
not less than 3 mm providing full disconnection
,
where MFA is
used to select the current circuit breakers and residual current
operation breakers:
1. Select the wire diameters( minimum value) individually for each
unit based on the table 6.3.
2. Maximum allowable voltage range variation between phases is
2%.
Table 6.3
Nominal cross-sectional area (mm
2
)
>3
>6
>10
>16
>25
>32
>50
and
and
and
and
and
and
and
≤3
≤6
≤10
≤16
≤25
≤32
≤50
≤63
0.75
1
1.5
2.5
4
6
10
and
and
and
and
and
and
and
1
1.5
2.5
4
6
10
16
0.5 and 0.75
Flexible cords
Cable for fixed wiring
4
10
to
1.5
4
to
1
2.5
to
1
2.5
to
1
2.5
to
2.5
6
to
6
16
to
10
25
to
Rated current
of appliance
(
A
)
Содержание e-Lite
Страница 1: ...LV FS 2DC IOM 20 04 E e Lite FLOOR STANDING UNIT Installation and Operation Manual...
Страница 2: ......
Страница 21: ......
Страница 22: ......
Страница 23: ......