Lennox Dave Lennox Signature SL28XCV Скачать руководство пользователя страница 4

Page 4

SETTING THE UNIT (Continued) –  

Unit Placement 

NOTICE!

Roof Damage!

This system contains both refrigerant and oil. Some 

rubber roofing material may absorb oil, causing the 

rubber to degrade. Failure to follow this notice could 

result in damage to roof surface.

 IMPORTANT

This unit must be matched with an indoor coil as 

specified with AHRI. For AHRI Certified system match-

ups and expanded ratings, visit www.LennoxPros.com

Coils previously charged with HCFC-22 must be flushed.

 WARNING

To prevent personal injury, as well as damage to panels, 

unit or structure, observe the following:
While installing or servicing this unit, carefully stow all 

removed panels so that the panels will not cause injury 

to personnel, objects or nearby structures. Also, take 

care to store panels where they will not be subject to 

damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any 

weather conditions (especially wind) that may cause 

panels to be blown around and damaged.

 IMPORTANT

Exhaust vents from dryers, water heaters and furnaces 

should be directed away from the outdoor unit. Prolonged 

exposure to exhaust gases and the chemicals contained 

within them may cause condensation to form on the steel 

cabinet and other metal components of the outdoor unit. 

This will diminish unit performance and longevity

NOTICE!

Charging information is given on the charging 

procedure sticker on the unit access panel. For more in-

depth information, consult the Installation and Service 

Procedures manual on LennoxPros.com or through the 

Technical Support department at 800-453-6669.

 CAUTION

As with any mechanical equipment, contact with sharp 

sheet metal edges can result in personal injury. Take 

care while handling this equipment and wear gloves and 

protective clothing.

REFRIGERANT PIPING 

 IMPORTANT

If this unit is being matched with an approved line set 

or indoor unit coil that was previously charged with 

mineral oil, or if it is being matched with a coil which 

was manufactured before January of 1999, the coil 

and line set must be flushed prior to installation. Take 

care to empty all existing traps. Polyvinyl ether (PVE) 

oils are used in Lennox units charged with HFC-410A 

refrigerant. Residual mineral oil can act as an insulator, 

preventing proper heat transfer. It can also clog the 

expansion device and reduce system performance and 

capacity.  Failure  to  properly  flush  the  system  per  this 

instruction and the detailed Installation and Service 

Procedures manual will void the warranty.

Flush the existing line set per the following instructions. 

For more information, refer to the Installation and Service 

Procedures manual available on LennoxPros.com. CAU-

TION - DO NOT attempt to flush and re-use existing line 

sets or indoor coil when the system contains contaminants 

(i.e., compressor burn out). 
Polyvinyl ether (PVE) oil is used in the SL28XCV com-

pressors. For installations of the SL28XCV unit with re-

frigerant lines or coils previously charged with R410A and 

POE oil, Lennox recommends flushing the existing lines 

and coil with R410A refrigerant to remove excess POE oil 

that may be in the system.
If a new line set is being installed, size the piping per table 1.

NOTE

 - 

When installing refrigerant lines longer than 50 

feet, refer to the Refrigerant Piping Design and Fabrica-

tion Guidelines manual available on LennoxPros.com 

(Corp. 9351-L9), or contact the Technical Support Depart-

ment Product Application group for assistance.

NOTE

 - 

For new or replacement line set installation, refer 

to Service and Application Note - Corp. 9112-L4 (C-91-4)

 IMPORTANT

The Clean Air Act of 1990 bans the intentional venting of 

refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. 

Approved methods of recovery, recycling or reclaiming 

must be followed. Fines and/or incarceration may be 

levied for noncompliance.

 WARNING

When using a high pressure gas such as 

nitrogen to pressurize a refrigeration or air 

conditioning system, use a regulator that can 

control the pressure down to 1 or 2 psig (6.9 

to 13.8 kPa).

Содержание Dave Lennox Signature SL28XCV

Страница 1: ...NTROL PANEL ACCESS LOCATION 6 152 36 914 12 305 30 762 24 610 LINE SET CONNECTIONS ACCESS PANEL REAR VIEW OF UNIT 48 1219 MINIMUM CLEARANCE BETWEEN TWO UNITS CLEARANCE ON ALL SIDES INCHES MILLIMETERS...

Страница 2: ...E FOR EXTRA STABILITY Deck Top Mounting Elevated Slab Mounting using Feet Extenders Stabilizing Unit on Uneven Surfaces WOOD OR PLASTIC SLAB NO PLASTIC ANCHOR HOLE DRILL 1 8 INSTALL UNIT LEVEL OR IF O...

Страница 3: ...8XCV 024 47 00 35 50 39 40 35 00 15 97 SL28XCV 036 47 00 35 50 39 40 35 00 15 97 SL28XCV 048 47 00 35 50 39 40 35 00 15 97 SL28XCV 060 47 00 35 50 39 40 35 00 15 97 4 5 8 117 BASE WITH ELONGATED LEGS...

Страница 4: ...ly charged with mineral oil or if it is being matched with a coil which was manufactured before January of 1999 the coil and line set must be flushed prior to installation Take care to empty all exist...

Страница 5: ...ths may be more or less depending on remaining system design factors Maximum linear actual length 150 feet Maximum linear liquid lift 60 feet NOTE Maximum lifts are dependent on total length number of...

Страница 6: ...50 41 31 22 1 2 25 50 60 60 60 60 3 8 25 50 36 22 8 NR 1 2 25 50 60 60 60 59 Shaded rows indicate rated liquid line size A Find your unit on the left side of the table B Start with the rated liquid li...

Страница 7: ...t the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid r...

Страница 8: ...t nitrogen flow will have an exit point NITROGEN HIGH LOW B A C PIPING PANEL REMOVAL PREPARING LINE SET CAP AND CORE REMOVAL Remove piping panel to access service valves Cut ends of the refrigerant li...

Страница 9: ...S POINT FLAME AWAY FROM SERVICE VALVE LIQUID LINE WATER SATURATED CLOTHS WATER SATURATED CLOTHS 6A 6B SUCTION VAPOR SERVICE PORT MUST BE OPEN AND MOVED TO ALLOW EXIT POINT FOR NITROGEN FLOW IMPORTANT...

Страница 10: ...bulb insulation is required if mountedexternal to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSEMBLY 3 Instal...

Страница 11: ...psig 1034 kPa Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify th...

Страница 12: ...nifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned to deliver liquid...

Страница 13: ...ct Specifications bulletin EHB and unit rating plate WARNING ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit insta...

Страница 14: ...AT WIRING CONNECTION PUSH BUTTON 7 SEGMENT DISPLAY PUMP DOWN WHEN UNIT IS IN PUMP DOWN MODE Pd WILL BE DISPLAYED ON 7 SEGMENT TO ACTIVATE PUMP DOWN MODE THE CONTROL MUST BE IN THE IDLE STATE AND THE P...

Страница 15: ...Page 15 FIGURE 10 Typical Field Wiring...

Страница 16: ...TAPED 2 WRAPS MIN MACHINE TIGHTENED ARE NOT TAPED INTERNATIONAL UNITS M T VOLTAGE ARE ALWAYS TAPED 2 WRAPS MIN 6 REFER TO COMPRESSOR FOR ACTUAL TERMINAL ARRANGEMENT 7 WIRES WILL BE SHOWN GOING TO PRO...

Страница 17: ...d also include an additional wire that should be connected on each end to the C terminal as shown in the figure below Any excess high voltage field wiring should be trimmed and secured away from any l...

Страница 18: ...art Hub C i i R HD Display Subbase or Mag Mount COMMBUS A B ACC1 ACC2 SL28XCV Outdoor Unit SL28XCV RAST 6 Pin Connectors OATS Optional DATS Optional B A O Y1 FIGURE 12 SL28XCV with iComfort S30 Commun...

Страница 19: ...ANIFOLD GAUGE SET AND SERVICE VALVES The liquid and vapor line service valves are used for re moving refrigerant flushing leak testing evacuating checking charge and charging Each valve is equipped wi...

Страница 20: ...e table below Then add the additional refrigerant charge to the system Charge should be checked and adjusted using the ta bles provided on the charging procedure sticker on the unit access panel Detai...

Страница 21: ...shrubbery away from the unit and periodically check for debris which collects around the unit During the winter months keep the snow level below the louvered panels NOTE The filter and all access pan...

Страница 22: ...Pour water in pans to confirm proper drainage from the pan through to the outlet of the pipe Clean or replace as necessary 5 Inspect and clean indoor coil if necessary 6 Inspect the condition of the...

Страница 23: ...y Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and approach tem...

Отзывы: