UNIT START-UP 

 IMPORTANT

If unit is equipped with a crankcase heater, it should 

be energized 24 hours before unit start-up to prevent 

compressor damage as a result of slugging.

1 -  Rotate fan to check for binding. 
2 - 

 Inspect  all  factory-  and  field-installed  wiring  for 

loose connections. 

3 -   After evacuation is complete, open the liquid line and 

vapor line service valve stems to release the refrigerant 

charge (contained in outdoor unit) into the system. 

4 -   Replace the stem caps and tighten to the value 

listed in table 2. 

5 -   Check voltage supply at the disconnect switch. The 

voltage must be within the range listed on the unit’s 

nameplate. If not, do not start the equipment until 

you have consulted with the power company and 

the voltage condition has been corrected. 

6 -   Connect manifold gauge set for testing and charging 

or use the Lennox Dealer Setup App to monitor the 

pressures and temperatures of the refrigeration 

system. 

7 -   Turn on power to the indoor unit and close the 

outdoor unit disconnect switch to start the unit.   

Start-up and testing should be performed with the 

unit operating at the maximum cooling capacity 

(100% capacity). The unit can be operated at 

maximum capacity by entering the test mode at 

the thermostat or using the Lennox Dealer Setup 

App. The S30 Test Mode can be selected by going 

to Menu> Advanced Settings> View Dealer Control 

Center> Test and then select Cooling - Maximum 

Rate Test. 

8 -   Recheck voltage while the unit is running. Power 

must be within range shown on the unit nameplate. 

9 - 

 Check  system  for  sufficient  refrigerant  using  the 

procedures outlined under 

Checking Refrigerant 

Charge. 

OPERATING MANIFOLD GAUGE SET AND SERVICE 

VALVES 

The liquid and vapor line service valves are used for re-

moving  refrigerant,  flushing,  leak  testing,  evacuating, 

checking charge and charging. 
Each valve is equipped with a service port which has a 

factory-installed valve stem. Figures 14 and 15 provide 

information on how to access and operate both angle- and 

ball-type service valves. 

Torque Requirements 

When servicing or repairing heating, ventilating and air 

conditioning components, ensure the fasteners are appro-

priately tightened. Table 2 lists torque values for fasteners.

TABLE 1  –   TORQUE REQUIREMENTS

Parts

Recommended Torque

Service valve cap

8 ft.-lb.

11 NM

Sheet-metal screws

16 in.-lb.

2 NM

Machine screws #10

28 in.-lb.

3 NM

Compressor bolts

90 in.-lb.

10 NM

Gauge port seal cap

8 ft.-lb.

11 NM

 IMPORTANT

To prevent stripping of the various caps used, the 

appropriately  sized  wrench  should  be  used  and  fitted 

snugly over the cap before tightening.

Using Manifold Gauge Set 

When checking the system charge, only use a manifold 

gauge set that features low loss anti-blow back fittings. 

Manifold gauge set used with HFC-410A refrigerant sys-

tems must be capable of handling the higher system oper-

ating pressures. The gauges should be rated for use with 

pressures of 0 - 800 psig on the high side and a low side 

of 30" vacuum to 250 psig with dampened speed to 500 

psi. Gauge hoses must be rated for use at up to 800 psig 

of pressure with a 4000 psig burst rating.

BALL (SHOWN

CLOSED)

SERVICE PORT

CORE

TO 

OPEN,

 ROTATE STEM

COUNTERCLOCKWISE 90°.

TO 

CLOSE, 

ROTATE STEM

CLOCKWISE 90°.

SERVICE PORT

SERVICE PORT

CAP

STEM CAP

VALVE

STEM

1 - Remove stem cap with an appropriately sized wrench.
2 - Use an appropriately sized wrench to open. To open valve, rotate

stem counterclockwise 90°. To close, rotate stem clockwise 90°.

OPERATING BALL-TYPE SERVICE VALVE

FIGURE 13 

Содержание Dave Lennox Signature SL28XCV

Страница 1: ...NTROL PANEL ACCESS LOCATION 6 152 36 914 12 305 30 762 24 610 LINE SET CONNECTIONS ACCESS PANEL REAR VIEW OF UNIT 48 1219 MINIMUM CLEARANCE BETWEEN TWO UNITS CLEARANCE ON ALL SIDES INCHES MILLIMETERS...

Страница 2: ...E FOR EXTRA STABILITY Deck Top Mounting Elevated Slab Mounting using Feet Extenders Stabilizing Unit on Uneven Surfaces WOOD OR PLASTIC SLAB NO PLASTIC ANCHOR HOLE DRILL 1 8 INSTALL UNIT LEVEL OR IF O...

Страница 3: ...8XCV 024 47 00 35 50 39 40 35 00 15 97 SL28XCV 036 47 00 35 50 39 40 35 00 15 97 SL28XCV 048 47 00 35 50 39 40 35 00 15 97 SL28XCV 060 47 00 35 50 39 40 35 00 15 97 4 5 8 117 BASE WITH ELONGATED LEGS...

Страница 4: ...ly charged with mineral oil or if it is being matched with a coil which was manufactured before January of 1999 the coil and line set must be flushed prior to installation Take care to empty all exist...

Страница 5: ...ths may be more or less depending on remaining system design factors Maximum linear actual length 150 feet Maximum linear liquid lift 60 feet NOTE Maximum lifts are dependent on total length number of...

Страница 6: ...50 41 31 22 1 2 25 50 60 60 60 60 3 8 25 50 36 22 8 NR 1 2 25 50 60 60 60 59 Shaded rows indicate rated liquid line size A Find your unit on the left side of the table B Start with the rated liquid li...

Страница 7: ...t the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid r...

Страница 8: ...t nitrogen flow will have an exit point NITROGEN HIGH LOW B A C PIPING PANEL REMOVAL PREPARING LINE SET CAP AND CORE REMOVAL Remove piping panel to access service valves Cut ends of the refrigerant li...

Страница 9: ...S POINT FLAME AWAY FROM SERVICE VALVE LIQUID LINE WATER SATURATED CLOTHS WATER SATURATED CLOTHS 6A 6B SUCTION VAPOR SERVICE PORT MUST BE OPEN AND MOVED TO ALLOW EXIT POINT FOR NITROGEN FLOW IMPORTANT...

Страница 10: ...bulb insulation is required if mountedexternal to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSEMBLY 3 Instal...

Страница 11: ...psig 1034 kPa Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify th...

Страница 12: ...nifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned to deliver liquid...

Страница 13: ...ct Specifications bulletin EHB and unit rating plate WARNING ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit insta...

Страница 14: ...AT WIRING CONNECTION PUSH BUTTON 7 SEGMENT DISPLAY PUMP DOWN WHEN UNIT IS IN PUMP DOWN MODE Pd WILL BE DISPLAYED ON 7 SEGMENT TO ACTIVATE PUMP DOWN MODE THE CONTROL MUST BE IN THE IDLE STATE AND THE P...

Страница 15: ...Page 15 FIGURE 10 Typical Field Wiring...

Страница 16: ...TAPED 2 WRAPS MIN MACHINE TIGHTENED ARE NOT TAPED INTERNATIONAL UNITS M T VOLTAGE ARE ALWAYS TAPED 2 WRAPS MIN 6 REFER TO COMPRESSOR FOR ACTUAL TERMINAL ARRANGEMENT 7 WIRES WILL BE SHOWN GOING TO PRO...

Страница 17: ...d also include an additional wire that should be connected on each end to the C terminal as shown in the figure below Any excess high voltage field wiring should be trimmed and secured away from any l...

Страница 18: ...art Hub C i i R HD Display Subbase or Mag Mount COMMBUS A B ACC1 ACC2 SL28XCV Outdoor Unit SL28XCV RAST 6 Pin Connectors OATS Optional DATS Optional B A O Y1 FIGURE 12 SL28XCV with iComfort S30 Commun...

Страница 19: ...ANIFOLD GAUGE SET AND SERVICE VALVES The liquid and vapor line service valves are used for re moving refrigerant flushing leak testing evacuating checking charge and charging Each valve is equipped wi...

Страница 20: ...e table below Then add the additional refrigerant charge to the system Charge should be checked and adjusted using the ta bles provided on the charging procedure sticker on the unit access panel Detai...

Страница 21: ...shrubbery away from the unit and periodically check for debris which collects around the unit During the winter months keep the snow level below the louvered panels NOTE The filter and all access pan...

Страница 22: ...Pour water in pans to confirm proper drainage from the pan through to the outlet of the pipe Clean or replace as necessary 5 Inspect and clean indoor coil if necessary 6 Inspect the condition of the...

Страница 23: ...y Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and approach tem...

Отзывы: