background image

©2020 Lennox Industries Inc. 

Dallas, Texas, USA

Page 1

General 

This SL28XCV outdoor air conditioner 

with all-aluminum 

coil

 is designed for use with HFC-410A refrigerant only. 

These instructions are intended as a general guide and do 

not supersede local codes in any way. Consult authorities 

having jurisdiction before installation.

INSTALLATION 

INSTRUCTIONS

AIR CONDITIONER 

508022-01

3/2020

Dave Lennox 

Signature

®

  

Collection SL28XCV System

 WARNING

Improper installation, adjustment, alteration, service 

or maintenance can cause property damage, personal 

injury or loss of life. Installation and service must  be 

performed by a licensed professional HVAC installer or 

equivalent, or service agency.

IMPORTANT:

 Special procedures are required for clean-

ing the all-aluminum coil in this unit. See page 20 in this 

instruction for information. 

CONTROL

PANEL ACCESS

LOCATION

6 (152)

36 (914)

12 (305)

30 (762)

24

(610)

LINE SET

CONNECTIONS

ACCESS

PANEL

REAR VIEW OF UNIT

48 (1219)

MINIMUM CLEARANCE BETWEEN TWO UNITS

CLEARANCE ON ALL SIDES — INCHES (MILLIMETERS)

MINIMUM CLEARANCE

ABOVE UNIT

NOTES:

Clearance to access panel must be 30

inches (762mm).
Clearance to  one  of  the  other  three

sides must be 36 inches (914mm).
Clearance to one of the remaining two

sides may be 12 inches (305mm) and

the  final  side  may  be  6  inches

(152mm).

Note: Dimensions are not to scale.

THIS UNIT IS A INTEGRAL COMPONENT OF A SYSTEM THAT

WILL  REQUIRE  A  COMMUNICATING   THERMOSTAT  AND

COMMUNICATING  AIR HANDLER OR FURNACE.

SL28XCV

Communicating air handler 

or furnace

Communicating 

thermostat

SETTING THE UNIT – Clearances

THIS MANUAL MUST BE LEFT WITH THE  

HOMEOWNER FOR FUTURE REFERENCE

PACKING LIST

OUTDOOR UNIT

WARRANTY

CARD

GROMMETS (2) BUSHING (1)

RAST 6-PIN

CONNECTOR (1)

This unit must be installed with an approved indoor air 

handler or coil. For AHRI Certified system match-ups and 

expanded ratings, visit www.LennoxPros.com.

Содержание Dave Lennox Signature SL28XCV

Страница 1: ...NTROL PANEL ACCESS LOCATION 6 152 36 914 12 305 30 762 24 610 LINE SET CONNECTIONS ACCESS PANEL REAR VIEW OF UNIT 48 1219 MINIMUM CLEARANCE BETWEEN TWO UNITS CLEARANCE ON ALL SIDES INCHES MILLIMETERS...

Страница 2: ...E FOR EXTRA STABILITY Deck Top Mounting Elevated Slab Mounting using Feet Extenders Stabilizing Unit on Uneven Surfaces WOOD OR PLASTIC SLAB NO PLASTIC ANCHOR HOLE DRILL 1 8 INSTALL UNIT LEVEL OR IF O...

Страница 3: ...8XCV 024 47 00 35 50 39 40 35 00 15 97 SL28XCV 036 47 00 35 50 39 40 35 00 15 97 SL28XCV 048 47 00 35 50 39 40 35 00 15 97 SL28XCV 060 47 00 35 50 39 40 35 00 15 97 4 5 8 117 BASE WITH ELONGATED LEGS...

Страница 4: ...ly charged with mineral oil or if it is being matched with a coil which was manufactured before January of 1999 the coil and line set must be flushed prior to installation Take care to empty all exist...

Страница 5: ...ths may be more or less depending on remaining system design factors Maximum linear actual length 150 feet Maximum linear liquid lift 60 feet NOTE Maximum lifts are dependent on total length number of...

Страница 6: ...50 41 31 22 1 2 25 50 60 60 60 60 3 8 25 50 36 22 8 NR 1 2 25 50 60 60 60 59 Shaded rows indicate rated liquid line size A Find your unit on the left side of the table B Start with the rated liquid li...

Страница 7: ...t the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid r...

Страница 8: ...t nitrogen flow will have an exit point NITROGEN HIGH LOW B A C PIPING PANEL REMOVAL PREPARING LINE SET CAP AND CORE REMOVAL Remove piping panel to access service valves Cut ends of the refrigerant li...

Страница 9: ...S POINT FLAME AWAY FROM SERVICE VALVE LIQUID LINE WATER SATURATED CLOTHS WATER SATURATED CLOTHS 6A 6B SUCTION VAPOR SERVICE PORT MUST BE OPEN AND MOVED TO ALLOW EXIT POINT FOR NITROGEN FLOW IMPORTANT...

Страница 10: ...bulb insulation is required if mountedexternal to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSEMBLY 3 Instal...

Страница 11: ...psig 1034 kPa Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify th...

Страница 12: ...nifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned to deliver liquid...

Страница 13: ...ct Specifications bulletin EHB and unit rating plate WARNING ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit insta...

Страница 14: ...AT WIRING CONNECTION PUSH BUTTON 7 SEGMENT DISPLAY PUMP DOWN WHEN UNIT IS IN PUMP DOWN MODE Pd WILL BE DISPLAYED ON 7 SEGMENT TO ACTIVATE PUMP DOWN MODE THE CONTROL MUST BE IN THE IDLE STATE AND THE P...

Страница 15: ...Page 15 FIGURE 10 Typical Field Wiring...

Страница 16: ...TAPED 2 WRAPS MIN MACHINE TIGHTENED ARE NOT TAPED INTERNATIONAL UNITS M T VOLTAGE ARE ALWAYS TAPED 2 WRAPS MIN 6 REFER TO COMPRESSOR FOR ACTUAL TERMINAL ARRANGEMENT 7 WIRES WILL BE SHOWN GOING TO PRO...

Страница 17: ...d also include an additional wire that should be connected on each end to the C terminal as shown in the figure below Any excess high voltage field wiring should be trimmed and secured away from any l...

Страница 18: ...art Hub C i i R HD Display Subbase or Mag Mount COMMBUS A B ACC1 ACC2 SL28XCV Outdoor Unit SL28XCV RAST 6 Pin Connectors OATS Optional DATS Optional B A O Y1 FIGURE 12 SL28XCV with iComfort S30 Commun...

Страница 19: ...ANIFOLD GAUGE SET AND SERVICE VALVES The liquid and vapor line service valves are used for re moving refrigerant flushing leak testing evacuating checking charge and charging Each valve is equipped wi...

Страница 20: ...e table below Then add the additional refrigerant charge to the system Charge should be checked and adjusted using the ta bles provided on the charging procedure sticker on the unit access panel Detai...

Страница 21: ...shrubbery away from the unit and periodically check for debris which collects around the unit During the winter months keep the snow level below the louvered panels NOTE The filter and all access pan...

Страница 22: ...Pour water in pans to confirm proper drainage from the pan through to the outlet of the pipe Clean or replace as necessary 5 Inspect and clean indoor coil if necessary 6 Inspect the condition of the...

Страница 23: ...y Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and approach tem...

Отзывы: