Power Loss/Recovery

Thermostat memory is retained for a minimum of 24 hours
during a power loss (includes retention of programmed
temperature setpoint, heat/cool and fan mode settings, fil-
ter reminder status, and equipment protection timers). Af-
ter 24 hours of power loss, programmed settings will be
lost and replaced with default settings.

IMPORTANT

Power must be applied for at least six consecutive
hours prior to a power loss in order for memory to
be retained for the specified time.

LCD Backlight

Activated for 8 seconds when any key is pressed.

NOTE − During an electrical storm or similar disturbance,
the backlight may activate for a few seconds. This is nor-
mal and will no longer occur after the electrical disturbance
has passed.

Thermostat Operating Conditions

35°F to 105°F, 5% to 90% RH

Thermostat Storage Conditions

−40°F to 185°F, 5% to 95% RH

Thermostat Output Table

Table 2 depicts the L3011C thermostat output states for
various input conditions.

Table 2. L3011C Thermostat Outputs

Condition

W1

Y1

G

Gas Heat, Auto Fan

heat demand

X

cool demand

X

X

no demand

Gas Heat, Continuous Fan

heat demand

X

X

cool demand

X

X

no demand

X

Electric Heat, Auto Fan

heat demand

X

X

cool demand

X

X

no demand

Electric Heat, Continuous Fan

heat demand

X

X

cool demand

X

X

no demand

X

NOTE −  X =  output is activated with 24VAC.