background image

Page 6

(/(&75,&$/

USE COPPER CONDUCTORS ONLY
All field wiring must be done in accordance with Na-

tional Electric Code recommendations, local codes and

applicable requirements of UL or in accordance with

Canadian Electrical Code, local codes and CSA Stan-

dards. Power wiring, disconnect means, and over--cur-

rent protection are to be supplied by installer. See unit

rating plate for maximum over--current protection,

minimum circuit ampacity, as well as operating volt-

age. The power supply must be sized and protected ac-

cording to specifications supplied. See figure 6 for field

connection of line voltage wiring and figure 7 for typi-

cal wiring diagram.

&$87,21

:KHQ FRQQHFWLQJ HOHFWULFDO SRZHU DQG FRQWURO ZLU

LQJ WR WKH XQLW ZDWHUSURRI W\SH FRQQHFWRUV 0867

EH XVHG VR WKDW ZDWHU RU PRLVWXUH FDQQRW EH GUDZQ

LQWR WKH XQLW GXULQJ QRUPDO RSHUDWLRQ

208/230 LINE VOLTAGE WIRING

NOTE -- If 208 voltage is supplied, transformer connections

must be made.

/

)86(' ',6&211(&7 6:,7&+

)851,6+(' %< ,167$//(5

*5281'

/8*

/

FIGURE 6

&217$&725

Unit must be grounded with separate ground conduc-

tor. The unit wiring diagram is located inside the unit

access panel. Low voltage control wiring are pigtail

leads located below the main control box and are color

coded to match the connection called out on the wiring

schematic.
If any of the original unit wiring is replaced, the same
size and type wire must be used. Electrical wiring must
be sized to carry minimum circuit ampacity marked on
the unit. Each unit must be wired with a separate
branch circuit and be properly fused.

FIGURE 7

CHP29 SERIES HEAT PUMP PACKAGED UNITS

TYPICAL WIRING DIAGRAM

Содержание CHP29 Series

Страница 1: ...0 17 5 48 5 0 176 5 1 6 5 1 1 6 77 1 81 7 21 16 7 5 1 7 56 6833 1 5 7851 211 7 216 287 225 1 5 1 6 2035 66256 5 1 6 7 56 237 21 75 7 75 6 67 0 3 5 250 1 6 48 1 2 23 5 7 21 0 17 1 1 5 3 5 3 576 67 Thi...

Страница 2: ...1 2 1 2 5 7851 5 23 1 1 25 217 6833 5 23 1 1 25 217 5 7851 5 23 1 1 287 225 2 17 5 287 225 2 287 225 2 867 5 5 7 6 2 5 25 217 5 7851 5 23 1 1 7 5 5 6 5 17 5 2 5 9 7 1 25 7 6 276 URQW DQG DFN 2QO 6 5 6...

Страница 3: ...ct system in the outdoor air stream The outdoor fan is not designed to operate against any additional static pressure Minimum and maximum operating conditions must be observed to assure maximum system...

Страница 4: ...d or vibration into condi tioned space Unit foundation should be raised to a minimum of 3 above finish grade In areas which have prolonged pe riods of temperature below freezing and snowfall the unit...

Страница 5: ...of liquid refrigerant into the compressor The following steps should be taken on initial start up to prevent possible compres sor damage This procedure must be followed at initial start up as well as...

Страница 6: ...ZLU LQJ WR WKH XQLW ZDWHUSURRI W SH FRQQHFWRUV 0867 EH XVHG VR WKDW ZDWHU RU PRLVWXUH FDQQRW EH GUDZQ LQWR WKH XQLW GXULQJ QRUPDO RSHUDWLRQ 208 230 LINE VOLTAGE WIRING NOTE If 208 voltage is supplied...

Страница 7: ...70qF dry bulb return air Data in table 4 is based on 80qF dry bulb 87qF wet bulb return air Allow unit operation to stabilize before taking pressure readings 7 3 68 7 21 683 5 7 7 UNIT MODEL NO SUCTIO...

Страница 8: ...ontactor starting compressor and outdoor fan The reversing valve is not energized in the heating mode The thermostat again automatically brings on the indoor blower at the same time Upon satisfying he...

Страница 9: ...sposable 0RWRUV Indoor and outdoor fan motors are permanently lubri cated and require no maintenance 2XWGRRU RLO Dirt should not be allowed to accumulate on the out door coil surface or other parts in...

Отзывы: