507656-01  7/2018

NOTE

 - When the coil is connected directly with a

condensing furnace, the coil must be level from return end
to supply end. The front (access side) of the furnace may
be pitched downward up to 1 inch to accommodate a
½-inch pitched coil.

3. Secure the supply duct to the coil cabinet.
4. Refer to the instructions provided with the condensing

unit for leak testing, evacuating and charging
procedures. 

Always check the entire system for

leaks before charging. 

5.

Applications using CH35-60 D-width unit with
C-width furnace

 — Figure 2 shows an application

that includes a D-width coil and a C-width furnace.
This application requires construction of an insulated,
field-supplied block‐off plate to cover the open space
on the coil housing.

SUPPLY AIR UNIT

FRONT

PLUMBING

CONNECTIONS

SUPPLY AIR

UNIT REAR

TEST HOLE

AIR FLOW

FIELD‐FABRICATED

INSULATED BLOCK-

OFF PLATE

Figure 2. D-Width Coil with C-Width Furnace

 

(Top View)

SUPPLY AIR UNIT FRONT

PLUMBING

CONNECTIONS

SUPPLY AIR UNIT REAR

AIR FLOW

TEST HOLE

SLOPE 1/2”

(13 MM)

90% GAS FURNACE
DRAIN

COIL DRAIN

SUPPLY AIR UNIT

FRONT

BACK

COIL

(SUPPLY AIR END VIEW)

AIR
FLOW

Figure 3. Left-Hand Air Discharge

COIL
FRONT

NOTE - Use of this orientation is acceptable for 80% AFUE furnaces.

Do not use this orientation for 90% condensing furnaces.

(SUPPLY AIR END VIEW)

SUPPLY AIR UNIT FRONT

PLUMBING CONNECTIONS

SUPPLY AIR UNIT REAR

TEST HOLE

SLOPE 1/2”

(13 MM)

COIL
DRAIN

SUPPLY AIR UNIT

SUPPLY AIR

UNIT FRONT

COIL

AIR FLOW

(Top View)

AIR

FLOW

Figure 4. Right-Hand Air Discharge

FIELD-PROVIDED SPACER
(6 IN.)

COIL

BACK

FRONT

SUPPLY AIR UNIT FRONT

PLUMBING CONNECTIONS

SUPPLY AIR UNIT REAR

TEST HOLE

SLOPE 1/2”

(13 MM)

COIL DRAIN

SUPPLY AIR
UNIT FRONT

(TOP VIEW)

AIR FLOW

90% GAS FURNACE

DRAIN

(SUPPLY AIR END VIEW)

AIR

FLOW

Figure 5. Right-Hand Air Discharge with Spacer

Содержание CH35 Series

Страница 1: ...ne Connections 5 Leak Testing Evacuating and Charging 6 Sealing Ducts 6 Condensate Drain Connection 6 Blower Speed Connection 7 Maintenance 8 General CH35 all aluminum coil horizontal evaporator coils...

Страница 2: ...3 8 3 8 3 8 Condensate drain fpt in 3 4 3 4 3 4 3 4 3 4 Evaporator Coil Net face area sq ft 1 75 3 5 3 5 4 33 4 67 Tube diameter in 3 8 3 8 3 8 3 8 3 8 Number of rows 2 3 2 3 3 Fins per inch 18 14 19...

Страница 3: ...d of pressure Installation WARNING Risk of explosion or fire Can cause injury or death Recover all refrigerant to relieve pressure before open ing the system Install the furnace or air handler accordi...

Страница 4: ...LY AIR UNIT REAR TEST HOLE AIR FLOW FIELD FABRICATED INSULATED BLOCK OFF PLATE Figure 2 D Width Coil with C Width Furnace Top View SUPPLY AIR UNIT FRONT PLUMBING CONNECTIONS SUPPLY AIR UNIT REAR AIR F...

Страница 5: ...eat damage during brazing See figure 7 WATER SATURATED RAGS PLACE A WET RAG AGAINST COIL CABINET AND AROUND THE SUCTION LINE CONNECTION BRAZE CONNECTION ALLOW PIPE TO COOL BEFORE REMOVING WET RAG 1 2...

Страница 6: ...e coil cabinet flanges WARNING There must be an airtight seal between the bottom of the furnace and the return air plenum Use fiberglass sealing strips caulking or equivalent sealing method between th...

Страница 7: ...EADING SECONDARY DRAIN PAN 2 51MM TRAP DEPTH P TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J TRAP 91P90 Figure 10 Typical Main and Overflow Drain Installations Blower Speed Connection Pro...

Страница 8: ...his or any other maintenance turn off all power to the indoor unit at the main unit disconnect switch It is also recommended that you wear personal protective gear safety glasses and or a face shield...

Отзывы: