General Information

The Elite

®

 CBX27UH series air handler is designed for

installation with optional field−installed electric heat and a
matching HFC−410A outdoor unit

This instruction is intended as a general guide and does
not supersede local or national codes in any way. Consult
authorities having jurisdiction before installation. Check
equipment for shipping damage; if found, immediately
report damage to the last carrier.

Shipping and Packing List

Package 1 of 1 contains the following:

1

Assembled air handler unit

1

Horizontal drip shield (CBX27UH−60 only)

NOTE − For down−flow applications, order kit number
83M57.

Requirements

IMPORTANT

This unit must be matched with an indoor coil as speci-
fied in Lennox Engineering Handbook. Coils previous-
ly charged with HCFC−22 must be flushed.

In addition to conforming to manufacturer’s installation
instructions and local municipal building codes, installation
of Lennox air handler units (with or without optional electric
heat), shall conform with the following National Fire
Protection Association (NFPA) standards:

S

NFPA No. 90A − Standard for Installation of Air
Conditioning and Ventilation Systems

S

NFPA No. 90B − Standard for Installation of Residence
Type Warm Air Heating and Air Conditioning Systems

This unit is approved for installation clearance to
combustible material as stated on the unit rating plate.
Accessibility and service clearances must take
precedence over combustible material clearances.

Installing the Unit

These units are factory−configured for up−flow and
horizontal right−hand discharge installation. For down−flow
or horizontal left−hand discharge, certain field
modifications are required.

DISASSEMBLE/REASSEMBLE AIR HANDLER UNITS

The air handler units consists of two factory-assembled
sections. It may be necessary to disassemble the sections
when positioning the unit for installation.

To disassemble:

1. Remove access panels.
2. Remove both blower and coil assemblies. This will

lighten the cabinet for lifting.

3. Remove one screw from the left and right posts inside

the unit. Remove one screw from each side on the
back of the unit. Unit sections will now separate.

To reassemble:

1. Align cabinet sections together.
2. Reinstall screws.
3. Replace blower and coil assemblies.
4. Replace access panel.

UP−FLOW APPLICATION

Use the following procedures to configure the unit for
up−flow operations:

1. Remove access panels.
2. Remove and discard the horizontal drip shield (−060

model, used only on horizontal applications) and the
corrugated padding between the blower and coil
assembly.

3. The horizontal drain pan must be removed when the

coil blower is installed in the up−flow position.
Removing horizontal drain pain will allow proper
airflow and increase efficiency.

4. After removing horizontal drain pan, place the unit in

desired location. Set unit so that it is level. Connect
return and supply air plenums as required using sheet
metal screws as illustrated in figure 1.

5. Install units that have no return air plenum on a stand

that is at least 14" from the floor to allow for proper air
return. Lennox offers an optional up−flow unit stand as
listed in table 1.

HORIZONTAL DRAIN PAN
(MUST BE REMOVED)

UP−FLOW/

DOWN−FLOW

DRAIN PAN

Figure 1. Up−flow Configuration

Table 1. Optional Unit Side Stand (Up−Flow Only)

Model

Kit Number

−21, −26, and −31

45K31

−41 through −65.

45K32

HORIZONTAL RIGHT−HAND DISCHARGE
APPLICATION

Use the following procedures to configure the unit for
horizontal right−hand discharge operations:

NOTE − For horizontal applications, a secondary drain pan
is recommended. Refer to local codes.

Содержание CBX27UH

Страница 1: ...r reclaiming must be followed Fines and or incarceration may be levied for noncompliance INSTALLATION INSTRUCTIONS Elite Series CBX27UH Units MULTI POSITION AIR HANDLERS 506294 01 07 11 Supersedes 05...

Страница 2: ...N LINE Return Air Opening SUPPLY AIR FILTER SUPPLY AIR TOP VIEW FRONT VIEW SIDE VIEW BLOWER A B C 11 1 16 281 F D E COIL 5 8 16 5 8 16 5 8 16 5 8 16 5 8 16 LOW VOLTAGE RIGHT SIDE LINE VOLTAGE LEFT SID...

Страница 3: ...AND LEFT SIDE Horizontal Position Right Hand Air Discharge FILTER ACCESS FILTER ACCESS 5 3 4 146 1 1 2 38 1 3 4 44 CONDENSATE DRAINS 2 HORIZONTAL A 5 8 16 G H A 5 8 16 G 1 25 1 25 11 1 16 281 PIPING P...

Страница 4: ...BLE REASSEMBLE AIR HANDLER UNITS The air handler units consists of two factory assembled sections It may be necessary to disassemble the sections when positioning the unit for installation To disassem...

Страница 5: ...EW END VIEW ANGLE IRON OR SHEET METAL electrical inlet clearance 4 in 102 mm 1 2 in Screws Maximum Figure 3 Suspending Horizontal Unit IMPORTANT When removing the coil there is possible danger of equi...

Страница 6: ...ccess door and replace it on the unit 13 Set unit so that it is sloped 1 4 toward the drain pan end of the unit Connect return and supply air plenums as required using sheet metal screws 14 If suspend...

Страница 7: ...e both wet rags 8 Refer to instructions provided with outdoor unit for leak testing evacuating and charging procedures 9 Install access panel Table 2 Refrigerant Line Sizes Model Liquid Line Vapor Lin...

Страница 8: ...TWO PART DESIGN FOR USE WHERE OBSTRUCTIONS PREVENT DIRECT THREADING SECONDARY DRAIN PAN 2 51MM TRAP DEPTH LENNOX P TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J TRAP 91P90 Figure 8 Typic...

Страница 9: ...according to the job requirements 4 For best air performance external static pressure drop must not exceed 0 5 W C 1 2 kPa Refer to blower data tables for cfm and external static 5 Seal around the hol...

Страница 10: ...213 1365 264 1485 325 30 815 101 970 136 1195 214 1310 265 1430 322 805 105 975 142 1210 219 1330 275 1445 337 40 750 106 915 148 1155 225 1275 273 1385 334 770 114 930 153 1170 231 1285 283 1405 345...

Страница 11: ...to the low voltage terminal strip in the control section The speed can be increased by swapping wires as shown in figure 10 WIRING CONNECTIONS 1 Install line voltage power supply to unit from a prope...

Страница 12: ...ND CONNECT YEL WIRE MOTOR SPEED TAPS 1 AND 2 Figure 10 Motor Speed Taps 208 230V Single Phase MOTOR SPEED TAPS 1 AND 2 TO INCREASE MOTOR SPEED DISCONNECT GRN WIRE AND CONNECT YEL WIRE Figure 11 Motor...

Страница 13: ...Page 13 CBX27UH SERIES Figure 12 Typical System Wiring Diagram 208 230V Single and Three Phase...

Страница 14: ...Page 14 506294 01 Figure 13 Typical System Wiring Diagram 460V Single and Three Phase 036 048 and 060 only...

Страница 15: ...should be cut in an X pattern peeled open glued with an appropriate all purpose glue and placed back against the cabinet surface being careful to not overly compress the insulation so the insulation...

Отзывы: