Lennox @DNOVA 2mAC ADVANCED CONTROLLER Скачать руководство пользователя страница 18

Page  - IOM / @DNOVA-µAC-0907-E

The  trigger  is  excluded  with  a  fixed  relative  differential  of 

1.5°C  (P.  22). The  trigger  is  also  excluded  if  probe  B2  is 

malfunctioning. The  percentage  of  opening  of  the  damper 

is shown on the display via the vertical bars next to the ice 

symbol, while the start-up of the compressor is indicated by the 

number 1 below the symbol itself. If free-cooling is activated 

in  ON-OFF  (Out3),  the  bars  may  be  either  all  on  or  all  off 

depending on the status of the damper.

Range: 0÷30°c 0÷54°F  Def.: 9

rn Lower supply temperature limit

This parameter represents the minimum limit for the supply 

temperature below which the damper of the shelter is closed. 

With probe B4 present, the regulation is of the type described 

in Fig. 6. The percentage of opening of the damper, see Fig. 

6, is reduced proportionally until it is completely closed if the 

supply temperature is lower than 

rn-3°c

. This prevents air of 

a too low temperature being sent into the room. In the ED and 

CW configurations, the actuators turn OFF progressively, when 

the supply temperature falls below the m set, the differential 

is fixed at 3°C. During dehumidification, no limitation of the 

supply temperature is made.

Range: -20÷30°c -4÷86°F  Def.: 5

ro Reading probe B2

External air temperature. 

only appears when the probe is 

installed.

rP Reading probe B3

Percentage  of  humidity  or  pressure  value. 

only  when  the 

probe is

installed.

rr Reading probe B4

Supply air temperature. 

only appears when the probe is 

installed.

rt time band setting

Sets, if the clock option is installed, the time band mode (see 

chap. 7)

0= 

time bands disabled

1= 

fan on at minimum speed with temperature monitoring

2= 

ON/OFF

Range: 0÷2 flags Def.: 0

temperature regulation diagrams

Fig. 3 : 1heating element and 1 compressor

 

Fig. 3 : Diagram showing operation with free-cooling

DESCRIPTION AND CONFIGURATION OF THE PARAMETERS

Lt

low limit

Ht

Diagrams showing operation with free-cooling

low limit

If not enabled

Dumper 100%

Set = r1

Telecom unit with free-cooling

0.5°C

Set-rL

Dumper

Free-cooling control enabled

Содержание @DNOVA 2mAC ADVANCED CONTROLLER

Страница 1: ...Providing indoor climate comfort DNOVA AC IOM 0907 E Installation operating and maintenance DNOVA 2 AC ADVANCED CONTROLLER...

Страница 2: ......

Страница 3: ...rameters 7 Parameter modification 7 DESCRIPTION AND CONFIGURATION OF THE PARAMETERS 9 probe parameters 12 r regulation parameters 13 c compressor management parameters 16 F fan management parameters 1...

Страница 4: ...rs can be configured not only using the keypad located on the front panel but also using a hardware key and or via serial line GENERAL CHARACTERISTICS General description The AC is an electronic contr...

Страница 5: ...mbol off the Set point is displayed time band selected dehumidification active ventilation active fan speed cooling active number 1 or 2 cooling actuators opening cooling valve or in shelter mode open...

Страница 6: ...the Factory parameters Pressed together for 2 secs reset the alarms Status indicators The main states of the regulator power supply present alarm active and remote ON OFF input status are displayed to...

Страница 7: ...Hc Damper ON OFF Out4 Damper 2 Hc Out5 Supply fan Relay digital outputs Connector 3 Out 6 Alarm HF Out 7 Alarm HA Rotation control H2 Analogue outputs Connector 1 Y1 Damper output 2 Hc Y2 Condensatio...

Страница 8: ...ia the master unit 1 sends the command to activate and deactivate the unit in stand by the command is updated every 10 minutes Heating element Air outlet Air inlet Air flow diverter Condenser air outl...

Страница 9: ...arameter HL Level Access DIRECT D immediate access USER U access via password 22 parameter HH FACTORY F access via factory password 177 Parameter modification Accessing Direct parameters D The value o...

Страница 10: ...ed while the and buttons can be used to modify such value Press enter again to temporarily store the new value Then using the and buttons scroll the parameters menu repeating the previous steps for ea...

Страница 11: ...allows the key to be programmed with the machine s parameters During this operation the message EC is displayed and in the case of errors ECEE Adjusting LCD contrast The contrast of the display can b...

Страница 12: ...mperature Set Point heating Minimum temperature set point also for compensation Maximum temperature setpoint also for compensation Minimum humidity set point Maximum humidity set point Type of tempera...

Страница 13: ...on If used in condensation the fan is switched off below the value of F5 with an hysteresis of 0 5 bar for pressure or 1 C for temperature Minimum Triac voltage threshold Maximum Triac voltage thresho...

Страница 14: ...U o M Var Def Pres U F F F 0 250 s 10 20 U F F F 0 90 s 1 5 U F F F 0 250 s 1 40 U U U U 0 15 min 1 0 F F F 1 5 flag 1 1 5 U F U U 0 50 90 C F 1 10 U F U U 0 50 90 C F 1 10 U F U U 0 50 rH 1 20 2 0 U...

Страница 15: ...ling ON OFF with Out3 4 condensation control Function of probe B3 0 humidity control 1 condensation control ON OFF digital input 0 absent 1 present Alarm relay logic 0 de energised in alarm for all al...

Страница 16: ...nge 10 0 10 0 rH bar Def 0 0 9 Calibration input B4 Corrects the value measured by B4 Range 6 0 6 0 C 10 8 10 8 F Def 0 0 A Digital filter Stabilises the coefficient used in the digital filtering of t...

Страница 17: ...compensation of the set point using the external air probe this value also represents the lower limit for the excursion of the set point Range 20 rb C 4 rb F Def 0 rb Maximum temperature set point Lim...

Страница 18: ...oo low temperature being sent into the room In the ED and CW configurations the actuators turn OFF progressively when the supply temperature falls below the m set the differential is fixed at 3 C Duri...

Страница 19: ...ing of limits F2 and F3 0 always ON 1 proportional speed regulation with minimum speed 2 proportional speed regulation with cut off The values 1 or 2 indicate operation of the supply fan in proportion...

Страница 20: ...Sets the operating time at maximum speed on starting up the fans if used for condensation control to overcome the mechanical inertia of the motor If set to 0 the function is not performed that is the...

Страница 21: ...ature This value is specified as a differential in respect to the effective setpoint considering any compensation operations see parameters 1 rG rH Hc These alarms in the case of automatic reset have...

Страница 22: ...lows ID7 24Vac Heating Set r9 ID7 0 Cooling Set r1 When the machine is in cooling mode the presence and the number of heating elements depends on parameter H6 in heating mode on the other hand the coo...

Страница 23: ...minutes in stand by or time band sleep mode for a period of H7 2 seconds These procedures like the complete closing of the valve on instrument start up allow the degree of opening of the valve to be a...

Страница 24: ...energised only for serious alarms Range 0 3 flags Def 0 HG Delay on start up Sets the delay time on each switching from stand by to ON or POWERON During this phase the green LED is on but all actuato...

Страница 25: ...m the modifications made Time bands Entering the parameter rt see USER parameter modification allows the selection of rt 1 or 2 enabling the time band function Pressing the Sel button displays in sequ...

Страница 26: ...wed by the Alarm button The code of the last alarm event is shown and on repeatedly pressing Sel the hour minute and the date The and buttons scroll the alarm data In places where no alarm has been re...

Страница 27: ...board EEPROM and must be performed when installing the board itself The alarm codes displayed are those reported in the table in the chapter on the alarms in addition other special codes have been in...

Страница 28: ...mm FC ON ON 34 nn counter fan imm FA ON ON serious alarms in the configuration with two alarm relays these activate the alarm output the other alarms ON the other hand activate the dehumidification In...

Страница 29: ...ion of the compressor and causes its immediate switching off without waiting the corresponding delay times The alarm H2 is managed only if parameter H5 2 or 4 two independent circuits If condensation...

Страница 30: ...PA shelter power failure alarm External power failure alarm delayed by 2 seconds This is generated for models configured as shelters when input ID6 is open it causes the immediate switching off of the...

Страница 31: ...1 km Cables 1 twisted pair and shield AWG20 22 with capacity between leads 90pF m e g BELDEN 8761 8762 cables Protection against electric shock the device guarantees only a functional insulation betw...

Страница 32: ...d Input ID1 for Remote ON OFF switches on the machine when powered Input ID7 for Cooling heating enables heating operation when powered Y1 0 10Vdc output not optically isolated from power supply poten...

Страница 33: ......

Страница 34: ...IOM 0907 E BELGIUM LUXEMBOURG CZECH REPUBLIC FRANCE GERMANY NETHERLANDS POLAND PORTUGAL RUSSIA SLOVAKIA SPAIN UKRAINE UNITED KINGDOM AND IRELAND OTHER COUNTRIES Due to Lennox s ongoing commitment to...

Отзывы: