• 15 •
AWC
AWH
002
485
1,02
1,04
1,00
1,01
0,98
440
1,00
1,00
1,00
1,00
1,00
285
0,91
0,84
0,97
0,94
1,11
003
550
1,04
1,10
1,01
1,03
0,95
515
1,00
1,00
1,00
1,00
1,00
335
0,94
0,89
0,99
0,95
1,08
007
1430
1,02
1,06
1,02
1,02
0,96
1250
1,00
1,00
1,00
1,00
1,00
1010
0,96
0,92
0,97
0,99
1,08
008
1620
1,01
1,03
1,01
1,01
0,98
1500
1,00
1,00
1,00
1,00
1,00
1250
0,96
0,93
0,98
0,98
1,06
010
2100
1,02
1,04
1,03
1,01
0,98
1900
1,00
1,00
1,00
1,00
1,00
1550
0,96
0,92
0,98
0,97
1,07
012
2200
1,02
1,03
1,03
1,01
0,98
2000
1,00
1,00
1,00
1,00
1,00
1620
0,96
0,92
0,98
0,97
1,09
015
2610
1,01
1,03
1,01
1,01
0,98
2450
1,00
1,00
1,00
1,00
1,00
1850
0,94
0,89
0,97
0,96
1,12
018
3100
1,01
1,03
1,01
1,01
0,98
2800
1,00
1,00
1,00
1,00
1,00
2060
0,92
0,87
0,97
0,95
1,12
020
3500
1,01
1,03
1,02
1,01
0,98
3100
1,00
1,00
1,00
1,00
1,00
2450
0,94
0,89
0,98
0,96
1,12
15
TC (kW)
1,03
0,91
17
TC (kW)
1,02
0,95
20
TC (kW)
1,00
1,00
22
TC (kW)
0,99
1,04
24
TC (kW)
0,98
1,08
21
15
TC (kW)
0,88
SC (kW)
0,89
0,99
24
17
TC (kW)
0,94
SC (kW)
0,94
1,00
27
19
TC (kW)
1,00
SC (kW)
1,00
1,00
29
21
TC (kW)
1,07
SC (kW)
0,99
1,00
32
23
TC (kW)
1,13
SC (kW)
1,04
1,01
AQUALEAN - AWC/AWH - MIL118E-1407 / 10-2013
1.9.- CORRECTION FACTORS
AIR FLOW
The data in the capacity tables have been calculated for nominal air
fl
ow rate; with maximum/minimum air
fl
ow rates use these cor-
rection factors :
AIR FLOW RATE
COOLING MODE
HEATING MODE
Total capacity
kW
EER
Sensible capacity
kW
Total capacity
kW
Total absorbed power
kW
Maximum
Nominal
Minimum
Maximum
Nominal
Minimum
Maximum
Nominal
Minimum
Maximum
Nominal
Minimum
Maximum
Nominal
Minimum
Maximum
Nominal
Minimum
Maximum
Nominal
Minimum
Maximum
Nominal
Minimum
Maximum
Nominal
Minimum
AIR INLET
COOLING MODE AWC/AWH.
The data in the capacity tables has been calculated for air inlet
temperature: 27ºC DB and 19ºC WB. For another conditions
use these correction factors.
HEATING MODE AWH
The data in the capacity tables has been calculated for air
inlet temperature: 20ºC DB. For another conditions use these
correction factors.
TC : Total capacity
SC : Sensible capacity
D.B. : Dry bulb
W.B. : Wet bulb
Air inlet temperature (D.B.)
Power input (kW)
Power input (kW)
Power input (kW)
Power input (kW)
Power input (kW)
Air inlet temperature
(D.B.)
Air inlet temperature
(W.B.)
Power input (kW)
Power input (kW)
Power input (kW)
Power input (kW)
Power input (kW)
GENERAL CHARACTERISTICS