background image

Page 35

TABLE 12

TCA210H NORMAL OPERATING PRESSURES

Outdoor

Coil

Entering

Air Temp

CIRCUIT 1

CIRCUIT 2

CIRCUIT 3

CIRCUIT 4

Dis.

+10

psig

Suc.

+5

psig

Dis.

+10

psig

Suc.

+5

psig

Dis.

+10

psig

Suc

+5

psig

Dis.

+10

psig

Suc.

+5

psig

65°F

170

77

173

80

172

80

168

80

75°F

197

78

198

81

197

81

193

81

85°F

223

79

225

82

225

82

221

82

95°F

255

81

255

83

257

83

252

83

105°F

289

83

287

84

293

85

287

85

115°F

329

85

323

86

333

87

327

87

TABLE 13

TCA240S NORMAL OPERATING PRESSURES

Outdoor

Coil

Entering

Air Temp

CIRCUIT 1

CIRCUIT 2

CIRCUIT 3

Dis.

+10

psig

Suc.

+5

psig

Dis.

+10

psig

Suc.

+5

psig

Dis.

+10

psig

Suc.

+5

psig

65°F

185

69

182

73

183

72

75°F

212

71

209

75

210

74

85°F

236

72

233

75

234

75

95°F

267

73

265

76

264

75

105°F

297

74

301

77

300

76

115°F

335

76

340

78

338

78

TABLE 14

TCA240H NORMAL OPERATING PRESSURES

Outdoor

Coil

Entering

Air Temp

CIRCUIT 1

CIRCUIT 2

CIRCUIT 3

CIRCUIT 4

Dis.

+10

psig

Suc.

+5

psig

Dis.

+10

psig

Suc.

+5

psig

Dis.

+10

psig

Suc

+5

psig

Dis.

+10

psig

Suc.

+5

psig

65°F

179

75

181

79

174

79

176

79

75°F

207

76

208

81

203

79

204

80

85°F

239

78

238

82

233

80

234

81

95°F

272

80

270

83

266

83

266

83

105°F

307

83

303

84

301

84

300

85

115°F

351

85

342

85

343

86

342

86

TABLE 15

TCA300S NORMAL OPERATING PRESSURES

Outdoor

Coil

Entering

Air Temp

CIRCUIT 1

CIRCUIT 2

CIRCUIT 3

CIRCUIT 4

Dis.

+10

psig

Suc.

+5

psig

Dis.

+10

psig

Suc.

+5

psig

Dis.

+10

psig

Suc

+5

psig

Dis.

+10

psig

Suc.

+5

psig

65°F

185

69

183

70

186

72

179

71

75°F

213

72

210

74

215

76

207

75

85°F

247

75

241

77

249

78

240

78

95°F

280

77

271

78

281

80

271

79

105°F

320

79

309

79

317

81

307

80

115°F

361

81

346

80

358

82

345

82

Charge Verification − Approach Method

 1− Using the same thermometer, compare liquid temper-

ature to outdoor ambient temperature.

Approach Temperature = Liquid temperature minus

ambient temperature.

 2− Approach temperatures should match values in table

16. An approach temperature greater than 

this value

 in-

dicates an undercharge. An approach temperature

less than 

this value

 indicates an overcharge.

 3− Do not use the approach method if system pressures

do not match pressures in tables 9 through 15. The ap-

proach method is not valid for grossly over or under-

charged systems.

TABLE 16

APPROACH TEMPERATURES

Unit

Liquid Temp. Minus Ambient Temp.

1st Stage

2nd Stage

3rd Stage

4th Stage

180S
210S
240S
180H

7°F + 1 

(3.9°C + 0.5)

7°F + 1 

(3.9°C + 0.5)

7°F + 1 

(3.9°C + 0.5)

NA

210H

9°F + 1 

(5°C + 0.5)

7°F + 1 

(3.9°C + 0.5)

8°F + 1 

(4.4°C + 0.5)

8°F + 1 

(4.4°C + 0.5)

240H

10°F + 1 

(5.6°C + 0.5)

9°F + 1 

(5°C + 0.5)

9°F + 1 

(5°C + 0.5)

10°F + 1 

(5.6°C + 0.5)

300S

14°F + 1 

(7.8°C + 0.5)

12°F + 1 

(6.7°C + 0.5)

12°F + 1 

(6.7°C + 0.5)

12°F + 1 

(6.7°C + 0.5)

V− SYSTEMS SERVICE CHECKS 

A−Cooling System Service Checks

TCA  units are factory charged and require no further adjust-
ment; however, charge should be checked periodically using
the approach method. The approach method compares actual
liquid temperature with the outdoor ambient temperature. See
section IV−CHARGING.

NOTE−When unit is properly charged discharge line pres-
sures should approximate those in tables 9  through 15.

VI−MAINTENANCE 

CAUTION

Electrical shock hazard. Turn off power to unit be-
fore performing any maintenance, cleaning or
service operation on the unit.

CAUTION

Danger of sharp metallic edges. Can cause injury.
Take care when servicing unit to avoid accidental
contact with sharp edges.

Содержание ALLIED Commercial TCA180H2B High

Страница 1: ...at each corner Refer to the installation instructions for the prop er rigging technique WARNING Improper installation adjustment alteration service or maintenance can cause property damage person al...

Страница 2: ...andard Static 3 hp 2 2 kW 3 hp 2 2 kW 5 hp 3 7 kW 5 hp 3 7 kW High Static 5 hp 3 7 kW 5 hp 3 7 kW 7 5 hp 5 6 kW 7 5 hp 5 6 kW Max usable motor output US Only Low Static 3 45 hp 2 6 kW 3 45 hp 2 6 kW 5...

Страница 3: ...6 kW 7 5 hp 5 6 kW 10 hp 7 5 kW High Static 10 hp 7 5 kW 10 hp 7 5 kW N A Max usable motor output US Only Low Static 5 75 hp 4 3 kW 5 75 hp 4 3 kW 8 63 hp 6 4 kW Standard Static 8 63 hp 6 4 kW 8 63 h...

Страница 4: ...60 866 3 86 898 4 11 926 4 36 954 4 61 984 4 90 1013 5 19 1038 5 44 NOTE Bold To operate in this range unit must be ordered with High Static Drive and drive kit 3 must be ordered separately for field...

Страница 5: ...his range unit must be ordered with High Static Drive and drive kit 7 must be ordered separately for field installation 1 40 to 2 50 in w g TCA210 Air Volume cfm External Static in w g Covered By Driv...

Страница 6: ...811 4 87 845 5 22 879 5 57 910 5 94 941 6 31 970 6 67 999 7 02 1027 7 38 1054 7 74 1079 8 08 1104 8 41 1 40 to 2 50 in w g TCA240 Air Volume cfm External Static in w g Covered By Drive At Nominal Air...

Страница 7: ...1155 10 45 1178 10 83 11500 915 7 40 948 7 88 980 8 35 1010 8 80 1040 9 25 1068 9 68 1095 10 10 1118 10 53 1140 10 95 1165 11 40 1190 11 85 1210 12 23 12000 935 7 95 963 8 35 990 8 75 1020 9 23 1050...

Страница 8: ...85 6600 3115 92 229 77 191 67 167 54 134 6800 3210 99 246 83 206 72 174 58 144 7000 3305 1 03 256 87 216 76 189 49 122 41 102 36 90 62 154 40 99 7200 3400 1 09 271 92 229 80 199 66 164 7400 3490 1 15...

Страница 9: ...0 11 5 7 5 8 6 1045 1285 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required Maximum usable output of motors furnished...

Страница 10: ...49 1 3 249 Full Load Amps each total 4 8 9 6 2 6 5 2 2 0 4 0 Locked Rotor Amps each total 9 4 18 8 4 8 9 6 3 8 7 2 Service Outlet 115V GFI 15 Amps 15 Amps 15 Amps Indoor Blower Motor Horsepower 3 5 7...

Страница 11: ...2 65 68 60 kW 164 172 181 82 85 90 66 68 72 without power exhaust 71 77 84 35 37 41 28 30 33 2 Maximum Overcurrent Protection with power exhaust 0 kW 90 90 110 40 45 50 35 35 40 15 kW 90 90 110 40 45...

Страница 12: ...W 94 100 107 45 48 52 37 39 42 15 kW 94 100 107 45 48 52 37 39 42 30 kW 110 118 127 55 58 63 44 47 50 45 kW 155 163 172 77 81 85 62 65 68 60 kW 164 172 181 82 85 90 66 68 72 90 kW 236 244 253 118 122...

Страница 13: ...94 97 101 without power exhaust 83 89 97 41 43 47 30 32 35 2 Maximum Overcurrent Protection with power exhaust 0 kW 100 110 125 45 50 60 35 40 45 15 kW 100 110 125 45 50 60 35 40 45 30 kW 110 125 150...

Страница 14: ...26 130 97 101 103 without power exhaust 100 107 114 49 52 55 38 40 42 2 Maximum Overcurrent Protection with power exhaust 0 kW 125 125 150 60 60 70 45 50 50 15 kW 125 125 150 60 60 70 45 50 50 30 kW 1...

Страница 15: ...01 103 without power exhaust 100 108 114 52 55 58 41 44 46 2 Maximum Overcurrent Protection with power exhaust 0 kW 110 125 150 60 60 70 45 50 50 15 kW 110 125 150 60 60 70 45 50 50 30 kW 125 150 150...

Страница 16: ...97 101 103 without power exhaust 108 116 127 55 58 61 45 47 49 2 Maximum Overcurrent Protection with power exhaust 0 kW 125 150 150 60 70 70 50 50 60 15 kW 125 150 150 60 70 70 50 50 60 30 kW 125 150...

Страница 17: ...c Motor Drive Combination stock unit f f f f High Static Motor Drive Combination f f f f 1 Standard to Low Static Conversion Kit Drive Kit A C1DRKT044 1 x 1 Standard to Low Static Conversion Kit Drive...

Страница 18: ...metric Relief Dampers Hood Furnished LAGEDH18 24 x x x x Outdoor Air Dampers Hoods Damper Section down flow Automatic Order Hood Separately T1DAMP20C 1 Damper Section down flow Manual Order Hood Separ...

Страница 19: ...AIN FILTERS SIX 24 X 24 X 2 ECONOMIZER DAMPERS OPTIONAL ELECTRIC HEAT OPTIONAL BLOWERS MCC A45 CONTROL OUTDOOR FANS COMPRESSORS 4TH COMPRESSOR ON 210H 240H 300H UNITS ONLY FILTER DRIERS FIGURE 2 TCA C...

Страница 20: ...MCC board A45 For thermostats with occupied and un occupied modes a factory installed jumper across termi nals A1 and A2 should be removed Unit wiring is designed for a three stage thermostat For two...

Страница 21: ...terminal designations Tables 4 5 6 and 7 show pin terminal designations Features The MCC A45 is equipped with a green LED for board sta tus See table 1 for LED flash codes While in the cooling mode th...

Страница 22: ...switch selected Make sure switches are set correctly Refer to figure 5 Flashes Rapidly Simultaneous heat and cool demands Check thermostat and wiring Press pushbutton and immediately release to overri...

Страница 23: ...nsformer T1 C Ground K3 From Transformer T18 Y3 To Processor micro chip TABLE 5 P113 TERMINAL DESIGNATIONS Terminal Function S49 Relay KA To Freeze Stat S49 From Freeze Stat K10 Relay KA To Outdoor Fa...

Страница 24: ...ontinue to operate 3 Low Ambient Switches optional S11 S84 S85 all units S94 210H 240H 300S only The low ambient switch is an optional field installed auto reset N O pressure switch which allows for m...

Страница 25: ...D REFRIGERANT CIRCUITS DETAIL FIGURE 7 B1 COMPRESSOR B1 B13 S7 optional S28 optional SUCTION LINE OPTIONAL HIGH PRESSURE SWITCH S4 DISCHARGE LINE FREEZESTAT 3 ONE FOR EACH STAGE OF COIL LOCATED ON RET...

Страница 26: ...GERANT CIRCUITS DETAIL FIGURE 8 COMPRESSOR B1 B20 S7 S28 S96 B13 DRIERS 4 FREEZESTAT 4 ONE FOR EACH STAGE OF COIL LOCATED ON RETURN BEND SUCTION LINE DISCHARGE LINE OPTIONAL HIGH PRESSURE SWITCH S4 PR...

Страница 27: ...toward outside of unit When pulling the base out further than 12 305mm disconnect wir ing to K3 blower contactor T1 T2 and T3 Pull wiring toward blower to allow enough slack to slide the base out furt...

Страница 28: ...rce below these values indicates an underten sioned belt A force above these values indicates an overtensioned belt MEASURE BELT TENSION FIGURE 10 DEFLECTION 1 64 PER INCH OF SPAN OR 1 5mm PER 100mm O...

Страница 29: ...t Hat Section Figure 13 3 Electric Heat Relay K9 All TCA series units with electric heat use an electric heat relay K9 K9 is a N O DPDT pilot relay intended to electrically iso late the unit s 24V cir...

Страница 30: ...through F3 8 10 Terminal Strip TB3 Electric heat line voltage connections are made to terminal strip TB3 or a fuse block on some models located in the up per left corner of the electric heat vestibule...

Страница 31: ...EHA156S 15 208 230V 60 Amp 250V 60 Amp 250V 460V 50 Amp 600V 575V 40 Amp 600V 2 EHA360 22 5 45 kW Total or 2 EHA156 22 5 208 230V 50 Amp 250V 25 Amp 250V 50 Amp 250V 25 Amp 250V 460V 25 Amp 600V 15 Am...

Страница 32: ...ONTACTOR K15 SECOND STAGE ELECTRIC HEAT CONTACTOR K16 FIRST HEAT SECTION LEFT SIDE SECOND HEAT SECTION RIGHT SIDE FUSE F3 F3 1 FUSE F3 F3 2 FUSE F3 F3 3 FUSE F3 F3 4 TERMINAL STRIP TB3 FIRST STAGE ELE...

Страница 33: ...Blower Compartment Blower Belt Adjustment B Cooling Startup The thermostat specified for use on this unit has three cool ing outputs 1 Remove coil covers before starting unit 2 Initiate first and seco...

Страница 34: ...the outdoor ambient temperature 4 Apply the outdoor temperature to tables 9 through 15 to determine normal operating pressures 5 Compare the normal operating pressures to the pres sures obtained from...

Страница 35: ...79 309 79 317 81 307 80 115 F 361 81 346 80 358 82 345 82 Charge Verification Approach Method 1 Using the same thermometer compare liquid temper ature to outdoor ambient temperature Approach Temperatu...

Страница 36: ...Wheel Annually inspect supply air blower wheel for accumulated dirt or dust Turn off power before attempting to remove ac cess panel or to clean blower wheel D Evaporator Coil Inspect and clean coil a...

Страница 37: ...22 Refer to the roof mounting frame installa tion instructions for proper plenum construction and attach ment FIGURE 21 ASSEMBLED ROOF MOUNTING FRAME FRONT END END BACK CENTER SUPPORTS TWO PIECES EAC...

Страница 38: ...nt requiring more fresh air See figure 24 FIGURE 24 A6 ENTHALPY CONTROLLER A B C D Open Min Pos FREE COOLING SETPOINT A Completely counterclockwise D Completely clockwise OUTDOOR AIR SUITABLE LED Free...

Страница 39: ...alf way when CO2 rises above setpoint Adjust the DCV MAX potentiometer to the approximate setting specified by the controls con tractor Refer to figure 24 Note DCV Max must be set higher than economiz...

Страница 40: ...here the two lines meet Read the percent of fresh air intake on the side 7 If fresh air percentage is less than desired adjust thumbwheel higher If fresh air percentage is more than desired adjust thu...

Страница 41: ...OUTDOOR AIR IS NOT SUITABLE FOR FREE COOLING FREE COOL LED OFF THERMOSTAT DEMAND DAMPER POSITION MECHANICAL COOLING UNOCCUPIED OCCUPIED Off Closed Closed No G Closed Minimum No Y1 Closed Minimum Stage...

Страница 42: ...able for TCA180 300 units are power ex haust fans used in downflow applications only The fans re quire optional down flow gravity exhaust dampers and T1ECON economizers Power exhaust fans provide exha...

Страница 43: ...Page 43 VIII Wiring Diagrams and Sequence of Operation TCA180S 180H 210S 240S UNIT DIAGRAM...

Страница 44: ...rough N C freezestat S49 optional N C high pressure switch S4 to energize compressor contactor K1 8 N O contacts K1 close energizing compressor B1 9 Optional N O low ambient switch S11 closes to energ...

Страница 45: ...Page 45 TCA210H 240H 300S UNIT DIAGRAM...

Страница 46: ...energized 8 N O contacts K1 closes energizing compressor B1 9 Optional N O low ambient switch S11 closes to energize condenser fan relay K10 10 N O contacts K10 1 and K10 2 close energizing condenser...

Страница 47: ...Page 47 EHA 15 30 45 60 90kW Y VOLTAGE...

Страница 48: ...Page 48 EHA 15 30 45 60 90KW G J M...

Страница 49: ...nts to be energized SECOND STAGE HEAT With the first stage heat operating an additional heat ing demand initiates at W2 in the thermostat 4 Relay K19 is energized N O contacts K19 1 close en ergizing...

Страница 50: ...al strip TB1 found on the main control module A45 energize thermostat components with 24VAC OPERATION 2 The main control module A45 receives data from the electronic thermostat A2 Y1 Y2 Y3 W1 W2 G OCP...

Страница 51: ...tactor K3 is ener gized OPERATION 2 Enthalpy sensor A7 and A62 if differential enthalpy is used communicates to the economizer control module A6 when to power the damper motor B7 3 Economizer control...

Отзывы: