Heat exchanger gas unit – ALARM E4
Smart Energy Company
www.systemapolska.pl
Reason
Solution
Ignition electrode(s) are
incorrectly positioned or
damaged or out of working
1. Electrodes are installed incorrectly, improve it ( see drawing
in MOI page 57
2. Replace them with original spare parts. Note! Use the same
type of elctrodes for box F, G, H and for C, D, E, E+ with
serial no higher than L21G11320. For modules C, D, E, E+
with lower serial no – use repair kit burner
3. Replace the ground electrode conector (wire yellow-green)
with the ignition electrode connector ( red wire)
Ignitor broken
If it is spark issue and / or replace with the original spare parts
(see above point)
Содержание 70LENX1000
Страница 9: ...Burner units model E Baltic C D E box Smart Energy Company www systemapolska pl ...
Страница 10: ...Burner units model E Baltic F G H box Smart Energy Company www systemapolska pl ...
Страница 31: ...Heat exchanger gas unit Main board operation ...
Страница 49: ...Smart Energy Company www systemapolska pl Commissioning procedure start up ...
Страница 56: ...HEGU procedure to put in Hi Lo power Smart Energy Company www systemapolska pl ...
Страница 58: ...Supply pressure in countries Smart Energy Company www systemapolska pl Tabele 5 1 page 44 ...
Страница 61: ...Gas valve calibration Smart Energy Company www systemapolska pl Based on E Baltic C box IOM page 62 ...
Страница 67: ...Burner electrode change in module C D E E Smart Energy Company www systemapolska pl From serial no L21G11320 ...
Страница 74: ...Heat exchanger gas unit Troubleshooting Smart Energy Company www systemapolska pl ...
Страница 97: ...Smart Energy Company www systemapolska pl THANK YOU FOR ATTENTION ...