Lennox 2SCU13-18 Скачать руководство пользователя страница 2

Page 2 of 19

506874-01

Issue 1140

INSTALLATION

General

The 2SCU13 air conditioner, which will also be referred to
in this instruction as the outdoor unit, uses HCFC-22
refrigerant.  This outdoor unit is intended as a replacement
outdoor component for use in residential systems which
include an existing indoor coil which is functioning properly.

It is NOT intended for new installations.

This outdoor unit is:

shipped from the factory with nitrogen holding charge
that must be purged from the unit;

designed for use with HCFC-22 refrigerant only;

designed for use in systems that use either a RFC
device (orifice) included with outdoor unit or thermal
expansion valve (TXV). See the 2SCU13 product
specification sheet for approved fixed orifice sizes and
expansion valve kit match ups.

IMPORTANT:

 

 The air conditioning unit must have properly

matched system components including indoor unit and
refrigerant metering device.  Mismatched equipment may
have an impact on the operation, performance, reliability,
and warranty of the air conditioning unit.

Read this entire instruction manual, as well as the
instructions supplied in separate equipment, before
starting the installation.  Observe and follow all
warnings, cautions, instructional labels, and tags.
Failure to comply with these instructions could result
in an unsafe condition and/or premature component
failure.

These instructions are intended as a general guide only for
use by qualified personnel and do not supersede any national
or local codes in any way.  The installation must comply with
all provincial, state, and local codes as well as the National
Electrical Code (U.S.) or Canadian Electrical Code (Canada).
Compliance should be determined prior to installation.

When servicing or repairing HVAC components, ensure the
fasteners are appropriately tightened.  Table 1 shows torque
values for fasteners.

I

nspection of Shipment

Upon receipt of equipment, carefully inspect it for possible
shipping damage. If damage is found, it should be noted on
the carrier’s freight bill.  Take special care to examine the
unit inside the carton if the carton is damaged.  Any
concealed damage discovered should be reported to the
last carrier immediately, preferably in writing, and should
include a request for inspection by the carrier’s agent.

If any damages are discovered and reported to the carrier
DO NOT INSTALL THE UNIT

, as claim may be denied.

Check the unit rating plate to confirm specifications are
as ordered.
Location of Unit

Outdoor units operate under a wide range of weather
conditions; therefore, multiple factors must be considered
when positioning the unit.  The unit must be positioned to
give adequate clearances for sufficient airflow and servicing.
Refer to Figure 1 for installation clearances.

Slab Mounting

When installing unit at grade level, install on level slab high
enough so that water from higher ground will not collect
around unit (see Figure 2).

Roof Mounting

Install unit at a minimum of 4" above surface of the roof.
Care must be taken to ensure weight of unit is properly
distributed over roof joists and rafters.  Either redwood or
steel supports are recommended.

Figure 1

Installation Clearances

* A service clearance of 30" must be maintained on one of the sides adjacent

to the control box. Clearance to one of the other three sides must be 36".
Clearance to one of the remaining two sides may be 12" and the final side
may be 6".

A clearance of 24" must be maintained between units.

48" clearance required on top of unit. Maximum soffit overhang is 36".

Torque Table

Table 1

Fastener

Torque

Stem Caps

8 ft. lbs.

Service Port Caps

8 ft. lbs.

Sheet Metal Screws

16 in. lbs.

#8 Machine Screws

16 in. lbs.

#10 Machine Screws

28 in. lbs.

Compressor Bolts

90 in. lbs.

Содержание 2SCU13-18

Страница 1: ...y glasses and gloves when installing this equipment WARNING Sharp metal edges can cause injury When installing the unit use care to avoid sharp edges WARNING Installation and servicing of air conditio...

Страница 2: ...onents ensure the fasteners are appropriately tightened Table 1 shows torque values for fasteners Inspection of Shipment Upon receipt of equipment carefully inspect it for possible shipping damage If...

Страница 3: ...or unit and thermostat except when required by the indoor thermostat Refer to thermostat installation instructions C common connection between indoor unit and outdoor unit required for proper operatio...

Страница 4: ...ibration Line Set Isolation Illustrations on the following pages demonstrate procedures which ensure proper refrigerant line set isolation Figure 5 shows how to install line sets on horizontal runs Fi...

Страница 5: ...in Armaflex Liquid Line Strap Liquid Line to Vapor Line Figure 5 To hang line set from joist or rafter use either metal strapping material or anchored heavy nylon wire ties Strapping Material around v...

Страница 6: ...he 2SCU13 unit Place the supplied fixed orifice sticker on the indoor cabinet after installation Figure 8 shows how to install the replacement fixed orifice Do not twist distributor tubes when looseni...

Страница 7: ...anifold gauge set that is equipped with low loss hoses Do not use a manifold gauge set with anything other than a low loss hose Liquid and Suction Line Service Valves The liquid line and suction line...

Страница 8: ...nd indoor unit must be checked for leaks Using an Electronic Leak Detector 1 Connect the high pressure hose of the manifold gauge set to the suction valve service port Normally the high pressure hose...

Страница 9: ...igerant to produce substances that corrode copper piping and compressor parts Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns Use an instrument that reads down t...

Страница 10: ...ion line service valve High pressure gauge to liquid line service valve 2 Close manifold gauge set valves Connect the center manifold hose to an upright cylinder of HCFC 22 3 Ifroomtemperatureisbelow7...

Страница 11: ...ature according to the chart from the suction line temperature to determine the superheat 5 Compare the superheat value with those shown in Table 7 on page 12 If superheat is greater than shown add so...

Страница 12: ...at the system is not properly charged or that a problem exists with some component in the system 6 Compare the approach value with those shown in Table 8 If the values to do not agree with those provi...

Страница 13: ...1 Page 13 of 19 Issue 1140 Table 9 Normal Operating Pressures L Liquid S Suction Values provided above are typical pressures Indoor unit matchup indoor air quality and indoor load will cause pressures...

Страница 14: ...k wiring for loose connections 5 Check for correct voltage at unit with unit operating 6 Check amp draw outdoor fan motor Unit Name Plate ________ Actual _________ NOTE If owner complains of insuffici...

Страница 15: ...___________ Service Technician ________________________________________ Nameplate Voltage ______________ Rated Load Ampacity ________ Compressor _______________ Outdoor Fan ___________________ Maximum...

Страница 16: ...NAL AND LOCAL CODES OUTDOOR FAN F C H 1 2 3 R S C C 2 3 1 EQUIPMENT GROUND HR1 L2 208 230 60 1 L1 K1 1 BLACK YELLOW RED RED C12 BLACK ORANGE B4 PURPLE K1 S4 S24 A4 C Y1 TO 24 VAC POWER SOURCE 20 VA MI...

Страница 17: ...L2 L3 EQUIPMENT GROUND HR1 S40 K1 1 BLACK BLACK B1 BLACK ORANGE BLACK B4 C1 PURPLE RED 1 FOR USE WITH COPPER CONDUCTORS ONLY REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCUR...

Страница 18: ...installation date and location if warranty claim c An accurate description of the problem 2 Call your local installing contractor 3 If the installing contractor is unable to provide warranty parts che...

Страница 19: ......

Страница 20: ......

Отзывы: