background image

Page 14 of 19

506874-01

Issue 1140

OPERATION

MAINTENANCE

Outdoor unit and indoor blower cycle on demand from the
room thermostat. When the thermostat blower switch is
moved to the ON position, the indoor blower operates
continuously.

Maintenance and service must be performed by a qualified
installer or service agency.

At the beginning of each cooling season, the system should
be checked as follows:

1.

Clean and inspect condenser coil.  Coil may be flushed
with a water hose. Be sure the power is off before using
water to clean the coil.

2.

Outdoor fan motor is pre-lubricated and sealed. No
further lubrication is needed.

3.

Visually inspect connecting lines and coils for evidence
of oil leaks.

4.

Check wiring for loose connections.

5.

Check for correct voltage at unit (with unit operating).

6.

Check amp-draw outdoor fan motor.

Unit Name Plate ________  Actual _________

NOTE:

   

If owner complains of insufficient cooling, the unit

should be gauged and refrigerant charge checked.  Refer
to the 

Refrigerant Charging

 section on page 10.

Indoor Coil

1.

Clean coil, if necessary.

2.

Check connecting lines and coils for evidence of oil
leaks.

3.

Check condensate pan line and clean, if necessary.

Indoor Unit

1.

Clean or change filters.

2.

Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM.

3.

Belt drive blowers: 

Check belt for wear and proper

tension.

Before performing maintenance operations on system,
turn the electric power to unit OFF at disconnect
switch(es). Unit may have multiple power supplies.
Electrical shock could cause personal injury or death.

  WARNING

Содержание 2SCU13-18

Страница 1: ...y glasses and gloves when installing this equipment WARNING Sharp metal edges can cause injury When installing the unit use care to avoid sharp edges WARNING Installation and servicing of air conditio...

Страница 2: ...onents ensure the fasteners are appropriately tightened Table 1 shows torque values for fasteners Inspection of Shipment Upon receipt of equipment carefully inspect it for possible shipping damage If...

Страница 3: ...or unit and thermostat except when required by the indoor thermostat Refer to thermostat installation instructions C common connection between indoor unit and outdoor unit required for proper operatio...

Страница 4: ...ibration Line Set Isolation Illustrations on the following pages demonstrate procedures which ensure proper refrigerant line set isolation Figure 5 shows how to install line sets on horizontal runs Fi...

Страница 5: ...in Armaflex Liquid Line Strap Liquid Line to Vapor Line Figure 5 To hang line set from joist or rafter use either metal strapping material or anchored heavy nylon wire ties Strapping Material around v...

Страница 6: ...he 2SCU13 unit Place the supplied fixed orifice sticker on the indoor cabinet after installation Figure 8 shows how to install the replacement fixed orifice Do not twist distributor tubes when looseni...

Страница 7: ...anifold gauge set that is equipped with low loss hoses Do not use a manifold gauge set with anything other than a low loss hose Liquid and Suction Line Service Valves The liquid line and suction line...

Страница 8: ...nd indoor unit must be checked for leaks Using an Electronic Leak Detector 1 Connect the high pressure hose of the manifold gauge set to the suction valve service port Normally the high pressure hose...

Страница 9: ...igerant to produce substances that corrode copper piping and compressor parts Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns Use an instrument that reads down t...

Страница 10: ...ion line service valve High pressure gauge to liquid line service valve 2 Close manifold gauge set valves Connect the center manifold hose to an upright cylinder of HCFC 22 3 Ifroomtemperatureisbelow7...

Страница 11: ...ature according to the chart from the suction line temperature to determine the superheat 5 Compare the superheat value with those shown in Table 7 on page 12 If superheat is greater than shown add so...

Страница 12: ...at the system is not properly charged or that a problem exists with some component in the system 6 Compare the approach value with those shown in Table 8 If the values to do not agree with those provi...

Страница 13: ...1 Page 13 of 19 Issue 1140 Table 9 Normal Operating Pressures L Liquid S Suction Values provided above are typical pressures Indoor unit matchup indoor air quality and indoor load will cause pressures...

Страница 14: ...k wiring for loose connections 5 Check for correct voltage at unit with unit operating 6 Check amp draw outdoor fan motor Unit Name Plate ________ Actual _________ NOTE If owner complains of insuffici...

Страница 15: ...___________ Service Technician ________________________________________ Nameplate Voltage ______________ Rated Load Ampacity ________ Compressor _______________ Outdoor Fan ___________________ Maximum...

Страница 16: ...NAL AND LOCAL CODES OUTDOOR FAN F C H 1 2 3 R S C C 2 3 1 EQUIPMENT GROUND HR1 L2 208 230 60 1 L1 K1 1 BLACK YELLOW RED RED C12 BLACK ORANGE B4 PURPLE K1 S4 S24 A4 C Y1 TO 24 VAC POWER SOURCE 20 VA MI...

Страница 17: ...L2 L3 EQUIPMENT GROUND HR1 S40 K1 1 BLACK BLACK B1 BLACK ORANGE BLACK B4 C1 PURPLE RED 1 FOR USE WITH COPPER CONDUCTORS ONLY REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCUR...

Страница 18: ...installation date and location if warranty claim c An accurate description of the problem 2 Call your local installing contractor 3 If the installing contractor is unable to provide warranty parts che...

Страница 19: ......

Страница 20: ......

Отзывы: