Table 19. Alert Codes and Troubleshooting
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat
Alert
Code
Inverter
Flash
Code
Priority
Condition
Actual Displayed
Alert Text
Under dealer
control center >
Notifications
Component or System Operational State and Troubleshooting Tip
How to clear alert code
420
Service Soon
AH EIM Defrost
Out Of Cycle
The heat pump defrost cycle has taken more than 20 minutes to complete.
• Defrost cycle lasts longer than 20 minutes.
• Check heat pump operation.
• This is applicable only in communicating indoor unit with non-communicating heat pump.
Automatically clears when
W1
signal
is removed.
421
Service
Urgent
OD EIM W
External Miswire
Fault
The
W
output terminal on the outdoor unit is not wired correctly. Voltage sensed on
W
output
terminal when
Y1
out is deactivated.
Automatically clears once voltage
is not sensed on output or power is
cycled.
422
Service Soon
OD Compressor
Top Cap Switch
Open
Compressor top cap switch exceeding thermal limit.
• Check condenser fan motor, TXV and indoor unit blower motor.
•
Check for stuck reversing valve or clogged refrigerant filter.
• XC/XP25: Check to ensure that one of the wires from the top cap switch has not been
disconnected from one of the
TP
terminals on the outdoor control. Reconnect wire if
disconnected.
• Check superheat and sub-cooling.
Automatically clears when error is
corrected.
423
40
Service
Soon/Service
Urgent
OD Inverter CT
Circuit Fault
The inverter has detected a circuit issue.
• When this condition is detected the outdoor control will stop outdoor unit operations and start
the anti-short cycle timer – moderate condition.
• Outdoor control will lockout unit after 10 strikes within an hour – critical condition.
•
Inverter LEDs will flash code 40
•
Refer to the unit service documentation for troubleshooting procedures.
Inverter flash code 40:
The sequence is:
Red LED: Four Flashes
Green LED: Off
NOTE:
Inverter normal operations with no error code present is as follows. Red LED is ON and
Green LED is OFF.
A moderate alert code will clear
automatically when the inverter
detects the condition no longer exist
and will send a clear alert code
message.
To clear critical alert code disconnect
power to outdoor unit and restart.