Table 19. Alert Codes and Troubleshooting
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat
Alert
Code
Inverter
Flash
Code
Priority
Condition
Actual Displayed
Alert Text
Under dealer
control center >
Notifications
Component or System Operational State and Troubleshooting Tip
How to clear alert code
31
Service
Urgent
Lost
communication
with Device
The applicable system component (indoor, equipment interface, damper control module or outdoor
unit) has not communicated with thermostat for more than three minutes.
•
Check connections and voltages.
• Ohm wires for electrical continuity.
•
If float switch is installed on air handler drain pain, check condensate line to ensure it is not
clogged and tripping the float switch connected in series with
R
terminal.
• Check to see if freezestat is installed.
If fault persists, then cycle power.
Fault clears after communication is
restored.
32
Information
Only-Dealer
Device
Resetting
The applicable system component (device) is resetting itself. This issue may occur during a power
outage or power fluctuation in the system. If persistent or if it coincides with the system operations
then proceed with the following troubleshooting steps.
• Check the power connections.
•
Check the amperage draw at the transformer (possible overloaded).
•
Check 24VAC voltage at the system component (device).
• If the fault persists after checking the connections, replace the applicable control.
To clear the alert code, go to
menu
> settings > advanced settings
> view dealer control center >
notifications
and select the alert
code and press the
clear
button.
34
Service
Urgent
Must Program
Unit Capacity
For Device
The thermostat does not know the capacity (tonnage) of the indoor or outdoor unit. The applicable
system component is missing the programmed unit capacity.
•
Remove power to thermostat before programming the unit control.
• Go to applicable unit control and program the unit capacity manually (see the unit installation
instruction for configuration instructions).
•
Once configuration is complete then reconnect thermostat wires.
• Go to
menu
>
settings
>
advanced settings
>
view dealer control center
>
equipment
and press
reset HVAC equipment
. This will allow the system to auto-detect any Lennox
communicating components attached.
Automatically clears when the
system detects that the issue no
longer exists.