Installing Indoor Metering Device

A

Attach  the  vapor  line  sensing  bulb  in  the  proper

orientation as illustrated to the right using the clamp and

screws provided.

NOTE 

— Confirm proper thermal contact between vapor line

and expansion bulb before insulating the sensing bulb once

installed.

B

Connect the equalizer line from the expansion valve to

the equalizer vapor port on the vapor line. Finger tighten

the flare nut plus 1/8 turn (7 ft-lbs) as illustrated below.

TWO PIECE

PATCH PLATE

(UNCASED

COIL ONLY)

VAPOR

LINE

LIQUID LINE

ORIFICE

HOUSING

DISTRIBUTOR

TUBES

LIQUID LINE

MALE EQUALIZER LINE

FITTING (SEE

EQUALIZER LINE

INSTALLATION FOR

FURTHER DETAILS)

SENSING

LINE

EQUALIZER

LINE

EXPANSION

VALVE

TEFLON

®

RING

(Uncased Coil Shown)

Sensing  bulb  insulation  is  required  if

mounted external to the coil casing. sensing

bulb installation for bulb positioning.

STUB

END

TEFLON

®

RING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

DISTRIBUTOR

ASSEMBLY

A

Remove  the  field-provided  fitting  that  temporary

reconnected the liquid line to the indoor unit's distributor

assembly.

B

Install one  of  the  provided  Teflon

®

  rings  around  the

stubbed end of the expansion valve and lightly lubricate

the connector threads and expose surface of the Teflon

®

ring with refrigerant oil.

C

Attach the stubbed end of the expansion valve to the

liquid line  orifice  housing.  Finger  tighten  and  use  an

appropriately sized wrench to turn an additional 1/2 turn

clockwise as illustrated in the figure above, or 20 ft-lb.

D

Place the remaining Teflon

®

 washer around the other

end of the expansion valve. Lightly lubricate connector

threads and  expose  surface  of  the  Teflon

®

  ring  with

refrigerant oil.

E

Attach the liquid line assembly to the expansion valve.

Finger tighten and use an appropriately sized wrench to

turn an additional 1/2 turn clockwise as illustrated in the

figure above or 20 ft-lb.

ON  7/8”  AND  LARGER LINES,

MOUNT  SENSING  BULB  AT

EITHER THE 4 OR 8 O'CLOCK

POSITION. NEVER MOUNT ON

BOTTOM OF LINE.

12

ON LINES SMALLER THAN

7/8”,  MOUNT  SENSING

BULB AT EITHER THE 3 OR

9 O'CLOCK POSITION.

12

BULB

VAPOR LINE

VAPOR LINE

NOTE — NEVER MOUNT ON BOTTOM OF LINE.

BULB

BULB

BULB

VAPOR LINE

FLARE NUT

COPPER FLARE

SEAL BONNET

MALE BRASS EQUALIZER

LINE FITTING

FLARE SEAL CAP

OR

1

2

3

4

5

6

7

8

9

10

11 12

1/2 Turn

SENSING BULB INSTALLATION

EQUALIZER LINE INSTALLATION

1

2

3

4

5

6

7

8

9

10

11 12

1/8 Turn

A

Remove and discard either the flare seal cap or flare nut

with copper flare seal bonnet from the equalizer line port

on the vapor line as illustrated in the figure to the right.

B

Remove and discard either the flare seal cap or flare nut

with copper flare seal bonnet from the equalizer line port on

the vapor line as illustrated in the figure to the right.

INDOOR EXPANSION VALVE INSTALLATION

FIGURE 9. Installing Indoor Expansion Valve

This outdoor unit is designed for use in systems that use a 

check expansion valve metering device at the indoor coil.
See the Lennox 16ACX Product Specification bulletin for 

approved expansion valve kit match-ups. The expansion 

valve unit can be installed internal or external to the indoor 

coil. 

In applications where an uncased coil is being installed in 

a field-provided plenum, install the expansion valve in a 

manner that will provide access for field servicing of the 

expansion valve. Refer to below illustration for reference 

during installation of expansion valve unit.

Содержание 16ACX Series

Страница 1: ...isconnect all remote electric power supplies before opening access panel Unit may have multiple power supplies 16ACX Table of Contents Installation Clearances 2 Model Number Identification 2 Dimension...

Страница 2: ...mm Clearance to one of the remaining two sides may be A clearance of 24 in must be maintained between two units 48 in 1219 mm clearance required on top of unit Model Number Identification 16 AC X 036...

Страница 3: ...NECTION 6 3 8 162 TOP VIEW BASE SECTION COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT STAND OFF KIT 4 Field Installed 111 4 3 8 4 3 8 4 3 8 4 3 8 6 3 8 162 111 111 111 111 4 3 8...

Страница 4: ...0 97 0 95 Outdoor Fan Motor Full load amps 1 0 1 7 1 7 1 4 Locked Rotor amps 1 9 3 2 3 2 3 2 CONTROLS ORDER SEPARATELY iComfort M30 Smart Wi Fi Thermostat 15Z69 Remote Outdoor Temperature Sensor X265...

Страница 5: ...riately sized wrench should be used and fitted snugly over the cap before tightening TABLE 1 Torque Requirements Parts Recommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 ft lb 2...

Страница 6: ...7 8 9 10 11 12 1 12 TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately...

Страница 7: ...ent of unit in relation to a window see the provided illustration in figure 3 detail A PLACING UNIT ON SLAB When installing unit at grade level the top of the slab should be high enough above grade so...

Страница 8: ...ons that may cause panels to be blown around and battered WARNING REMOVAL STEP 1 INSERT PANEL UNDER UNIT TOP CAP LIP AND LIFT SLIGHTLY TO CLEAR SIDE LIP OF PANEL FROM BASE STEP 2 PANEL INSTALLATION TO...

Страница 9: ...of refrigerant charge in the system No need to add oil in system with 20 pounds of refrigerant or less For systems over 20 pounds add one ounce for every five pounds of refrigerant Recommended topping...

Страница 10: ...be used if line set is to be installed on exterior of outside wall PVC PIPE FIBERGLASS INSULATION CAULK OUTSIDE WALL VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE OUTSIDE WALL LIQUID LINE VAPOR LINE WO...

Страница 11: ...dous to your health Avoid breathing vapors or fumes from brazing operations Perform operations only in well ventilated areas Wear gloves and protective goggles or face shield to protect against burns...

Страница 12: ...SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT AND D...

Страница 13: ...tions for the next step in preparing the unit WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE...

Страница 14: ...ISTING INDOOR UNIT GAUGE MANIFOLD INVERTED CYLINDER CONTAINS CLEAN HCFC22 TO BE USED FOR FLUSHING LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE...

Страница 15: ...hreads and expose surface of the Teflon ring with refrigerantoil E Attach the liquid line assembly to the expansion valve Finger tighten and use an appropriately sized wrench to turn an additional 1 2...

Страница 16: ...losed connect the cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allo...

Страница 17: ...r unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F When the...

Страница 18: ...to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 24VAC TRANSFORMER Use the transformer provided with the furnace or air han dler for low voltage control power 24...

Страница 19: ...Page 19 FIGURE 12 Typical Wiring Diagram...

Страница 20: ...shut off compressor operation The auto reset switch closes when the compressor cas ing temperature falls to 151 187 F 66 C 86 C and the compressor is re energized This single pole single throw SPST bi...

Страница 21: ...s filter is located It will be either at the indoor unit installed internal or external to the cabinet or behind a return air grille in the wall or ceiling Check the filter monthly and clean or repla...

Страница 22: ...he thermostat for a cooling demand Turn on power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit 7 Recheck voltage while the unit is running Power must be with...

Отзывы: