background image

Page 17

line at manifold. Break vacuum in system with nitro-
gen pressure by opening manifold high pressure
valve. Close manifold high pressure valve to center
port.

 4− Close nitrogen drum valve and disconnect from

gauge manifold center port. Release nitrogen pres-
sure from system.

 5− Connect  vacuum  pump  to  gauge  manifold  center

port. Evacuate system through manifold service
valves until vacuum in system does not rise above
.5mm of mercury absolute pressure or 500 microns
within a 20−minute period after stopping vacuum pump.

 6− After evacuation is complete, close manifold center port,

and connect refrigerant drum. Pressurize system
slightly with refrigerant to break vacuum.

III − CHARGING 

This system is charged with HFC−410A refrigerant which
operates at much higher pressures than HCFC−22. The
recommended check expansion valve is approved for use
with HFC−410A. Do not replace it with a valve that is de-
signed to be used with HCFC−22. This unit is NOT ap-
proved for use with coils that include metering orifices or
capillary tubes.
The unit is factory−charged with the amount of HFC−410A
refrigerant indicated on the unit rating plate. This charge is
based on a matching indoor coil and outdoor coil with a 15
foot (4.6 m) line set. 

For varying line set lengths and for

various indoor unit matchups, the refrigerant charge
must be adjusted per tables

 

6 (Page 19) and 7

(Page 19).

 A blank space is provided on the unit rating

plate to list the actual field charge.

IMPORTANT

Mineral oils are not compatible with HFC−410A. If oil
must be added, it must be a polyol ester oil.

A − Check indoor air before charging

Figure 18

IMPORTANT

CHECK AIRFLOW BEFORE CHARGING!

NOTE − Be sure that filters and indoor and outdoor coils are
clean before testing.

Cooling mode indoor airflow check

Check airflow using the Delta−T (

D

T)

 process (figure 18).

Heating mode indoor airflow check

Blower airflow (CFM) may be calculated by energizing
electric heat and measuring:

S

temperature rise between the return air and supply air
temperatures at the indoor coil blower unit,

S

measuring voltage supplied to the unit,

S

measuring amperage being drawn by the heat unit(s).

Then, apply the measurements taken in following formula
to determine CFM:

CFM =

Amps x Volts x 3.41

CFM =

1.08 x Temperature rise (F)

B − Set Up for Checking and Adding Charge

Setup for charging

Connect the manifold gauge set to the unit’s service ports
(see figure 14):

S

low pressure gauge to 

vapor service port

S

high pressure gauge to 

liquid service port

Close manifold gauge set valves. Connect the center man-
ifold hose to an upright cylinder of HFC−410A.

Calculating charge

If the system is void of refrigerant, first, locate and repair
any leaks and then weigh in the refrigerant charge into the
unit. To calculate the total refrigerant charge:

Amount
specified
on
nameplate

Adjust amt. for
variation in 
line set length
(table 6)

Additional charge
specified per 
indoor unit matchup
(table 7)

Total
charge

+

+

=

Содержание 14HPX

Страница 1: ...vice technicians only All specifications are subject to change ELECTROSTATIC DISCHARGE ESD Precautions and Procedures CAUTION Electrostatic discharge can affect electronic components Take precautions during unit instal lation and service to protect the unit s electronic controls Precautions will help to avoid control exposure to electrostatic discharge by putting the unit the control and the techn...

Страница 2: ...tor Amps 1 4 1 4 1 4 2 9 OPTIONAL ACCESSORIES must be ordered extra Compressor Crankcase Heater 93M04 S S S p Factory S Compressor Hard Start Kit 10J42 S S S S Compressor Low Ambient Cut Off 45F08 S S S S Compressor Sound Cover 69J03 S S S S Freezestat 3 8 in tubing 93G35 S S S S 5 8 in tubing 50A93 S S S S Hail Guards 92M89 S S 92M88 S 27W34 S Indoor Blower Off Delay Relay 58M81 S S S S Loss of C...

Страница 3: ...Amps 2 9 2 9 2 9 OPTIONAL ACCESSORIES must be ordered extra Compressor Crankcase Heater Factory S S S Compressor Hard Start Kit 10J42 S S p 81J69 S Compressor Low Ambient Cut Off 45F08 S S S Compressor Sound Cover 69J03 S S S Freezestat 3 8 in tubing 93G35 S S S 5 8 in tubing 50A93 S S S Hail Guards 27W36 S S 94M94 S Indoor Blower Off Delay Relay 58M81 S S S Loss of Charge Kit 84M23 S S S 5 Low Am...

Страница 4: ...ssor is energized by a contactor located in the control box See figure 2 Single pole contactors are used in 14HPX series units See wiring diagrams for specific unit K1 is energized through the CMC1 board by the in door thermostat terminal Y1 24V when thermostat de mand is present DANGER Electric Shock Hazard May cause injury or death Disconnect all remote electrical power supplies before opening u...

Страница 5: ...ontrol Pressure Switch Settings High Pressure auto reset trip at 590 psig reset at 418 Low Pressure auto reset trip at 25 psig reset at 40 psig 5 Strike Lockout Feature The internal control logic of the control counts the pressure switch trips only while the Y1 Input line is active If a pres sure switch opens and closes four times during a Y1 In put the control logic will reset the pressure switch...

Страница 6: ...priate fault code Heating and cooling operation will be allowed in this fault condition NOTE Within a single room thermostat demand if 5 strikes occur the board will lockout the unit Defrost board 24 volt power R must be cycled OFF or the TEST pins on board must be shorted between 1 to 2 sec onds to reset the board Defrost Temperature Termination Shunt Jumper Pins The defrost control selections ar...

Страница 7: ...t cycle will be initiated after 34 minutes of heating mode compressor run time The con trol will attempt to self calibrate after this and all other de frost cycle s Calibration success depends on stable system tempera tures during the 20 minute calibration period If the control fails to calibrate another defrost cycle will be initiated after 45 minutes 90 minutes 1 to 4 boards of heating mode comp...

Страница 8: ...faults open or shorted If a fault exists the unit will remain in Heat Mode and no further test mode operation will be executed until the test short is removed and re applied If no fault exists and ambient temperature is below 35ºF the unit will go into Defrost mode The unit will terminate defrost and enter Heat Mode uncalibrated with defrost timer set for 34 minute test No further test mode operat...

Страница 9: ...g Valve ON W1 line ON Monitor coil temperature and time in defrost mode HOW DID DEFROST TERMINATE Coil temperature was above 35 F 2 C for 4 min of the 14 min de frost OR reached defrost termination temp DCB s 60L3901 and 46M8201 LO PS Termination Option selected Defrost terminated by pressure Defrosted for 14 min with out the coil temp going above 35 F 2 C for 4 min and coil did not reach terminat...

Страница 10: ...as internal component failure Cycle 24 volt power to board If code does not clear replace control FAULT LOCKOUT CODES Each fault adds 1 strike to that code s counter 5 strikes per code LOCKOUT OFF SLOW Flash Low Pressure Fault 1 Restricted air flow over indoor or outdoor coil 2 Improper refrigerant charge in 1 Remove any blockages or restrictions from coils and or fans Check indoor and outdoor fan...

Страница 11: ...tinues the gas is forced toward the center of the scroll and the gas pocket becomes compressed figure 12 3 When the compressed gas reaches the center it is discharged vertically into a chamber and discharge port in the top of the compressor figure 11 The discharge pressure forcing down on the top scroll helps seal off the upper and lower edges tips of the scrolls figure 11 During a single orbit se...

Страница 12: ...panel If replacing outdoor fan motor on the 14HPX 060 align motor shaft 1 4 from the hub For all other 14HPX model units motor shaft should be flush with hub See figure 13 Drip loops should be used in wir ing when servicing motor D Reversing Valve L1 and Solenoid A refrigerant reversing valve with electromechanical so lenoid is used to reverse refrigerant flow during unit op eration The reversing ...

Страница 13: ...s taken out of the circuit I Drier A filter drier designed for all 14HPX model units is factory installed in the liquid line The filter drier is designed to re move moisture and foreign matter which can lead to com pressor failure Moisture and or Acid Check Because POE oils absorb moisture the dryness of the system must be verified any time the refrigerant sys tem is exposed to open air A compress...

Страница 14: ...TION EXPANSION CHECK VALVE INDOOR UNIT OUTDOOR UNIT LIQUID LINE SERVICE PORT GAUGE MANIFOLD DISTRIBUTOR INDOOR COIL FIGURE 15 14HPX HEATING CYCLE SHOWING MANIFOLD GAUGE CONNECTIONS OUTDOOR COIL EXPANSION CHECK VALVE BIFLOW FILTER DRIER TO HFC 410A DRUM LOW PRESSURE HIGH PRESSURE COMPRESSOR REVERSING VALVE VAPOR LINE VALVE MUFFLER NOTE ARROWS INDICATE DIRECTION OF REFRIGERANT FLOW SERVICE PORT SUCT...

Страница 15: ...serve as the primary leak seal NOTE Always keep valve stem caps clean To Access Schrader Port 1 Remove service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is completed replace service port cap Tighten finger tight then an additional 1 6 turn To Open Liquid or Vapor Line Service Valve 1 Remove stem cap with an adjustable wrench 2 Using service wrench and he...

Страница 16: ...ll amount of HFC 410A 3 to 5 psig 20kPa to 34kPa then pressurize with nitrogen to 150 psig 4 Release nitrogen pressure from the system correct any leaks and recheck WARNING Danger of explosion When using a high pressure gas such as dry nitrogen to pressurize a refriger ant or air conditioning system use a regulator that can control the pressure down to 1 or 2 psig 6 9 to 13 8 kPa WARNING Fire Expl...

Страница 17: ...nd 7 Page 19 A blank space is provided on the unit rating plate to list the actual field charge IMPORTANT Mineral oils are not compatible with HFC 410A If oil must be added it must be a polyol ester oil A Check indoor air before charging Figure 18 IMPORTANT CHECK AIRFLOW BEFORE CHARGING NOTE Be sure that filters and indoor and outdoor coils are clean before testing Cooling mode indoor airflow chec...

Страница 18: ...ance checks This is not a procedure for charging the unit Refer to Charging Checking Charge section Minor variations in these pressures may be expected due to differences in installations Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system Table 5 Normal Operating Pressures Liquid 10 Vapor 5 PSIG 14HPX 018 14HPX 024 ...

Страница 19: ...f necessary operate heating to reach that temperature range then set thermostat to cooling mode setpoint to 68ºF 20ºC When pressures have stabilized continue with step 6 Using heating mode When the outdoor ambient temperature is below 60 F 15 C Target subcooling values in table below are based on 65 75 F 18 24 C indoor return air temperature if necessary operate cooling to reach that temperature r...

Страница 20: ...H 060 14 4 0 0 CBX27UH 030 11 6 2 4 CBX27UH 042 12 6 0 8 CBX27UH 060 12 5 0 0 CBX32M 030 11 6 1 6 CBX32M 048 12 6 0 7 CBX32M 048 060 12 5 0 0 CBX32M 036 11 6 2 4 CBX32MV 048 12 6 0 8 CBX32MV 048 060 12 5 0 0 CBX32MV 024 030 11 6 1 6 CH33 62D 12 6 0 10 CBX32MV 068 12 7 1 0 CBX32MV 036 11 6 2 4 CH33 50 60C 12 6 0 7 CH33 50 60C 12 5 0 0 C33 44C 11 6 2 3 CH33 60D 12 6 0 4 CH33 62D 12 5 0 0 CH33 36C 11...

Страница 21: ...9 44 127 3 75 217 4 106 345 3 137 519 3 45 129 7 76 220 9 107 350 1 138 525 8 46 132 2 77 224 4 108 355 0 139 532 4 47 134 6 78 228 0 109 360 0 140 539 0 48 137 1 79 231 6 110 365 0 141 545 6 49 139 6 80 235 3 111 370 0 142 552 3 50 142 2 81 239 0 112 375 1 143 559 1 51 144 8 82 242 7 113 380 2 144 565 9 52 147 4 83 246 5 114 385 4 145 572 8 53 150 1 84 250 3 115 390 7 146 579 8 54 152 8 85 254 1 ...

Страница 22: ...nit operating 6 Check amp draw on outdoor fan motor Unit nameplate__________Actual__________ 7 Inspect drain holes in coil compartment base and clean if necessary NOTE If insufficient heating or cooling occurs the unit should be gauged and refrigerant charge should be checked Indoor Coil 1 Clean coil if necessary 2 Check connecting lines joints and coil for evidence of oil leaks 3 Check condensate...

Страница 23: ...Page 23 V WIRING DIAGRAM AND SEQUENCE OF OPERATION 14HPX UNIT DIAGRAM 5 1 2 3 4 6 ...

Страница 24: ...nal thermostat wiring de energizes terminal O by heating mode selection de energizing the reversing valve L1 See steps 1 2 and 3 End of FIRST STAGE HEAT See steps 4 5 and 6 DEFROST MODE When a defrost cycle is initiated the control ener gizes the reversing valve solenoid and turns off the condenser fan The control will also put 24VAC on the W1 auxiliary heat line The unit will stay in this mode un...

Отзывы: