background image

Page 5

Figure 2

Service Clearances

3 (76)*

48 (1219)

30

(762)

24

(610)

*Rear clearance is 18" (457) when required for
accessory maintenance.
NOTE − Top Clearance − 36 in. (914 mm)
NOTE − Entire perimeter of unit base requires
support when elevated above mounting surface.

FRONT

REAR

NOTE − Do not permit overhanging structures or shrubs to
obstruct condenser air discharge outlet.

In the U.S. units may be installed on combustible floors
made from wood or class A, B, or C roof covering material.
In Canada, units may be installed on combustible floors.

Existing Common Vent Systems

The 13CHA packaged cooling units with auxiliary electric
heat may replace an existing furnace which is being re-
moved from a venting system commonly run with sepa-
rate gas appliances. In this case, the existing vent system
is likely to be too large to properly vent the remaining at-
tached appliances.

Conduct the following test while each appliance is operat-
ing and the other appliances (which are not operating) re-
main connected to the common venting system. If the
venting system has been installed improperly, you 

must

correct the system as indicated in the general venting re-
quirements section.

 1 − Seal any unused openings in the common venting sys-

tem.

 2 − Inspect the venting system for proper size and horizontal

pitch. Determine that there is no blockage, restriction,
leakage, corrosion, or other deficiencies which could
cause an unsafe condition.

 3 − Close all building doors and windows and all doors be-

tween the space in which the appliances remaining
connected to the common venting system are located
and other spaces of the building. Turn on clothes dry-
ers and any appliances not connected to the common
venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they will oper-
ate at maximum speed. Do not operate a summer ex-
haust fan. Close fireplace dampers.

 4 − Follow the lighting instructions. Turn on the appliance

that is being inspected. Adjust the thermostat so that
the appliance operates continuously.

 5 − After the main burner has operated for 5 minutes, test

for leaks of flue gases at the draft hood relief opening.
Use the flame of a match or candle, or smoke from a
cigarette, cigar, or pipe.

 6 − After determining that each appliance connected to the

common venting system is venting properly, (step 3)
return all doors, windows, exhaust fans, fireplace
dampers, and any other gas−burning appliances to
their previous mode of operation.

 7 − If a venting problem is found during any of the preced-

ing tests, the common venting system must be modi-
fied to correct the problem.

Resize the common venting system to the minimum
vent pipe size determined by using the appropriate
tables in Appendix G. (These are in the current stan-
dards of the National Fuel Gas Code
ANSI-Z223.1/NFPA 54 in the USA, and the appropri-
ate Category 1 Natural Gas and Propane appliances
venting sizing tables in the current standards of the
CSA B149 Natural Gas and Propane Installation
Codes in Canada.)

Содержание 13CHA SERIES

Страница 1: ...mage immediately contact the last carrier WARNING Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service...

Страница 2: ...lbs in in 13CHA 24 73 91 114 92 16 29 13CHA 30 73 91 114 92 16 29 13CHA 36 80 93 117 100 16 30 13CHA 42 102 128 151 120 21 33 13CHA 48 105 129 152 124 21 33 5 13CHA 60 105 129 152 124 21 33 5 Model N...

Страница 3: ...ditioner is not recommended during any phase of construction Very low return air temperatures harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit If this un...

Страница 4: ...1 Unit is designed for outdoor installation only Unit must be installed so all electrical components are protected from water 2 Condenser coils must have an unlimited supply of air 3 For ground level...

Страница 5: ...use an unsafe condition 3 Close all building doors and windows and all doors be tween the space in which the appliances remaining connected to the common venting system are located and other spaces of...

Страница 6: ...e the use of 1 2 or 4 filters If the optional filter kit is not used a filter must be field installed Filters must always be installed ahead of evaporator coil and must be kept clean or replaced Dirty...

Страница 7: ...is present at all components when unit is not in operation Disconnect all remote electric power supplies before opening access panel Unit may have multiple power supplies Failure to disconnect all pow...

Страница 8: ...Page 8 Figure 6 Blower Drive Control Typical Single Phase Unit Wiring Connections Figure 7...

Страница 9: ...Page 9 Figure 8 13CHA Series Packaged Electric Units Typical Wiring Diagram...

Страница 10: ...mpressor will stop System Performance For maximum performance of this cooling system the operating temperatures and pressure should be checked and superheat determined at Standard ARI test conditions...

Страница 11: ...outdoor fan and vent motors are permanently lubricated and require no further lubrication Motors should be cleaned yearly to prevent the accumulation of dust and dirt on the windings or motor exterio...

Отзывы: