background image

Page 1

©

2005 Lennox Industries Inc.

Corp. 0518−L8

13ACD

Service Literature

Revised 03−2007

13ACD SERIES UNITS

The 13ACD is a residential split-system condensing unit
with SEER ratings up to 14.80. The series is designed for
use with expansion valves (TXV) or refrigerant flow control
(RFC). All 13ACD units utilize scroll compressors.

13ACD condensing units are available in 1−1/2, 2, 2 -1/2, 3, 3
-1/2, 4 and 5 ton capacities. All major components (indoor
blower and coil) must be matched according to Lennox rec-
ommendations for the compressor to be covered under war-
ranty. Refer to the Engineering Handbook for approved sys-
tem matchups.

Information contained in this manual is intended for use by
qualified service technicians only. All specifications are subject
to change.

This manual is divided into sections which discuss the
major components, refrigerant system, charging proce-
dure, maintenance and operation sequence.

WARNING

Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person-
al injury or loss of life. Installation and service must
be performed by a qualified installer or service
agency.

WARNING

Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.

Failure to follow this warning may result in personal
injury or death.

TABLE OF CONTENTS

Specifications / Electrical Data

Page 2

. . . . . . . . . 

I Unit Components

Page 3

. . . . . . . . . . . . . . . . . . . 

II Refrigerant System

Page 5

. . . . . . . . . . . . . . . . . 

III Charging

Page 6

. . . . . . . . . . . . . . . . . . . . . . . . . 

IV Maintenance

Page 11

. . . . . . . . . . . . . . . . . . . . . . 

V Wiring and Operating Sequence

Page 12

. . . . . 

ELECTROSTATIC DISCHARGE (ESD)

Precautions and Procedures

CAUTION

Electrostatic discharge can affect electronic
components. Take precautions during unit instal-
lation and service to protect the unit’s electronic
controls. Precautions will help to avoid control
exposure to electrostatic discharge by putting
the unit, the control and the technician at the
same electrostatic potential. Neutralize electro-
static charge by touching hand and all tools on an
unpainted unit surface before performing any
service procedure.

IMPORTANT

The Clean Air Act of 1990 bans the intentional venting
of (CFC’s and HFC’s) as of July 1, 1992. Approved
methods of recovery, recycling or reclaiming must be
followed. Fines and/or incarceration my be levied for
noncompliance.

Содержание 13ACD Series

Страница 1: ...jury or loss of life Installation and service must be performed by a qualified installer or service agency WARNING Refrigerant can be harmful if it is inhaled Refrigerant must be used and recovered re...

Страница 2: ...um overcurrent protection amps 15 20 30 30 45 40 60 3 Minimum circuit ampacity 10 7 14 1 18 7 19 1 25 9 25 7 33 3 Compressor Rated load amps 7 7 10 4 14 1 14 4 19 2 19 2 26 1 p Power factor 98 96 96 9...

Страница 3: ...2 Dual Capacitor C12 The compressor and fan in 13ACD series units use per manent split capacitor motors The capacitor is located inside the unit control box see figure 2 A single dual capacitor C12 i...

Страница 4: ...ll draws gas into the outer crescent shaped gas pocket created by the two scrolls figure 5 1 The centrifugal action of the orbiting scroll seals off the flanks of the scrolls figure 5 2 As the orbitin...

Страница 5: ...beginning electrical service procedures DANGER FAN CONDENSER FAN MOTOR AND COMPRESSOR ACCESS Remove 7 screws REMOVE 7 SCREWS SECURING FAN GUARD REMOVE FAN GUARD FAN ASSEMBLY MOTOR FAN GUARD WIRING FI...

Страница 6: ...tem cap stem Use Adjustable Wrench To open rotate Stem Clockwise 90 To close rotate Stem Counter clockwise 90 ball shown open to outdoor coil to indoor coil Service Valve Valve Closed Schrader valve o...

Страница 7: ...HCFC 22 into the line set and indoor unit Weigh in a trace amount of HCFC 22 A trace amount is a maxi mum of 2 ounces 57 g or 3 pounds 31 kPa pressure Close the valve on the HCFC 22 cylinder and the v...

Страница 8: ...er and remove the man ifold gauge set D Charging Units are factory charged with the amount of HCFC 22 re frigerant indicated on the unit rating plate This charge is based on a matching indoor coil and...

Страница 9: ...t be used if ambient tem peratures are below 65 F For best results indoor tempera ture should be 70 F 21 C to 80 F 26 C 1 Restrict the airflow see figure 10 through the outdoor coil to achieve pressur...

Страница 10: ...5 153 79 157 81 152 77 164 77 75 24 166 81 173 80 167 77 170 76 167 80 170 81 165 77 177 78 80 27 180 82 187 81 181 78 186 76 182 80 184 82 179 78 192 78 85 29 195 82 218 82 195 78 201 77 198 81 198 8...

Страница 11: ...coil reinstall the mesh screen by positioning it in its original position and reinserting the push pin No tool is required to push the pin back into the same slot in the fins If the push pin is loose...

Страница 12: ...he thermostat 2 24VAC from indoor unit Y1 energizes the TOC timed off control if used which energizes contactor K1 3 K1 1 N O closes energizing compressor B1 and outdoor fan motor B4 4 Compressor B1 a...

Отзывы: