background image

Page 5

Outdoor Fan Clearances

Figure 4 illustrates the critical measurements of the out
door fan system. This dimension should be checked and
fan adjusted accordingly anytime servicing of the outdoor
fan system is required.

OUTDOOR FAN CLEARANCES

FIGURE 4

A

UNIT MODEL NO.

A

−024, −030

−036, −042, −048, −060

3"

3−1/2"

Compressors

Units are shipped with compressor mountings factory−ad
justed and ready for operation.

CAUTION

Do not loosen compressor mounting bolts.

Optional Electric Heat

The unit is fully equipped for heat pump operation without
auxiliary heat.

Installing Optional Electric Heat Section

 1 − Disconnect power and open main control access.

 2 − Disconnect  the  plug  separating  the  high  voltage

wire harness.

 3 − Remove the high voltage wire harness plug and discard.

 4 − Remove the heater blockoff by removing the four

screws holding it in place.

 5 − Cut away insulation covering opening, using the hole

in the panel as a template.

 6 − Insert the heater into the control panel and fasten in

the same mounting holes. See figure 5.

 7 − Plug the heater wiring harness into the wire harness

on the control assembly.

 8 − Field  wiring  of  auxiliary  heater  is  separate  from  unit

power supply. Wire power supply wiring for the heater
to appropriate connections on heater kit.

OPTIONAL ELECTRIC HEAT INSTALLATION

FIGURE 5

HEATER

BLOCKOFF

OPTIONAL

ELECTRIC

HEAT

Electrical

USE COPPER CONDUCTORS ONLY

All field wiring must be done in accordance with National
Electric Code recommendations, local codes and applica
ble requirements of UL or in accordance with Canadian
Electrical Code, local codes and CSA Standards. Power
wiring, disconnect means, and over−current protection are
to be supplied by installer. See unit rating plate for maxi
mum over−current protection, minimum circuit ampacity, as
well as operating voltage. The power supply must be sized
and protected according to specifications supplied. See
figure 6 for field connection of line voltage wiring and fig
ures 7 and 8 for typical wiring diagrams.

CAUTION

When connecting electrical power and control wir
ing to the unit, waterproof type connectors MUST be
used so that water or moisture cannot be drawn into
the unit during normal operation.

208/230 LINE VOLTAGE WIRING

NOTE − If 208 voltage is supplied, transformer connections must be
made.

L1

FUSED DISCONNECT SWITCH

(FURNISHED BY INSTALLER)

GROUND

LUG

L2

FIGURE 6

CONTACTOR

Содержание 12CHP024

Страница 1: ...GED HEAT PUMP UNIT 2 5 TONS 504 176M 06 03 Supersedes 01 00 Table of Contents Shipping Packing List 1 General 1 Unit Dimensions 2 Parts Arrangement 3 Requirements 3 Clearances 4 Rigging Setting Unit 4...

Страница 2: ...UTDOOR COIL EXHAUST AIR A C B B RIGHT SIDE BLOWER C HORIZONTAL RETURN AIR OPENING 048 060 A L E F G G 2 51 FF EE FILTER RACK BASE RAIL 2 7 16 62 4 5 8 117 CENTER OF GRAVITY K K K K J J J J E H N FORKL...

Страница 3: ...gent to remove any residue from manufacturing processes Limitations for unit and appropriate accessories must also be observed The unit must not be installed with any duct system in the outdoor air st...

Страница 4: ...to prevent ice accumulation Unit should not be located near walkways to prevent possible icing of surface from defrost condensate Avoid placing unit near quiet areas i e sleeping quarters or study ro...

Страница 5: ...e control assembly 8 Field wiring of auxiliary heater is separate from unit power supply Wire power supply wiring for the heater to appropriate connections on heater kit OPTIONAL ELECTRIC HEAT INSTALL...

Страница 6: ...Page 6 12CHP Series Heat Pump Packaged Units Typical Wiring Diagram Does not Include 12CHP060 FIGURE 7...

Страница 7: ...Page 7 12CHP060 Series Heat Pump Packaged Units Typical Wiring Diagram FIGURE 8...

Страница 8: ...table could serve as a use ful service guide Table 3 should be used when unit is charged during the heating mode If outdoor ambient is below 45 F run unit through defrost cycle first wait 15 minutes...

Страница 9: ...outdoor fan The reversing valve is not energized in the heating mode The thermostat again automatically brings on the in door blower at the same time Upon satisfying heating de mand the thermostat op...

Страница 10: ...ally consists of changing or cleaning filters and under some conditions cleaning the coils WARNING Electric shock hazard Can cause inju ry or death Before attempting to per form any service or mainten...

Отзывы: