Defrost sensor will be closed at 32

_

 F or below. If tempera

tures are such that switch is not closed, jumper between
defrost sensor terminals on defrost control.

Start system in Heating Operation.

Jumper test pins. A 1/4" quick connect terminal crimped
onto a solid wire or brazing rod works well for test jumper.
Closing test pins speeds up time interval by a factor of 256.

Defrost Control Defrost Test Cycle Time

 

T1−30 minutes

 7 seconds

T2−60 minutes

14 seconds

T3−90 minutes

21 seconds

After closing test pins and appropriate cycle time has
elapsed, the reversing valve should shift to defrost mode
and outdoor fan should stop. After 2 seconds of defrost op
eration, reversing valve should shift back to heating opera
tion and outdoor fan should start.

Adjustments − 

12CHP060 Only

12CHP060 units are equipped with a variable speed indoor
blower motor. The blower speed is factory−set and should
not require field adjustment; however, air volume can be in
creased by 5 percent, if necessary. Follow the procedure
below.

 1 − Disconnect power.

 2 − Locate the blower control board wiring harness.

 3 − To increase air volume (CFM) in the cooling mode, use a

pin extractor to remove the wire from harness pin posi
tion 5 (violet wire).

 4 − To increase air volume (CFM) in the heating mode,

use a pin extractor to remove the wire from harness
pin position 11 (pink wire)

NOTE − If a pin extractor is not available, cut the wire and
tape off both ends.

Maintenance

Periodic inspection and maintenance normally consists of
changing or cleaning filters and (under some conditions)
cleaning the coils.

 

WARNING

Electric shock hazard. Can cause inju
ry or death. Before attempting to per
form any service or maintenance, turn
the electircal power to unit OFF at dis
connect switch(es). Unit may have
multiple power suppplies.

Filters

Not supplied. Inspect once a month. Replace disposable or
clean permanent type as necessary. DO NOT replace per
manent type with disposable.

Outdoor Motor

The outdoor fan motor is permanently lubricated and re
quires no maintenance.

Outdoor Coil

Dirt should not be allowed to accumulate on the outdoor
coil surface or other parts in the air circuit. Cleaning should
be as often as necessary to keep coil clean. Use a brush,
vacuum cleaner attachment, or other suitable means. If
water is used to clean coil, be sure power to the unit is shut
off prior to cleaning.

NOTE − Care should be used when cleaning the coil so that
the coil fins are not damaged.

Repair Parts List

When ordering parts, include the complete model number
and serial number which are printed on the rating plate lo
cated on the unit.

Control Group

Transformer

Blower Group

Blower Housing Assembly
Blower Wheel
Blower Motor
Blower Motor Mount
Blower Motor Capacitor (if used)
Fan Blade
Fan Motor
Fan Motor Capacitor

Cooling Group

Compressor
Coil−Evaporator
Drier
Cap Tube or Expansion Valve
Contactor
Time Delay Relay
Fan Relay
Capacitor
Coil−Condenser
Defrost Control
Reversing Valve Solenoid

Accessories

Description

Kit Number

LENNOX Cat. Number

Low Ambient Control

ALOAM111−1

42K88

High Pressure Cut−out Kit

AHPSW436−1

42K89

Outdoor Thermostat

LB−29740BA

56A87

Timed Off Control

ATIMR446−1

42K90

Содержание 12CHP024

Страница 1: ...GED HEAT PUMP UNIT 2 5 TONS 504 176M 06 03 Supersedes 01 00 Table of Contents Shipping Packing List 1 General 1 Unit Dimensions 2 Parts Arrangement 3 Requirements 3 Clearances 4 Rigging Setting Unit 4...

Страница 2: ...UTDOOR COIL EXHAUST AIR A C B B RIGHT SIDE BLOWER C HORIZONTAL RETURN AIR OPENING 048 060 A L E F G G 2 51 FF EE FILTER RACK BASE RAIL 2 7 16 62 4 5 8 117 CENTER OF GRAVITY K K K K J J J J E H N FORKL...

Страница 3: ...gent to remove any residue from manufacturing processes Limitations for unit and appropriate accessories must also be observed The unit must not be installed with any duct system in the outdoor air st...

Страница 4: ...to prevent ice accumulation Unit should not be located near walkways to prevent possible icing of surface from defrost condensate Avoid placing unit near quiet areas i e sleeping quarters or study ro...

Страница 5: ...e control assembly 8 Field wiring of auxiliary heater is separate from unit power supply Wire power supply wiring for the heater to appropriate connections on heater kit OPTIONAL ELECTRIC HEAT INSTALL...

Страница 6: ...Page 6 12CHP Series Heat Pump Packaged Units Typical Wiring Diagram Does not Include 12CHP060 FIGURE 7...

Страница 7: ...Page 7 12CHP060 Series Heat Pump Packaged Units Typical Wiring Diagram FIGURE 8...

Страница 8: ...table could serve as a use ful service guide Table 3 should be used when unit is charged during the heating mode If outdoor ambient is below 45 F run unit through defrost cycle first wait 15 minutes...

Страница 9: ...outdoor fan The reversing valve is not energized in the heating mode The thermostat again automatically brings on the in door blower at the same time Upon satisfying heating de mand the thermostat op...

Страница 10: ...ally consists of changing or cleaning filters and under some conditions cleaning the coils WARNING Electric shock hazard Can cause inju ry or death Before attempting to per form any service or mainten...

Отзывы: