background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

16

OPTIONAL EQUIPMENT
Combustion Air Kit

Use combustion air kit, Model FOAK-4 or
FOAK-4LD (

Figure 46 ), with these fireplace

systems. Refer to installation instructions
packed with the air kit for specific information.
Outside air drawn into the fireplace supplies air
to the fire for combustion. The outside air kit
must be installed before the fireplace is framed
and enclosed in the finished walls.

IMPORTANT: ALTHOUGH THE COMBUSTION
AIR KIT IS DESIGNATED AS AN OPTIONAL
ACCESSORY IT IS HIGHLY RECOMMENDED
THAT IT BE INSTALLED.  DUE TO THE OPER-
ATING CHARACTERISTICS OF MULTI-OPEN
FIREPLACES, A PROPERLY INSTALLED
SOURCE OF OUTSIDE COMBUSTION AIR CAN
ENHANCE THE OPERATING PERFORMANCE
OF THE APPLIANCE.  THE COMBUSTION AIR
KIT IS NOT REQUIRED FOR THE SAFE OP-
ERATION OF THE LS43ST.

There is a one-hand operated shut-off valve
located on each side of the fireplace opening
behind the screen.  Refer to label for directions
of operation. The combustion air damper
should be fully open when the fireplace is in
operation and fully closed when the fireplace is
not in use to prevent outside air from entering
your home.

If additional length of  duct is necessary,
purchase locally available 4 inch diameter
(12.5 in.

²

) Class 0 or Class 1 ducting. The

duct may extend up to 50' (15.2 m) in any
direction.

Figure 46

Outside combustion air may be run upwards
or vertically through framing and ceiling joists,
with the hood installed through an outside wall
and 3' (914 mm) below the termination. Duct-
ing may also be run downward through floor
joists and under the home to a ventilated
crawlspace not considered part of the living
area of the home.

CHIMNEY OFFSET 30

°

 THROUGH FLOOR

OR CEILING

It may be necessary to assemble the chimney
at 30

°

 when passing through the floor or

ceiling area.  Use the F10FS30-2 firestop
spacer as shown in 

Figures 42 and 43.

Support the chimney at floor or ceiling pen-
etration with a FTF13 stabilizer if distance of
chimney below ceiling is 10' (3 m) or more.
Maintain 2" (51 mm) minimum air space to
combustibles from chimney sections.  The
chimney must pass vertically through the
attic space.

Figure 42

Figure 43

GLASS DOORS

The LS43ST fireplace require the use of glass
doors.  The selection of glass doors available
for use with these fireplace are: 43LSBF,
43LSBF-B, 43LBF, 43LBF-BB, 43LBF-BS and
43TBA.  The use of any other non-listed door
on these fireplaces may result in a potential
fire hazard and is not recommended.

IMPORTANT: IT IS NECESSARY TO ORDER
AND INSTALL THE DOOR STYLE OF YOUR
CHOICE. GLASS DOORS ARE NOT OPTIONAL.

F10FS30-2

Firestop

Spacer

FTF13-S4

Stabilizer

2" (51mm)

Min. Air

Space

2" (51mm)

Min. Air

Space

30

°

 Firestop

and Attic Above

10'

(3m) Max.

Attic Space

2" (51mm)

Min. Air

Space

30

°

 Firestop

and Room Above

10'

(3m) Max.

Room Above

2" (51mm)

Min. Air

Space

F10FS30-2

Firestop

Spacer

FTF13-S4

Stabilizer

Figure 45

Glass Doors

Fully Open

Glass Doors

Fully Closed

Figure 44

Combustion

Air Kit

CAUTION: REMOVE THE PLASTIC PROTEC-
TIVE COATING FROM THE DOORS BRASS
PIECES BEFORE ASSEMBLY AND INSTALLA-
TION. FAILURE TO REMOVE THE COATING
BEFORE FIRST USE WILL RESULT IN DAM-
AGE TO THE BRASS FINISH.

Make a careful inspection of all parts before
installing the doors to insure they are un-
damaged and complete. Always use two (2)
glass door assemblies for each side of the
LS43ST fireplace.

CAUTION: DO NOT TOUCH THE DOORS WITH
YOUR HANDS WHILE THE FIREPLACE IS IN
USE. ALWAYS USE DOOR HANDLES.
DOORS WILL BECOME VERY HOT WHEN
FIREPLACE IS IN USE.

Note: Design characteristics of a dual-opening
fireplace (whether masonry or factory-built)
may cause it to not draft properly and smoke.
For this reason, glass doors are required with
the LS43ST fireplace.

W A R N I N G :   T H E S E   F I R E P L A C E S
SHOULD BE OPERATED ONLY WITH
THE DOORS FULLY OPEN OR FULLY
CLOSED (

FIGURES 44 AND 45 ).  IF

DOORS ARE LEFT PARTLY OPEN, GAS
AND FLAME MAY BE DRAWN OUT OF
THE FIREPLACE OPENING, CREATING
RISKS OF BOTH FIRE AND SMOKE.

Содержание MAGNA-FIRE LS43ST

Страница 1: ...ponents under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and accessories may void the warranty listings and...

Страница 2: ...ensure a safe fireplace system and to prevent the build up of soot and creosote inspect and clean the fireplace and chimney priortouseandperiodicallyduringtheheating season 5 Use solid fuel only DO N...

Страница 3: ...place and chimney system must be enclosed when installed in or passing through a living area where combustibles or people may come in contact with it This is important to prevent possible personal inj...

Страница 4: ...er just behind the firebox lintel Figure 3 The control lever snaps into place at the ex treme range of motion up and back in the closed position When pulled forward and down the damper is open Figure...

Страница 5: ...d and the fireplace positioned into the opening Usually no special floor support is needed for the fireplace however to be certain 1 Estimate the total weight of the fireplace system including chimney...

Страница 6: ...n 51 mm Platform Metal Safety Strips 2 Min 51 mm Figure 10 Figure 12 Figure 11 IMPORTANT UNDER NO CIRCUMSTANCES CAN THE FIREPLACE TOP SPACERS FIGURE 10 BE REMOVED OR MODIFIED NOR MAY YOU NOTCH THE HEA...

Страница 7: ...TO SCALE 7 Figure 14 Figure 15 Figure 16 FRAMING SPECIFICATIONS 26 667 mm 54 1391 mm 58 1490 mm 47 1197 mm 47 1197 mm 58 1490 mm Front View 54 1391 mm 19 489 mm Allow 19 For Clearance 26 667 mm For D...

Страница 8: ...NS Figure 17 27 700 mm Top View Front View End View 27 701 mm 8 216 mm 20 508 mm 44 1121 mm 42 1086 mm Outside Air Inlet This Side Only Gas Line Inlet 9 241 mm 11 298 mm 52 1335 mm 24 625 mm 52 1340 m...

Страница 9: ...extending for any continuous length surrounding the chimney See Figures 26 and 27 and charts Framing Dimensions for Ceiling and Roof on page 10 which specify minimum ceiling and roof di mensions For n...

Страница 10: ...ing tabs 7 locking tabs per joint Check each piece by pulling up slightly from the top to ensure proper engage ment before installing succeeding sections If the flue has been installed correctly it wi...

Страница 11: ...band at the pipe joint Locking bands wrap around pipe joints equally covering the joints of both pipe sections Use nut provided and TIGHTEN snugly Do not over tighten as this might damage chimney sec...

Страница 12: ...of the components are LS43ST Fireplace 58 1486 mm FTF13 12 10 260 mm FTF13 18 16 413 mm FTF13 36 34 870 mm CTD Termination 4 102 mm CT1 Termination 18 457 mm CT2 Termination 15 to 23 381 mm 584 mm CTD...

Страница 13: ...hes Feet Inches 12 18 36 MM M 461 38 5 0 1 13 11722 11 72 465 38 9 2 0 13 11824 11 82 471 39 3 1 1 13 11976 11 98 479 39 11 0 0 14 12179 12 18 489 40 9 1 0 14 12433 12 43 495 41 3 0 1 14 12586 12 59 4...

Страница 14: ...0 641 1334 26 54 1 0 1 0 1 667 1378 28 57 1 0 0 3 0 718 1467 29 59 1 0 0 1 1 743 1505 31 63 1 0 2 0 1 794 1600 32 65 1 0 4 1 0 826 1651 34 68 1 0 1 1 1 870 1734 36 71 1 0 3 0 1 921 1822 37 73 1 0 0 2...

Страница 15: ...must not be assembled to form a 60 offset However two sets of offset and return elbows may be used on a single flue system provided the total height of the system exceeds 22 5 6 m Return elbow support...

Страница 16: ...2 and 43 Support the chimney at floor or ceiling pen etration with a FTF13 stabilizer if distance of chimney below ceiling is 10 3 m or more Maintain 2 51 mm minimum air space to combustibles from chi...

Страница 17: ...sted and approved to ANSI IAS AGA Z21 11 2 for use with unvented gas appliances and complies with the stan dard for Factory Built fireplaces UL 127 The unit has been tested for use with any unventedga...

Страница 18: ...Stone Hearth stone 2 82 355 3 36 3 3 8 Wonderboard 3 23 31 3 85 3 7 8 Super Firetemp M Johns Manville 61 1 64 73 3 4 Super Firetemp L Johns Manville 54 1 85 64 5 8 Face brick 9 00 111 10 71 10 3 4 Co...

Страница 19: ...r lower k value insulating value than k 54 BTU IN FT2 HR F At no time may a perpendicular side wall be located closer than 9 from the fireplace opening If fireplace is installed diagonally across a 90...

Страница 20: ...ion 1110 West Taft Avenue Orange CA 92865 INSTALLATION COMPONENTS Offset Return Package 30 63L24 FTF13 ES30 Chase Termination Square 63L54 FTF13 CT2 63L19 FTF13 12 63L20 FTF13 18 Chimney Section 63L21...

Отзывы: