NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

4

CHIMNEY SYSTEM

These fireplaces are designed and code listed
for use with Security Chimneys FTF13 chimney
System only. Always use Security Chimneys
FTF13 chimney components with these fire-
places. Do not modify or alter these compo-
nents as this may cause a potential serious
hazard and void the Warranty.

Figure 2

Note: Do not insulate the chase cavity with
blown or fill type insulation materials.

Chimney Height

The total height of your LS43ST fireplace
system from the surface the fireplace rests
on to the chimney top must not exceed 80'
(24.4m) and must also meet minimum sys-
tem height chart.

Minimum System Height

Model LS43ST

Security's

FTF13

Vertical Installation

14' 0" (3.7 m)

One Offset

15 

¹⁄₂

 0" (3.9 m)

Two Offsets

22' 0" (5.6 m)

Chase Enclosure

A chase is a vertical box-like structure con-
structed to surround the fireplace and chim-
ney. Refer to 

Figure 2 for a typical chase

configuration. A chase should be constructed
and insulated just like any outside wall.  Chase
insulation in a cold climate installation is not
required for safety.

ASSEMBLY OUTLINE
Before You Start

Check your inventory list to be sure you have all
the necessary parts supplied in good usable
condition. Check also for any concealed damage.

Check the operation of the damper. The damper
is controlled through the use of a control lever
located within the firebox opening at the top
center just behind the firebox lintel (

Figure 3 ).

The control lever snaps into place at the ex-
treme range of motion, up and back in the
closed position.  When pulled forward and
down, the damper is open.

Figure 3

Damper

Closed

Damper
Open

Lintel

LOCATION OF FIREPLACE

Carefully select the proper location for heat
circulation, aesthetics, chimney obstructions
and clearance to side wall(s). With proper pre-
planning, a slight adjustment of a few inches
can save considerable time and expense later
during construction and assembly.

Figure 4

Insulate Joists

Same As Ceiling

Draft Stops

Firestop

FTF13
CTDT
Termination

Note: Non-

Combustible

Chase

Flashing

Must Be

Used To

Cover

Chase

Opening

Optional

Insulation

In Outside

Walls Of

Chase

Solid

Continuous

Surface

Outside

Base

Insulation
(Thermal Barrier)

8'

Level

Carefully consider the position of the fireplace
opening with respect to the location of adja-
cent or nearby stairwells, bath or kitchen ex-
haust fans and/or return air registers for forced
air furnaces/air conditioners that could cause
a smoking fireplace condition if the house is
tightly insulated.

This system is intended to be installed in resi-
dential homes and buildings of conventional
construction, not in mobile homes.

WARNING: DO NOT PACK OR FILL RE-
QUIRED AIR SPACES WITH INSULATION
OR OTHER MATERIAL. NO MATERIAL IS
ALLOWED IN THESE AREAS.

WARNING: IF INSULATION IS USED, THE
FIREPLACE MUST NOT BE PLACED DI-
RECTLY AGAINST IT. INSULATION OR
VAPOR BARRIERS, IF USED, MUST FIRST
BE COVERED WITH GYPSUM BOARD,
PLYWOOD, PARTICLE BOARD OR OTHER
MATERIAL TO ASSURE INSULATION AND
VAPOR BARRIERS REMAIN IN PLACE.

Содержание MAGNA-FIRE LS43ST

Страница 1: ...ponents under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and accessories may void the warranty listings and...

Страница 2: ...ensure a safe fireplace system and to prevent the build up of soot and creosote inspect and clean the fireplace and chimney priortouseandperiodicallyduringtheheating season 5 Use solid fuel only DO N...

Страница 3: ...place and chimney system must be enclosed when installed in or passing through a living area where combustibles or people may come in contact with it This is important to prevent possible personal inj...

Страница 4: ...er just behind the firebox lintel Figure 3 The control lever snaps into place at the ex treme range of motion up and back in the closed position When pulled forward and down the damper is open Figure...

Страница 5: ...d and the fireplace positioned into the opening Usually no special floor support is needed for the fireplace however to be certain 1 Estimate the total weight of the fireplace system including chimney...

Страница 6: ...n 51 mm Platform Metal Safety Strips 2 Min 51 mm Figure 10 Figure 12 Figure 11 IMPORTANT UNDER NO CIRCUMSTANCES CAN THE FIREPLACE TOP SPACERS FIGURE 10 BE REMOVED OR MODIFIED NOR MAY YOU NOTCH THE HEA...

Страница 7: ...TO SCALE 7 Figure 14 Figure 15 Figure 16 FRAMING SPECIFICATIONS 26 667 mm 54 1391 mm 58 1490 mm 47 1197 mm 47 1197 mm 58 1490 mm Front View 54 1391 mm 19 489 mm Allow 19 For Clearance 26 667 mm For D...

Страница 8: ...NS Figure 17 27 700 mm Top View Front View End View 27 701 mm 8 216 mm 20 508 mm 44 1121 mm 42 1086 mm Outside Air Inlet This Side Only Gas Line Inlet 9 241 mm 11 298 mm 52 1335 mm 24 625 mm 52 1340 m...

Страница 9: ...extending for any continuous length surrounding the chimney See Figures 26 and 27 and charts Framing Dimensions for Ceiling and Roof on page 10 which specify minimum ceiling and roof di mensions For n...

Страница 10: ...ing tabs 7 locking tabs per joint Check each piece by pulling up slightly from the top to ensure proper engage ment before installing succeeding sections If the flue has been installed correctly it wi...

Страница 11: ...band at the pipe joint Locking bands wrap around pipe joints equally covering the joints of both pipe sections Use nut provided and TIGHTEN snugly Do not over tighten as this might damage chimney sec...

Страница 12: ...of the components are LS43ST Fireplace 58 1486 mm FTF13 12 10 260 mm FTF13 18 16 413 mm FTF13 36 34 870 mm CTD Termination 4 102 mm CT1 Termination 18 457 mm CT2 Termination 15 to 23 381 mm 584 mm CTD...

Страница 13: ...hes Feet Inches 12 18 36 MM M 461 38 5 0 1 13 11722 11 72 465 38 9 2 0 13 11824 11 82 471 39 3 1 1 13 11976 11 98 479 39 11 0 0 14 12179 12 18 489 40 9 1 0 14 12433 12 43 495 41 3 0 1 14 12586 12 59 4...

Страница 14: ...0 641 1334 26 54 1 0 1 0 1 667 1378 28 57 1 0 0 3 0 718 1467 29 59 1 0 0 1 1 743 1505 31 63 1 0 2 0 1 794 1600 32 65 1 0 4 1 0 826 1651 34 68 1 0 1 1 1 870 1734 36 71 1 0 3 0 1 921 1822 37 73 1 0 0 2...

Страница 15: ...must not be assembled to form a 60 offset However two sets of offset and return elbows may be used on a single flue system provided the total height of the system exceeds 22 5 6 m Return elbow support...

Страница 16: ...2 and 43 Support the chimney at floor or ceiling pen etration with a FTF13 stabilizer if distance of chimney below ceiling is 10 3 m or more Maintain 2 51 mm minimum air space to combustibles from chi...

Страница 17: ...sted and approved to ANSI IAS AGA Z21 11 2 for use with unvented gas appliances and complies with the stan dard for Factory Built fireplaces UL 127 The unit has been tested for use with any unventedga...

Страница 18: ...Stone Hearth stone 2 82 355 3 36 3 3 8 Wonderboard 3 23 31 3 85 3 7 8 Super Firetemp M Johns Manville 61 1 64 73 3 4 Super Firetemp L Johns Manville 54 1 85 64 5 8 Face brick 9 00 111 10 71 10 3 4 Co...

Страница 19: ...r lower k value insulating value than k 54 BTU IN FT2 HR F At no time may a perpendicular side wall be located closer than 9 from the fireplace opening If fireplace is installed diagonally across a 90...

Страница 20: ...ion 1110 West Taft Avenue Orange CA 92865 INSTALLATION COMPONENTS Offset Return Package 30 63L24 FTF13 ES30 Chase Termination Square 63L54 FTF13 CT2 63L19 FTF13 12 63L20 FTF13 18 Chimney Section 63L21...

Отзывы: