Lennox Hearth Products Elite LBC-3824 Скачать руководство пользователя страница 9

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

9

CHIMNEY 30

°

 OFFSET THROUGH FLOOR

OR CEILING

It may be necessary to assemble the chimney at
30

°

 when passing through the floor or ceiling

area.  Use the F10FS30-2 firestop spacer as
shown in 

Figures 23 and 24.  Support the

chimney at floor or ceiling penetration with a
FTF10 stabilizer if distance of chimney below
ceiling is 10' or more. Maintain 2" minimum air
space to combustibles from chimney sections.

F10FS30-2

Firestop Spacer

FTF10-S4

Stabilizer

2" Min.

Air Space

30

°

 Firestop

And Attic Above

10'

Max.

Attic Space

2" Min.

Air Space

F10FS30-2

Firestop Spacer

FTF10-S4

Stabilizer

30

°

 Firestop

And Room Above

10'

Max.

Room Above

2" Min.

Air Space

2" Min.

Air Space

Figure 21

Figure 22

Firestop Spacer

Room Above

Firestop Spacer

Attic Above

Figure 23

Figure 24

For Canada Only

When installing the chimney system through
an open attic space, the attic shield assembly-
firestop spacer must be used (

Figure 25 ). This

installation is required only for use in Canada.

Locking

Tabs

(Lances)

Note: For Canadian installations, all chimney
installed outside the building must be constructed
with galvalume (outer sections only) effective
January 1, 1992. The appropriate model desig-
nations are located in the back of this manual.

The FTF10 chimney system is a two piece chim-
ney that snap locks together from the fireplace
up.  Always start with the inner flue section. With
the lanced end up, snap lock the joint into the
matching collar on top of the fireplace. At all
subsequent joints, the upper flue section fits into
the lower or preceding flue section. Each section
snaps together by means of locking tabs (9 tabs
per joint). Check each section by pulling up
slightly from the top to ensure proper engage-
ment before installing succeeding sections. If
the flue has been installed correctly, it will not
separate when tested. Also, the inner flue joint
where each section is joined should be tight and
flat without gaps (

Figure 26 ).

Figure 26

The outer chimney section installs the opposite
way; the lanced end goes down and each new
section installs OVER the outside of the previ-
ous section (

Figure 27 ).

Figure 27

Figure 25

Step 4.

  Note: All chimney sections are con-

structed with a unique locking tabs and hem
design, which ensures and immediate, tight
assembly between sections. Plan your chimney
requirements carefully before assembly, as the
chimney is difficult to disassemble after instal-
lation. If disassembled, the tabs might become
damaged. Be certain that the tabs are properly
formed to ensure they engage properly.

Step 3. Position the appropriate firestop
spacer at the ceiling and nail temporarily with
two (2) 8d nails. Use a flat firestop spacer,
Model F10FS-2, for the FTF10 system if chim-
ney penetrates vertically. If the chimney pen-
etrates through the ceiling at a 30

°

 angle (offset

chimney) then use a 30

°

 firestop spacer, Model

F10FS30-2. Use one nail on opposite sides of
the firestop to hold in position. Nail perma-
nently, using at least two (2) more 8d nails,
after the chimney sections have been assembled
through the firestop spacer and after necessary
adjustments have been made. The firestop
spacer must be secured in place by at least four
(4) 8d nails when completely installed.

Note: If there is a room above the ceiling level,
the firestop spacer must be installed on the
bottom side of the ceiling. If an attic is above the
ceiling level, the firestop spacer must be in-
stalled on the top side of the ceiling joists
(Figures 21 and 22 ).

Open Attic Space

Содержание Elite LBC-3824

Страница 1: ...beginning your installation Do not alter or modify the fireplace or its components under any circumstances Any modification or alteration of the fireplace system including but not limited to the fire...

Страница 2: ...as a result of handling or transporta tion These items should be inspected by your distributor or qualified factory representative to ensure safe condition When in doubt con sult your distributor 16...

Страница 3: ...re Protection Standard for chimneys fireplaces and solid fuel burning appliances NFPA 211 and in accordance with codes such as the BOCA Basic National Codes the Standard Me chanicalCodeandtheUniformBu...

Страница 4: ...ed for safety and the reduction of heat loss Chimney Height The total height of your completed fireplace system from the surface the fireplace rests on to the chimney top must not exceed 80 24 4 and m...

Страница 5: ...be certain 1 Estimate the total weight of the fireplace system including chimney and surround ma terials such as brick stone etc to be in stalled Shippingweightsforthefireplacemay be found on page 18...

Страница 6: ...7 IMPORTANT UNDER NO CIRCUMSTANCES CAN THE FIREPLACE TOP SPACERS FIGURE 10 BE REMOVED OR MODIFIED NOR MAY YOU NOTCH THE HEADER TO FIT AROUND OR BE INSTALLED LOWER THAN THE SPACERS THE HEADER MAY BE IN...

Страница 7: ...15 Figure 16 Figure 14 Note All framing dimensions calculated for 1 2 dry wall at the fireplace face If sheathing the chaseorfinishingwithotherthicknessmaterials calculations will need to be made FRA...

Страница 8: ...ing or roof above Drive a nail through the ceiling or roof frombelowtomarkposition Markandcutahole intheceiling aroundthenail Figure20 Then plumb from ceiling or roof directly above the cut hole to de...

Страница 9: ...int Check each section by pulling up slightly from the top to ensure proper engage ment before installing succeeding sections If the flue has been installed correctly it will not separate when tested...

Страница 10: ...chimney system Install the Model FTF10 S4 stabilizer by fitting inner section down into respective section of proceeding flue pipe and locking outer stabi lizer section into place over the outer chimn...

Страница 11: ...be at least 2 above this reference point In all cases the chimney cannot be less then 3 above the roof at the edge of the chimney The 2 in 10 rule is necessary in the interest of safety but does not...

Страница 12: ...Figure 29 3 The effective heights of the components are The Fireplace 48 3 8 FTF10 12 10 1 4 FTF10 18 16 1 4 FTF10 36 34 1 4 FTF10 CTDTM Termination 13 FTF10 CT1 Termination 12 to 18 FTF10 CT2 Termin...

Страница 13: ...hes Feet Inches 12 18 36 MM M 461 38 5 0 1 13 11722 11 72 465 38 9 2 0 13 11824 11 82 471 39 3 1 1 13 11976 11 98 479 39 11 0 0 14 12179 12 18 489 40 9 1 0 14 12433 12 43 495 41 3 0 1 14 12586 12 59 4...

Страница 14: ...of FTF10 A B Offset Height Offset Return FTF10 S4 Chimney Sections Offset Height Inches Inches Elbow Set Stabilizer 12 18 36 mm mm 4 15 1 0 0 0 0 102 400 9 24 1 0 1 0 0 229 622 12 29 1 0 0 1 0 305 756...

Страница 15: ...WHERE IT COULD BE BLOCKED BY SHRUBS SNOWDRIFTS ETC NEVERLOCATEAIRINLET IN A GARAGE OR IN ANY AREA WHERE THERE IS ANOTHER FUEL BURNING APPLIANCE OR PRODUCTS EMITTING COMBUSTIBLE GASES SUCH AS PAINT GA...

Страница 16: ...cold air could enter the room Surrounding materials must be caulked where it meets the black metal facing of the fireplace to avoid cold air intrusion Use noncombus tible caulking material only on fir...

Страница 17: ...lle 54 1 85 64 5 8 Face brick 9 00 111 10 71 10 3 4 Common brick 5 00 20 5 95 6 Cement mortar 5 00 20 5 95 6 Ceramic tile 12 5 08 14 88 14 7 8 Marble 11 09 13 10 13 1 8 Table 1 Methods of Determining...

Страница 18: ...der the hearth extension refer to Figures 6 7 A wall shield is required where a continuous perpendicular side wall is within 12 of the fireplace opening Figure 46 Use a 36 W x 36 H wall shield constru...

Страница 19: ...Allowed in Shaded Area 1 25mm 18 457mm Minimum Distance to Protected Side Wall LBR Models Figure 50 4 17 32 115mm 30 Combustible Materials Allowed in Shaded Area 1 2 13mm 12 305mm Minimum Distance to...

Страница 20: ...EARTH PRODUCTS P N 850 003M REV G 01 2010 INSTALLATION COMPONENTS CONTINUED NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 1110 West Taft Avenue Orange CA 92865 Forced Air Kit 12M73 LFAK 2000 Cold Climate K...

Отзывы: