13

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Figure 22

Figure 23

Figure 25

Figure 24

If the vent system extends more than 5' (1.5 m)
above the roof flashing, stabilizers may be nec-
essary. Additional screws may be used at section
joints for added stability. Guide wires may be
attached to the joint for additional support on
multiple joint configurations.

G. Continue installation of horizontal/inclined
sections -
 Continue with the installation of the
straight vent sections in horizontal/inclined
run as described in Step C. Install support
straps every 5 ft. (1.52 m) along horizontal/
inclined vent runs using conventional
plumber’s tape. 

See page 16, Figure 31. It is

very important that the horizontal/inclined
run be maintained in a straight (no dips) and
recommended to be in a slightly elevated
plane, in a direction away from the fireplace
of 
1/4" rise per foot (20 mm per meter) which is
ideal, though rise per foot run ratios that are
smaller are acceptable all the way down to at or
near level.  Use a carpenter’s level to measure
from a constant surface and adjust the support
straps as necessary.

It is important to maintain the required clear-
ances to combustibles: 1" (25 mm) at all sides
for all vertical runs; and 3" (76 mm) at the top,
1" (25 mm) at sides, and 1" (25 mm) at the
bottom for all horizontal/inclined runs.

Figure 21

One method of support is by utilizing field
provided support straps (conventional
plumber's tape).  Secure the plumber's tape
to the framing members with nails or screws.
Loop the tape around the vent, securing the
ends of the tape to the framing. If desired,
sheet metal screws #6 x 1/2" length may be
used to secure the support straps to the vent
pipe.  Refer to 

Figure 20.

F. Change vent direction to horizontal/in-
clined run -
 At transition from or to a horizon-
tal/inclined run, install the SV4.5E45 and
SV4.5E90 elbows in the same manner as the
straight vent sections. The elbows feature a
twist section to allow them to be routed about
the center axis of their initial collar section to
align with the required direction of the next
vent run element. Twist elbow sections in a
clockwise direction only so as to avoid the
possiblity of unlocking any of the previously
connected vent sections.
 See 

Figure 21.

K. Install the vertical termination - The final
step involves installation of the SV4.5CGV-1
Vertical Termination.  Extend the vent sec-
tions to the height as shown in the "Vertical
vent termination section" on page 5. The
SV4.5CGV-1 Vertical Termination 

(Figure 25)

can be installed  in the exact same fashion as
any other Secure Vent section. Align the
termination over the end of the previously
installed section, adjusting the radial align-
ment until the four locking dimples of the
termination are aligned with the inlets of the
four incline channels of the last vent section.
Push the termination down until it fully en-
gages, then twist the termination clockwise
running the dimples down and along the
incline channels until they are seated at the
end of the channels.

I.  Install the roof flashing - Extend the vent
sections through the roof structure. Install the
roof flashing over the vent section and position
such that the vent column rises vertically (use
carpenters level) (

Figure 23 ). Nail along pe-

rimeter to secure flashing or adjust roofing to
overlap the flashing edges at top and sides only
and trim where necessary. Seal the top and both
sides of the flashing with waterproof caulking.

J. Install the storm collar - Install the storm
collar, supplied with the flashing, over the
vent/flashing joint. See 

Figure 24. Loosen the

storm collar screw. Slide collar down until it
meets the top of the flashing. Tighten the
adjusting screw. Apply non-combustible caulk-
ing or mastic around the circumference of the
joint to provide a water tight seal.

SV4.5E90

(90

°

 Elbow)

8-1/8"

(206 mm)

Swivel Joint

(360

°

 swivel)

4-13/16"

(122 mm)

SV4.5E45

(45

°

 Elbow)

Swivel Joint

(360

°

 swivel)

C

D

Storm

Collar

H. Frame roof opening - Identify location for
vent at the roof. Cut and/or frame opening per
Roof Framing Chart and 

Figure 22.

Framing Dimensions for Roof

Pitch

C

D

0/12

10-1/2 in.

10-1/2 in.

(267 mm)

(267 mm)

6/12

10-1/2 in.

12 in.

(267 mm)

(305 mm)

12/12

10-1/2 in.

17-3/4 in.

(267 mm)

(451 mm)

Содержание Direct Vent MPD-33 Series

Страница 1: ...850 014CF Ce manuel d installation est disponible en francais simplement en faire la demande Num ro de la pi ce 850 014CF s l e d o M t l o v i l l i M s l e d o M c i n o r t c e l E M N C 8 2 3 3 T...

Страница 2: ...ntsmanu facturedbySecurityChimneysInternationaland Z Flex Model GA Venting Systems listed to UL1777 and ULCS635 manufactured by Flex master Canada Limited These approved vent system components are lab...

Страница 3: ...rving a separate solid fuel burning appliance These heater rated appliances are intended for use as supplemental heaters only Carbon Monoxide Poisoning Early signs of carbon monoxide poisoning are sim...

Страница 4: ...ble 2 APPLIANCE AND VENT CLEARANCES The appliance is approved with zero clearance to combustible materials on all sides as de tailed in Table 2 with the following exception When the unit is installed...

Страница 5: ...e and do not supersede local codes in any way Install vent according to local codes these instructions the current National Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CGA B14...

Страница 6: ...or securing the glass door Remove the door by tilting it outward at the bottom and lifting it up Set the door aside protecting it from inadvertent damage See Figure 53 on page 24 The fireplace should...

Страница 7: ...o t a l u g e r r e t e m t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e...

Страница 8: ...MPD 4540 Models Dimensions D and F occur when one 45 degree elbow is connected directly to the appliance collar MPD and MPDR units D E F A B MPD and MPDT units o N l e d o M A B C D E 8 2 3 3 T D P M...

Страница 9: ...3 8 1 5 4 6 1 1 1 6 2 8 7 4 3 6 1 7 7 1 9 3 9 3 6 1 m m 6 4 1 1 3 4 9 0 1 6 3 0 0 1 6 4 1 1 8 7 6 6 8 8 3 4 4 0 2 2 6 7 0 2 2 6 7 6 0 4 Step 3 INSTALL THE VENT SYSTEM General Information Theseinstruc...

Страница 10: ...ALL AND SECURELY TIGHTEN COVER PLATE SCREWS COULD RESULT IN LEAKAGE OF FLUEPRODUCTSINTOTHELIVINGSPACE VENTCOVERPLATEANDVENTSEALPLATE MUSTREMAINSECURELYINSTALLEDON UNUSED VENT COLLAR FAILURE TO DO SO C...

Страница 11: ...2 5 2 1 8 1 0 1 0 6 0 7 5 9 2 2 5 2 1 9 1 0 0 1 6 0 7 5 2 3 2 5 7 3 9 1 0 0 0 0 5 5 7 3 2 5 7 9 1 1 0 0 0 5 6 5 1 4 2 5 2 1 0 2 0 0 0 7 0 7 6 4 2 5 0 2 1 0 0 7 0 8 2 5 2 1 2 0 1 0 7 0 8 4 6 2 2 2 0 0...

Страница 12: ...nd number of elbows required Refer to Vertical Vent Figures and Tables on page 14 and 15 to select the type of vertical installation desired Vent sections are available in net lengths of 4 1 2 114 mm...

Страница 13: ...ction to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of unlocking any of the previously connected ve...

Страница 14: ...ed then 4 feet mini mum V vertical vent will be required This table shows a 1 V to 2 H ratio For every 1 foot of V vertical you are allowed 2 feet of H horizontal run up to a maximum horizontal run of...

Страница 15: ...V1 Ceiling Firestop Spacer SV4 5VF Wall Firestop Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When using Secure Flex use Firestop Spacer SF4 5HF Example If20feetof H horizontalven...

Страница 16: ...Push the vent component against the previous section until it fully engages then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of th...

Страница 17: ...the telescopic vent section SV4 5LA as the last vent section For wall thicknesses greater than that shown in Figure 32 refer to Table 4 on page 18 This table lists the additional venting components ne...

Страница 18: ...level Note Secure Vent components rigid vent pipe and terminal are shown in the figures SecureFlexcomponents flexibleventpipeand terminal may also be used Note Two45degreeelbowsmaybeusedinplace ofone...

Страница 19: ...s meters meters H1 V H Wall Firestop Spacer SV4 5HF Ceiling Firestop Spacer SV4 5VF When using Secure Flex use Firestop Spacer SF4 5HF When using Secure Flex use Firestop Spacer SF4 5VF Example If 20...

Страница 20: ...feet of H horizontal run up to a maxi mum horizontal run of 20 feet An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system See Figure 35...

Страница 21: ...with the inlets of the four incline channels of the last vent sectionorcollar Pushontheadapteruntilitfully engages then twist the adapter clockwise run ning the dimples down and along the incline chan...

Страница 22: ...and Honeywell Millivolt Wiring See Figure 43 1 Select any of the following optional con trols appliance mounted rocker switch or wall mounted switch thermostat oroneofthe optional remote control kits...

Страница 23: ...G e t i h W l a r t u e N OPENING CONTROL COMPARTMENT DOOR The millivolt control valve has a 3 8 10 mm NPT thread inlet port The electronic control valve has a 1 2 13 mm NPT thread inlet port and is f...

Страница 24: ...he firebox floor to the door s vee flange Close both the latches securely Electronic Appliance Checkout To light the burner turn ON the optional remote wall switch and turn the gas control switch to t...

Страница 25: ...N 8 1 2 3 p o r P 2 1 3 1 Figure 54 The adjustment rod and associated adjustable air shutter is patented technology Flame ad justments can be made quickly and accurately to taste without the need of...

Страница 26: ...ent door Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements Note Combustible wall finish materials and or surround mat...

Страница 27: ...m 0 1 6 h c n i 4 2 n o i t c e S 3 7 L 7 7 6 3 L 5 4 V S t n e V m m 4 1 9 h c n i 6 3 n o i t c e S 4 7 L 7 7 8 4 L 5 4 V S t n e V m m 9 1 2 1 h c n i 8 4 n o i t c e S 5 7 L 7 7 A L 5 4 V S n o i...

Страница 28: ...x e l F r o f n i m r e T l a c i t r e V n o i t c e s r e t p a d A x e l F h t i w 2 1 2 1 r a l l o c t r o p p u s f o o r t n e v d i g i r f o d n a g n i h s a l f f o o r y l b m e s s a r a...

Страница 29: ...ecuring screws WARNING THIS CONVERSION KIT SHALL BE INSTALLED BY A QUALIFIED SERVICE AGENCY IN ACCORDANCE WITH THE MANUFACTURER S IN STRUCTIONS AND ALL APPLICABLE CODES AND REQUIREMENTS OF THE AUTHORI...

Страница 30: ...re 61 s m e t s y S T I S t l o v i l l i M n o i s r e v n o C s a G e n a p o r P o T l a r u t a N s t i K s l e d o M e p y T t i n U o N g o l a t a C 8 2 3 3 T D P M 8 2 3 3 R D P M t l o v i l...

Страница 31: ...On Any Side Of The Hex Fitting b Attach manometer to the manifold side pressure test fitting and verify manifold pres sure reads 3 5 inches water column 0 87 kPa for natural gas and 10 0 inches water...

Страница 32: ...it Remove the slotted cap screw o ring pressure regulating adjusting screw and spring Retain all parts for possible later use Install new components from the kit Black cap and red spring for propane g...

Отзывы: