9
Setting operating parameters
9.1
Generalities
All the control devices are set and tested in the factory before the unit is dispatched. However,
after the unit has been in service for a reasonable period you can perform a check on the
operating and safety devices. The settings are shown in Table 13.
WARNING
All servicing of the equipment is to be considered extraordinary maintenance and
may be carried out BY QUALIFIED TECHNICIANS ONLY: incorrect settings may cause
serious damage to the unit and injuries to persons.
The operating parameters and control system settings configurable by means of the
microprocessor control are password protected if they have a potential impact on the integrity of
the unit.
Table 13
Setting of control devices.
Control device
Set point
Differential
Differential air pressure switch (air flow)
70
30
Pa
Differential air pressure switch (dirty filter)
70
20
Pa
INNOV@-DHF-IOM-0922-EN
• 26•