between the protective ground “PE” and the mains connection. The protective earth
is conducting high discharge currents (dependent on the switching frequency,
current source voltage and motor capacity). Earthing in compliance with EN
specifications shall therefore be observed even for testing and trial conditions (EN
50 178, Art.5.2.11).
Regarding the differential protection that needs to be installed upstream, it is necessary to use a
type A switch that is sensitive to direct currents. It is mandatory for it to have the following
features:
•
Calibratable operation threshold;
•
Calibratable operation delay.
•23•
INNOV@-DHF-IOM-0922-EN