3

460989001B 

Installing Jumpers

Jumper configuration 

Host communications:

Jumper J22 pins 1 & 2 for RS-485 reader communications. Install the 
jumper on last the SDC on the communications line.

Reader output voltage selection:

Jumper J12 pins 1 & 2 for +12VDC readers

Jumper J12 pins 2 & 3 for +5VDC readers

Reader RS-485 termination:

Jumper J20 pins 1 & 2 for RS-485 reader communications

Note:

Do NOT install the jumper for Wiegand/Clock & Data/F2F 
Reader Communications.

Reader data line pull-up voltage selection:

Jumper 9 pins 1 & 2 for +12VDC data lines

Jumper 9 pins 2 & 3 for +5VDC data lines

Notes:

Some readers have data lines pulled up to +5 while the data lines 
of other readers are pulled up to +12 VDC. Therefore, you need 
to set these to match your reader.

NOT required for RS-485 communications.

Jumper J21 is not used.

Status LEDs

LED Table for Series 2 LNL-1300 Mode

When switch 5 is in the ON position, the LEDs behave like the series 2 
LNL-1300.

LED Table for Normal Mode

When SW1 switch 5 is in the off position, the LEDs operate in Normal 
Mode.
External tamper (cabinet tamper) must be open for Input LEDs to be on. 
When tamper is closed (cabinet door closed) Input LEDs will be off.

Indication

LED

State

Power-up

ALL

Off

Initialization

D45

Flashing

After initialization

D45

Offline: 1 second rate, 20% ON
Online: 1 second rate, 80% ON

Communications

D1

ON

Indication

LED

State

RS-485 panel 
communication

D1

ON - Yellow

Reader 1 RS-485 
communication

D8

ON - Yellow

Power on

D18

ON - Green

Relay 1

D28

ON - Green

Relay 2

D36

ON - Green

Supervised input 
I1-I2

D40, D41

Active: ON - Yellow
Inactive: ON - Green
Foreign: ON - Red
Cut: Flashing - Green
Short: Flashing - Red
Ground: Flashing - Yellow

Unsupervised I1-I2

D40, D41

Closed ON - Red,
Open - Off

CPU status

D45

Offline: 1 second rate, 20% ON
Online: 1 second rate, 80% ON
Flash Green - Badge Read

External (cabinet) 
tamper

D46

Open ON - Red

Содержание LNL-1300-U

Страница 1: ...es a 12 to 24 VDC power source SDC board Dimensions are in inches mm Package Contents LNL 1300 U board 1000 ohm resistors Installation To install the SDC perform the installation procedures described...

Страница 2: ...bps off ON off ON 38400 bps ON ON ON ON SW1 Switch 5 State ON LEDs behave as the Access LNL series module off LED behavior is in Normal Mode Address SW2 switch 5 4 3 2 1 0 off off off off off 1 off o...

Страница 3: ...Ds LED Table for Series 2 LNL 1300 Mode When switch 5 is in the ON position the LEDs behave like the series 2 LNL 1300 LED Table for Normal Mode When SW1 switch 5 is in the off position the LEDs opera...

Страница 4: ...modem packet and terminated the firmware download operation Invalid Application firmware for module CPU 3 Red 0 Green The module is not operational Application firmware loaded on the module will not r...

Страница 5: ...hms maximum Belden 9841 West Penn or equivalent The drop cables to downstream devices should be kept as short as possible no longer than 10 feet The RS 485 communication is asynchronous half duplex us...

Страница 6: ...ing LCD reader display control Wiring for OSDP readers Elevator Control OnGuard hardware is capable of supporting elevator control for up to 128 floors An elevator reader has an input output module th...

Страница 7: ...uires a 12 to 24 VDC 10 power source for it input power Wire the power input with 18 AWG minimum twisted pair cable Power source wiring Notes Be sure to observe polarity Do not use an AC transformer t...

Страница 8: ...o 95 at 85 C 185 F non condensing storage Certifications FCC Part 15 FCC compliance This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15...

Отзывы: