background image

1

460989001B 

Single Door Controller Module LNL-1300-U Quick Reference 

For complete installation details, refer to the UL Listed Access Control and Proprietary Burglar

Alarm Systems in the Hardware Installation Guide, (DOC-600).

The LNL-1300-U Board

The LNL-1300-U provides a solution for interfacing to a Wiegand/ RS-485 type reader and door hardware. It can accept data from a reader with clock/data, 
wiegand signaling or 2-wire RS-485 (OSDP), and provides a tri-stated LED control and buzzer control. Two form-C relay outputs may be used for strike 
control or alarm signaling. Two supervised inputs are provided for monitoring the door contact and exit push button.
Communication to the interface is accomplished via a 2-wire RS-485 interface. It requires a 12 to 24 VDC power source.

SDC board (Dimensions are in inches [mm])

Package Contents

LNL-1300-U board

1000 ohm resistors

Installation

To install the SDC, perform the installation procedures described in the following sections, in the order in which they are presented. 
1.

Set baud rate (SW1), address (SW2), and LED control switches.

2.

Install jumpers.

3.

Mount the board into the enclosure.

4.

Wire the supervised alarm inputs for door position and REX exit push button monitoring.

5.

Wire the upstream host communication.

6.

Wire the relay outputs for door strike and AUX.

7.

Wire the downstream interface for the keypad or card reader.

8.

Wire tamper input.

9.

Wire power and communications inputs.

10. Validate proper operation on power up.

Configuration

The Single Reader SDC Interface Module board contains two (2) 8-position DIP switches that are user-selectable to control addressing, baud rate, and other 
functions, and four jumpers used to configure your system.

Содержание LNL-1300-U

Страница 1: ...es a 12 to 24 VDC power source SDC board Dimensions are in inches mm Package Contents LNL 1300 U board 1000 ohm resistors Installation To install the SDC perform the installation procedures described...

Страница 2: ...bps off ON off ON 38400 bps ON ON ON ON SW1 Switch 5 State ON LEDs behave as the Access LNL series module off LED behavior is in Normal Mode Address SW2 switch 5 4 3 2 1 0 off off off off off 1 off o...

Страница 3: ...Ds LED Table for Series 2 LNL 1300 Mode When switch 5 is in the ON position the LEDs behave like the series 2 LNL 1300 LED Table for Normal Mode When SW1 switch 5 is in the off position the LEDs opera...

Страница 4: ...modem packet and terminated the firmware download operation Invalid Application firmware for module CPU 3 Red 0 Green The module is not operational Application firmware loaded on the module will not r...

Страница 5: ...hms maximum Belden 9841 West Penn or equivalent The drop cables to downstream devices should be kept as short as possible no longer than 10 feet The RS 485 communication is asynchronous half duplex us...

Страница 6: ...ing LCD reader display control Wiring for OSDP readers Elevator Control OnGuard hardware is capable of supporting elevator control for up to 128 floors An elevator reader has an input output module th...

Страница 7: ...uires a 12 to 24 VDC 10 power source for it input power Wire the power input with 18 AWG minimum twisted pair cable Power source wiring Notes Be sure to observe polarity Do not use an AC transformer t...

Страница 8: ...o 95 at 85 C 185 F non condensing storage Certifications FCC Part 15 FCC compliance This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15...

Отзывы: