LEGRAND WattStopper UW-100 Скачать руководство пользователя страница 3

Fixed Time Delay

(DIP 1

&

2 OFF, 3 ON)

Visible

(DIP #5 ON)

Walk-Through
Mode

(DIP #4 ON)

The UW sensor turns the load OFF 3 minutes after the
a rea is initially occupied, if no motion is dete c ted afte r
the first 30 seconds. If motion continues beyond the
f i rst 30 seconds, the set time delay applies.

Audible Alerts

The UW can provide audible alerts as a warning befo re the load turns OFF.

Load turns OFF then back ON befo re delay ex p i re s .

Visible Alert

The UW sensor can provide a visual alert as a warning one minute befo re the

load turns OFF. 

Time delays of 5, 

1 5

( d e fault), or 30 minutes are

a va i l a b le. See DIP SWITCH SETTINGS for info r m a t i o n .

SmartSet™ auto
adjust time delay
and Test Mode

The sensor re co rds typical occupancy patterns. Using
this history (which is co n sta n t ly updated), it chooses an
optimal time delay from 7 minutes (if the space is
u s u a l ly va cant) up to 30 minutes (if the space gets
heavy usage). SmartSet behavior starts immediate ly,
and is refined co n t i n u a l ly as history is co l le c te d .

A Te st Mode with a short time delay of 5 seconds is set
when DIP switches 1, 2 & 3 are OFF. It ca n ce l s
a u to m a t i ca l ly after five minutes, or when you set a
f i xed time delay. To re start Te st Mode, change the time
delay setting to any fixed amount and then return it to
the Auto / Te st setting.

No visual alert for delay ex p i ration warning.

No Visible

(DIP #5 OFF)

No Alerts

" W h i st les" twice, at one minute and at 30 seco n d s
b e fo re turning OFF load. “Chirps” 10 seconds befo re
turning OFF load. “Beeps” three times 10 seco n d s
b e fo re the load goes OFF for Wa l k - T h ro u g h .

Audible Alerts

(DIP #6 ON)

No warnings prov i d e d .

Walk-Through

The Wa l k - T h rough mode shortens the time delay to re d u ce the amount of time
the load is ON after a brief moment of occ u p a n c y, such as returning to an office
to pick up a fo rg o t ten item then immediate ly ex i t i n g .

No Walk-Through

Wa l k - T h rough mode disable d .

Содержание WattStopper UW-100

Страница 1: ...ent magnetic or electronic ballast HorsepowerRating each relay 1 6 HP 120VAC Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec at initial po...

Страница 2: ...Manual ON In either mode the load can be turned ON or OFF using the ON OFF button Load turns ON and OFFautomatically based on occupancy If the load is turned OFF manually it stays OFF until 5 minutes...

Страница 3: ...the space is usuallyvacant up to 30 minutes if the space gets heavy usage SmartSet behavior starts immediately and is refined continually as history iscollected A Test Mode with a short time delay of...

Страница 4: ...r best performance use in spaces not larger than 15 x 15 Ultrasonic Sensor The sensor has two ultrasonic transceiversoperating at 40kHz Detection sensitivity can be adjusted using the trimpot under th...

Страница 5: ...metalbracket M a tchthem up with the holes in the wall box and tighten 4 Turn the circuit breaker ON Wait one minute then push the ON OFF button for each load and the lights will turn ON 5 Test and ad...

Страница 6: ...n LED DIP SWITCH SETTINGS Call 800 879 8585 for Technical Support Ultrasonic Cones Ultrasonic Sensitivity Adjustment Trimpot Button Hinges Tabs UW 200 shown UW 100 has a single button and the Ultrason...

Страница 7: ...ther the top sides of the buttonassembly Gently pull it away from the unit When the adjustments arecompleted replace the button cap by inserting its hinges into the tabs on the main unit and then sque...

Страница 8: ...30 277VAC 50 60Hz ASP 422 Blank cover plate for 2 gang box ASP 432 Switch option cover plate for 2 gang box Lights do not turn OFF 1 There can be up to a 30 minute time delay after the last motion is...

Отзывы: