LEGRAND Wattstopper Series Скачать руководство пользователя страница 5

5

NOTE: 

It is important to exit PtP mode within the three minute time limit mentioned above. If you do not, none of the device 

pairings will be remembered and you have to start the process over from the beginning.

Pairing a device to an existing network

If you need to add the LMPX-600 to an existing in room network, follow the procedure below:

1. 

Enter wireless Push-to-Pair (PtP) mode

 

on the room controller.

 Press the Config button three times (within three seconds) 

until the LED on the room controller flashes green.

2. 

Enter PtP mode on the LMPX-600.

 Press the Config button three times. As with the room controller, the LED on the sensor will 

flash green.

3. 

Pair the devices. 

Press the Config button on the LMPX-600 once to pair the LMPX-600 to the room controller. The load 

connected to the room controller will toggle once (if the load is OFF, it will turn ON; if ON, it will turn OFF) to indicate that pairing 

was successful and its config LED will turn solid green.

4. 

Exit PtP mode. 

Exit PtP on the room controller, by pressing the Config button 3 times. The LED on the room controller will flash 

blue while it completes the pairing process. The Network ID of the LMPX-600 will change to the value used by the previously 

paired devices and the room controller also returns to that value.

DEVICE PAIRING AND UNIT ADJUSTMENT USING THE DLM CONFIG APP

The DLM Config App is available for both iOS

®

 and Android devices

®

. Search “DLM Config” on 

your device to download.
The app provides the ability to pair various devices in a room. Additionally, you can modify load 

binding and edit various DLM parameters for each device.
For details on the features and operation, download the DLM Config App User Guide from the wattstopper web site at :
https://www.legrand.us/wattstopper.aspx

NOTE: 

LMCS-100 software, version 4.7 or later can also be used to pair devices and edit DLM parameters. However, LMCS-100 

requires use of an LMBR-650.

RESETTING THE LMPX-600

When you reset the LMPX-600, the Channel and Network ID will return to their default values, and if the 

sensor was previously paired, it will no longer be connected to that room network. All DLM parameters are 

also returned to their default values. 
There are two ways to reset the LMPX-600:

•  Press the Config button 10 times. The LED will blink green each time the Config button is pressed 

(except for the 7th press which will blink blue). After the 10th press, the LED will turn red then briefly 

turn white indicating it is rebooting.

•  On the back of the sensor, is a small hole that will fit a paper clip. Use a paper clip to depress the 

button inside that hole and hold for 10 seconds. When you first press the reset button, the LED will 

blink red once, then after the 10 seconds will reboot and the LED will briefly turn white, indicating it is 

rebooting.

Paper Clip

Reset Hole

Содержание Wattstopper Series

Страница 1: ...r Use Only Operating Temperature 32 to 104 F 0 to 40 C Storage Temperature 23 to 140 F 5 to 60 C Relative Humidity 5 to 95 non condensing Compliance Regulatory FCC RoHS Bluetooth certified UL and cUL listed E101196 Patent Pending Once paired to an LMRC 611 wireless room controller or LMBC 650 wireless bridge this unit is set for Plug n Go operation adjustment via the DLM Configuration App is recom...

Страница 2: ...Attach the mounting wedge to the ceiling with the two included 1 mounting screws 2 Align the slots of the bracket to the ribs on the back of the LMPX 600 Then slide the LMPX 600 downward onto the mounting wedge Threaded Rod Mount The threaded rod adapter can mount to a 3 8 16 1 4 20 or 1 2 13 hanging threaded rod 1 Screw the adapter onto the rod 2 Attach the mounting wedge to the adapter using the...

Страница 3: ...back towards sensor to lock in place Ball Mount to Ceiling This method is ideal for mounting to a drop ceiling with ceiling tile 1 Cut a hole in the ceiling tile the same diameter as the stem 2 Attach the stem to the back of the swivel bracket by rotating the stem until secure 3 Line up the center hole in the mounting plate with the hole in the ceiling Then attach the swivel bracket by rotating th...

Страница 4: ...ll flash on all room controllers The first room controller placed into PtP will become the master 2 Pair the room controllers together Press the Config button once on each room controller This indicates to the rooms controllers that they will be paired with each other The master room controller s LED blink rate will double once the first device is paired to it This faster blink rate is convenient ...

Страница 5: ...ND UNIT ADJUSTMENT USING THE DLM CONFIG APP The DLM Config App is available for both iOS and Android devices Search DLM Config on your device to download The app provides the ability to pair various devices in a room Additionally you can modify load binding and edit various DLM parameters for each device For details on the features and operation download the DLM Config App User Guide from the watt...

Страница 6: ...NFORMACIÓN DE LA GARANTÍA FCC REGULATORY STATEMENTS This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation NOTE This equipment has been tested and found to comply with the limits for a Cla...

Отзывы: