2
EXAMPLE OF CONNECTION FOR A DLM ROOM WITH LMTI-100 AND LMEQ-41
Line
Voltage
Deep J-Box
Room
Controller
Are...
Initialize System
Create Admin Password
Unswitched
Line
Voltage
B
Line Voltage
Switched with
0-10 Volt control
Dimming Ballast
LED Driver, etc.
Load
Examples
(any relay)
A
Switched
etc.
B
0–10V Dimming
Corner Mount
Sensor
Ceiling Mount
Sensor
DLM Local Network
Low Voltage
LMRJ Cables
PoE Connection
(LMRJ or Cat5e/Cat6 cable)
LMTI-100
LMEQ-41
PoE/PoE+
Ethernet Cable
Do not connect to
DLM local Bus (IRB)
Cat 5e cables
LMTI-100-xxx
Mounted above the ceiling
NOTE:
Max recommended cable
lengths for both IRB connection
to the LMTI and POE from the
LMTI to the LMEQ:
IRB to LMTI: IRB standard-
150' between devices,
up to 1,000’ total
PoE to LMEQ-41: Up to 300'
DLM Local Bus (IRB)
CAT 5E Cable
Screws*
*Use flat-head screws provided – US 6-32 x 0.75”
(Low-voltage bracket can be
used if application allows)
RJ-45 Connector
4” Square Junction Box,
Single Gang Mud Ring
LMEQ-41
Connects via DLM room’s local
Bus (IRB) Cat 5e cables. Each
LMTI-100-xxx can power
up to two LMEQ-41 touchscreens
UPGRADING THE LMEQ-41 VIA THE LMTI-100
The LMTI-100 contains an additional port next to the PoE ports,
labeled Class 2 Ethernet Diganostic Port. This port is used for
connection to LMCS-100 software, allowing the LMEQ-41 firmware
to be updated. For details, see the
LMCS-100 User Manual
.
APPLIANCE
CONTROL
88T9
E101196
26513r1
FCC Class A
CAN ICES-3(A)/NMB-3(A)
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) this device may not cause
harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
UL60950 POE Compliant
Indoor Use Only
Made In China
LMTI-100-120
DLM Touchscreen Injector
120VAC, 50/60HZ, Class 2 Output: 44-50VDC, 280mA
Converts DLM communication to touchscreen platform
PoE Connectors
Ethernet Connector
www.legrand.us/wattstopper
CONFIG BUTTON
The configuration button (Config) allows access to Wattstopper’s
patented Push n’ Learn™ technology to change binding
relationships between sensors, switches and loads.
Configure
Button
Lighting Management
IRB Network Ports