Wattstopper
®
DLM Touchscreen Injector
Injecteur à écran tactile DLM
Alimentador de Pantalla Táctil DLM
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: 27350 – 05/20 rev. 5
Catalog Numbers • Les Numéros de Catalogue • Los Números de Catálogo: LMTI-100-120, LMTI-100-277
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
SPECIFICATIONS
Input Voltage
LMTI-100-120 .........................120/230VAC, 50/60HZ
LMTI-100-277 ................................277VAC, 50/60HZ
Ouput Voltage
LMTI-100-120 ...................................... 48V @ 36.3W
LMTI-100-277 ...................................... 50V @ 41.1W
2 PoE Output ports per IEEE802.3af
1 Ethernet port
2 IRB ports .....................................(15VDC @ 8mA Max)
Operating Temperature ................ 32 to 122°F (0 to 50°C)
Storage Temperature ..................-4 to 158°F (-20 to 70°C)
Relative Humidity ...................... 10-95% Non-Condensing
UL2043 Plenum Rated, ROHS compliant
DESCRIPTION AND OPERATION
The Lighting Management Touchscreen Injector (LMTI-100-xxx) provides an interface from the Digital Lighting Management (DLM)
IRB network to a PoE (Power over Ethernet) network to manage the communication and power to the LMEQ-41. It supports up to 2
touchscreens per LMTI, and provides PnG capability for the LMEQ-41 to provide quick and efficient start-up.
INSTALLATION AND WIRING
The LMTI-100 mounts to a 4”x4” or 4-11/16” x 4-11/16” J-Box.
1. Loosen the screw that holds the mounting arm in place and swing arm away
from LMTI-100.
2. Attach 2 screws to opposite corners of the J-Box loosely (do not tighten).
3. Attach LMTI-100 to J-box by inserting key hole slots over screws, then slide
over so that narrow slots rest on screws. Then tighten screws.
4. Wire as follows: Black – Line; White – Neutral; Green with Yellow Stripe –
Ground. Power to the LMTI-100 must be
unswitched
.
5. Tuck wires back into J-box and swing LMTI-100 back towards mounting
plate. Then tighten the screw to secure.
6. Connect an LMRJ cable from one PoE jack to the LMEQ-41. A second jack
is available if using another LMEQ-41.
7. Connect an LMRJ from
one DLM Local Network
port to a room controller
or other DLM device. A
second port is available
for chaining DLM
devices.
NOTE:
LMRJ cable should
always
be used for
DLM connection.
LMRJ or other
Cat5e/Cat6 cable
can be used for PoE
connection.
WARNING:
TURN THE POWER OFF AT
THE CIRCUIT BREAKER BEFORE WIRING.
Loosen screw to
swing arm out
Tighten screws after
sliding mounting
arm into place.
Ground
(Green with
Yellow stripe)
Line (Black)
Neutral (White)
To Room controller
or other DLM device
To LMEQ-41