LEGRAND Wattstopper LMPL-101 Скачать руководство пользователя страница 3

3

All loads in the room turn 

OFF

 immediately after entering PnL, then one load will turn 

ON

. This is Load #1, which is bound to switch 

button #1 and occupancy sensors as part of the Plug n’ Go factory default setting. 

All switch buttons and sensors that are bound to 

this load have their blue LED solid ON.

Step 2 Load selection.

Press and release the Config button to step through the loads connected to the DLM local network. As each load turns 

ON

 note the 

devices (switch buttons and sensors) that are showing a bright solid blue LED. These devices are currently bound to the load that is 

ON

The blue LED on the room controller or plug load controller connected to the load is also lit.

•  To 

unbind

 a switch button from a load, press the switch button while its blue LED is 

ON

 bright. The blue LED goes dim to indicate 

the button no longer controls the load that is currently 

ON

.

•  To 

unbind

 an occupancy sensor, press the up (

) or down (

) adjustment button while its blue LED is 

ON

. The blue LED turns 

OFF

 to indicate the sensor no longer controls the load that is currently 

ON

.

•  Pressing the switch or up (

) or down (

) button again while the load is 

ON

 

rebinds

 the load to the button or sensor and the blue 

LED illuminates brightly.

Step 3 Exit Push n’ Learn.

Press and hold the Config button until the red LED turns 

OFF

, approximately 3 seconds.

TROUBLESHOOTING

Loads do not operate as expected.

LEDs on a switch or sensor 

don’t light.

1.  Check to see that the the device is connected to the DLM local network.
2.  Check for 24VDC input to the device: Plug in a different DLM device at the device location.  

If the device does not power up, 24VDC is not present:
•  Check the high voltage connections to the plug load controller.
•  If high voltage connections are good and high voltage is present, recheck DLM local network 

connections between the device and the plug load controller.

The wrong lights and plug 

loads are controlled.

1.  Configure the switch buttons and sensors to control the desired loads using the Push n’ Learn 

adjustment procedure.

LEDs turn ON and OFF, but 

load doesn’t switch.

1.  Make sure device is not in PnL.
2.  Check load connections to room controllers and/or plug load controllers.

Отзывы: