LEGRAND Wattstopper LMPL-101 Скачать руководство пользователя страница 2

2

MOUNTING THE CONTROLLER

Lin

e

J-Box

Load

J-Boxes

Load

Lin

e

Outside a 4" x 4" box

Inside a 4" x 4" box

ATTACHING CABLES

Remove rubber jack covers if using all 3 RJ45 receptacles. 

Leave covers in place for all unused receptacles.

CONNECTIVITY

The LMPL-101 communicates with all other DLM devices connected to the DLM local network. Connection drawings are for example 

only. The low voltage LMRJ cables can connect to any DLM device with an open RJ45 receptacle.
All line voltage wiring is #12 AWG.

CAUTION:

 TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE LMCI-100.  

NEVER CONNECT THE DLM LOCAL NETWORK TO AN ETHERNET PORT

 – IT MAY 

DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.

Line

Voltage

Room

Controller

Switch

Ceiling Mount

Sensor

Low Voltage

DLM Local Network

LMRJ Cables

Plug Load

Controller

LMPL-101

J-Box

120VAC

J-Box

Loads

2

1

White: Neutral

Yellow to 

Load 2 (B)

LMRC

102

Red: Switched

120VAC Line

Red to 

Load 1 (A)

Ground

PLUG N’ GO OPERATION (PNG)

The plug load circuit connected to the LMPL-101 is automatically controlled by all 

occupancy sensors on the DLM local network. After the last occupancy sensor’s time 

delay expires, or when a switch button bound to the LMPL-100 is operated, the LMPL-101 

shuts off the plug load circuit.

 

Load ON/OFF button

Blue LED ON when 

load is ON

UNIT ADJUSTMENT - PUSH N’ LEARN

Load Selection Procedure

Before testing or adjusting the DLM local network load configuration, plug a lamp or radio into one of the electrical outlets on the 

controlled plug load circuit.
A configuration button (Config) allows access to our patented Push n’ Learn™ technology to change binding 

relationships between sensors, switches and loads.

Step 1 Enter Push n’ Learn.

Press and hold the Config button (on any DLM device) for 3 seconds.

The red LED on the LMPL-101 begins to blink faster (2x per second) as does the red LED on ALL other 

communicating devices connected to the DLM local network.
The red LEDs continue to blink until you exit PnL mode.

Config button & red LED

WARNING:

 TURN THE POWER OFF AT THE 

CIRCUIT BREAKER BEFORE WIRING.