Digital Lighting Management Plug Load Controller

Installation Instructions • Instructions d’Installation • Instrucciones de Instalación

No: 24045 – 01/19  rev. 3

Catalog Number • Numéro de Catalogue • Número de Catálogo: LMPL-101

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

LMPL-101-U is BAA and TAA compliant (Product produced in the U.S.)

SPECIFICATIONS

Input Voltage .............................................................................. 120VAC, 50/60Hz
Output Capacity ............................................................................150mA@24VDC
Power Supply ........................................................... Wattstopper Room Controller
Connection to the DLM Local Network .............................................. 3 RJ-45 ports
DLM Local Network characteristics when using LMRC-11x/2xx room controllers:
 

Low voltage power provided over Cat 5e cable (LMRJ); max current 800mA. 

 

Supports up to 64 load addresses, 24 communicating devices including up  

 

to 4 LMRC-10x series and/or LMPL-101 controllers.  

 

Free topology up to 1,000’ max.

Environment ........................................................................... For Indoor Use Only
 

Operating Temperature ...........................................32° to 131°F (0° to 55°C)

 

Storage Temperature ............................................ 23° to 176°F (-5° to 80°C)

 

Relative Humidity .................................................5 to 95% (non condensing)

Patent Pending

This unit is pre-set for Plug n’ Go™ operation, adjustment is optional.

For full operational details, adjustment and more features of the product, see the DLM System Installation Guide provided with Wattstopper room 

controllers, and also available at www.legrand.us/Wattstopper.

Installation shall be in accordance with all applicable regulations, local and NEC codes. 

Wire connections shall be rated suitable for the wire size 

(lead and building wiring) employed. 

For Class 2 DLM devices and device wiring: To be connected to a Class 2 power source only. Do not reclassify and install as Class 1, or Power and 

Lighting Wiring.

PLACEMENT EXAMPLES

Switch

Ceiling Mount

Occupancy

Sensor

Plug Load

Controller

Line Voltage

(Class 1 wiring)

To Plug Load

(Class 1 wiring)

J-Box 

To Other

Electrical

Outlets

Switch

Ceiling Mount

Occupancy

Sensor

Room

Controller

J-Box 

Plug Load

Controller

Line Voltage

(Class 1 wiring)

To Plug Load

(Class 1 wiring)

J-Box 

To Lighting

Load

(Class 1 wiring)

To Other

Electrical

Outlets

Line Voltage

(Class 1 wiring)