17
Mode
By default, when the Type is Group, the Mode is set to
ToggleNT. With this value, the button will toggle, but the LED will
not track the actual settings of the loads. Additionally, the button
will not track if another source such as a sensor turns the load
ON. The reason for this is that the button can’t track the status of
all loads in the group.
Group ID
The button is assigned to the specific group chosen here.
Send, Next Button
These function the same as for a load button.
Assign Loads
Assign Loads
<0058721386>
Type:
Load
Load:
<1>
Member:
<Yes>
SEND
In this screen you choose one or more loads to be controlled by
a button or rocker.
The
Load
parameter has possible values of 1–64, which is the
maximum possible number of loads that can be assigned in a
room or panel. All values are shown regardless of whether those
loads exist in the room or panel, so care should be taken to
make sure you are assigning only to existing loads.
After selecting a load, scroll to the
Member
parameter, to
change whether that load will be controlled by the button or
rocker.
Once all loads are configured. Select
SEND
, then press the
same button you previously chose when entering the Button
Configuration screen.
DIMMING CONFIGURATION
Dimming Configuration enables communication between the
load and the LMCT-100. Use this function to change dimming
parameters.
S e n s o r C o n fi g u r a t i o n
L o a d C o n fi g ( P n L )
D a y l i g h t i n g C o n fi g
B u t t o n C o n fi g u r a t i o n
D i m m i n g C o n fi g u r a t i o n
M o r e
=
B AT
Load 1 quickly turns ON and OFF (or OFF and ON depending
on its original state).
Based on the room controller type (Dim or Switch) one of the
following screens displays for load 1.
Load 1 Dim Config
Type:
<Dim>
Low Trim:
<0%>
High Trim:
<100%>
Preset Level:
<Last>
Burn-in Hours:
<0>
SEND PRIOR NEXT
Type: Dimming
Load 1 Dim Config
Type:
<Switch>
Trip Point:
<51%>
(Trip point alters
when a relay switches
during a fade)
SEND PRIOR NEXT
Type: ON/OFF Switch
Important:
All loads connected to dimming capable room
controllers default to Load Type <Dim>. Be sure to select the
appropriate load type because these room controllers can
control either type of load. Default settings are based on the load
type selected.
Lock Button
Lock Button options are Yes and No. If set to No, a user can set
the current light level to a scene button by pressing and holding
the button for 7 seconds. If set to Yes, this feature is locked and
the user can’t change the scene setting.
Fade On, Fade Off
Fade On and Fade Off determines how much time it takes for
the loads to reach their target levels when this button is pressed.
The fade time defaults are Use Load’s. By default, all loads in a
scene carry a two second ON and OFF fade time. Each button
can be set for different fade times independently for the same
scene. Application: This feature allows the user to recall a scene
quickly from one button, but from another button the scene recall
is much slower and gradual.
Fade time value options are from None (immediate) to 18
hours in duration. As you scroll through the values, the units of
measure change from seconds to minutes to hours.
Send, Next Button
These function the same as for a load button.
Rocker Button Parameters
A rocker button, or paddle, is a specific type of load button. It
cannot be changed to any other value.
Rocker Button Config
<0058721386>
Fade On:
<Use Load’s>
Fade Off:
<Use Load’s>
Ramp Rate:
<17%/sec>
ASSIGN LOADS
SEND NEXT BUTTON
Fade On, Fade Off
Fade On and Fade Off determines the time that it takes for loads
bound to this rocker to reach the target level.
The fade time defaults are Use Load’s. By default, all loads carry
a two second ON and OFF fade time. Each rocker and button
can be set for a different fade time independently for the same
loads, allowing fast or slow load fade depending on the button or
rocker used.
Fade time value options are from None (immediate) to 18
hours in duration. As you scroll through the values, the units of
measure change from seconds to minutes to hours.
Ramp Rate
Ramp Rate determines the speed (or rate) at which the light
level of bound loads increases or decreases when the top or
bottom of the rocker is pressed and held. The default value is
17%/second which means that it takes approximately 6 seconds
to ramp from 0–100%.
Loads
Select this option to open the
Assign Loads
screen. This will
allow you select one or more loads to assign to the rocker .
See
Send, Next Button
These function the same as for a load button.
Group Button Parameters
If you select the Group for the Type, you can assign the button
to a Network Group. For details on Network Groups, see
Group Button Config
<0058721386>
Type:
<Group>
Mode:
<ToggleNT>
Group ID:
<??>
SEND NEXT BUTTON