2

LENS OPTIONS

Several lenses are available for use with the FSP-321. Lenses give coverage at mounting heights between 8' – 40' for applications such 

as offices, warehouses, and outdoor use. Density and range of the coverage is determined by the type of lens and mounting height. 

A lens with shroud option is also available. The shroud blocks light coming from the fixture, to prevent interference with the photocell 

function of the sensor. Lens modules are IP-66 rated when combined with an FSP-321 sensor mounted to an outdoor-rated fixture. See 

the FSP-Lx Lens Coverage Guide for more information.

WIRING

INSTALLATION

1.  Determine an appropriate mounting location inside the light 

fixture minimizing the electric light contribution to the sensor’s 

photocell. Allow a minimum distance of 0.2" (5.1mm) from the 

wiring end of the sensor to the wall of the fixture.

2.  Drill a hole 1.30" (33.0mm) in diameter through the sheet 

metal in the bottom of the fixture.

3.  Add the rubber gasket to the threaded collar, and install the 

sensor face down, parallel to the mounting surface. Ensure 

the rubber gasket touches the inside surface of the fixture. 

Install the nut (or optional collar) securely against the fixture 

to a torque of 25–30 in-lbs to ensure Ithe lens is installed 

properly. 

4.  Align the locking features between the sensor and lens 

module and push the lens module forward until the o-ring 

seals firmly. Turn the lens module clockwise to ensure it locks 

in place.

5.  Connect wires as shown in wiring diagram.
6.  Restore power from the circuit breaker.

NOTE: 

An optional collar can be installed in place of the tightening 

nut. See the Ordering Information table on page 4 for details.

NOTE: 

The Outside Fixture Wall thickness should be no 

greater than 0.125" (3.18mm) for optimal sensor 

mounting and security.

OUTDOORS—USE AT THE EXPOSED SENSOR COLLAR PART ONLY WHEN INSTALLED AT THE SPECIFIC LOCATION PER 

INSTALLATION INSTRUCTIONS WITH A LISTED OUTDOOR ENCLOSURE

.

WARNING:

 TURN THE POWER OFF AT THE 

CIRCUIT BREAKER BEFORE WIRING.

Tightening Nut

(or Optional Collar)

Fixture 

Wall

Lens Assembly

Outside 

Fixture Wall

Inside Fixture

Wall

Tightening Nut

(or Optional Collar)

Rubber

Gasket

Rubber

Gasket

Non-Dimming

Load

Load

(Red)

Gray

Violet

Neutral or

Phase B
White with

Black Stripes

Neutral or

Phase B

Black

White

Line or

Phase A

Dimming

Load

Neutral or

Phase B
White with

Black Stripes

Load

(Red)

Neutral or

Phase B

Black

Dim (-)

Gray

Dim (+)

Violet

White

Line or

Phase A

Class 1

Содержание Wattstopper FSP-321

Страница 1: ...power pack is required It is designed to be installed in both indoor and outdoor environments NOTE When the FSP 321 is powered up the first time it will use factory default parameters to operate If ad...

Страница 2: ...xture Install the nut or optional collar securely against the fixture to a torque of 25 30 in lbs to ensure Ithe lens is installed properly 4 Align the locking features between the sensor and lens mod...

Страница 3: ...Configuration App is available for both iOS and Android devices Search Wattstopper Sensor Config on your device to download The Sensor Configuration tool is a mobile app for changing defaults and tes...

Страница 4: ...ht FSP L7 S 360 lens up to 100 diameter at 40 height with shroud FSP C1 Small collar for use with FSP L2 and FSP L3 lenses FSP C2 Large collar for use with FSP L7 lens Sensor is White FCC REGULATORY S...

Страница 5: ...de consigne de la cellule photovolta que pour la Marche Arr t D sactiver OUVREZ L APPAREIL pour l installer dans un bo tier class selon les consignes d installation DESCRIPTION ET FONCTIONNEMENT Le F...

Страница 6: ...nsit et la port e de la zone de couverture est d termin e par le type de lentille et par la hauteur de montage Une lentille avec obturateur est galement disponible en option L obturateur bloque la lum...

Страница 7: ...TION DE CONFIGURATION DU CAPTEUR L App Configuration du capteur est disponible pour les appareils iOS et Android Rechercher Wattstopper Sensor Config sur votre appareil pour le t l charger L outil de...

Страница 8: ...our 6 m 20 pi de hauteur avec obturateur FSP L7 Lentille 360 jusqu 30 4 m 100 pi de diam tre pour 12 2 m 40 pi de hauteur FSP L7 S Lentille 360 jusqu 30 4 m 100 pi de diam tre pour 12 2 m 40 pi de hau...

Страница 9: ...n Desactivado Punto de ajuste de fotocelda para Encender Apagar Desactivado DISPOSITIVO ABIERTO para instalaci n en un gabinete calificado seg n las Instrucciones de instalaci n DESCRIPCI N Y FUNCION...

Страница 10: ...ajuste o collar n opcional Empaque de goma Empaque de goma NOTA Un collar n opcional se puede instalar en lugar de usar la tuerca de plastico Consulte la table de informaci n de pedidos en la p gina 1...

Страница 11: ...a aplicaci n de configuraci n del sensor est disponible para dispositivos iOS y Android Busque Wattstopper Sensor Config en su dispositivo para descargar La herramienta de configuraci n del sensor es...

Страница 12: ...LED rojo parpadeante Si el LED parpadea con pulsos largos en lugar de pulsos cortos el sensor ha alcanzado su punto de ajuste de mantener apagado o punto de ajuste de nivel de luz de fotocelda No hay...

Отзывы: