MOUNTING THE SENSOR

The DT-200 sensors can be mounted to walls or ceilings with the supplied swivel bracket, 

and the supplied junction box cover plate if necessary (see figure B). Mounting at fixture 

height is most effective.

Ceiling:

 It is best to leave approximately six inches between the sensor and the wall so 

that the Tightening Screw can be easily accessed. Orient the Base Bracket’s Half-Circle 

Notch in the direction that the sensor will point. 

Wall:

 Orient the Base Bracket’s Half-Circle Notch, up.

1.  Mount the Base Bracket to the mounting surface with screws.
2.  At the center of the Base Bracket, drill a hole in the ceiling or wall (unless mounting 

to a junction box) large enough to thread the sensor’s wires through. 

3.  Guide the sensor’s wires into the Base Bracket and through the hole in the ceiling or 

wall.

4.  Connect the sensor to the Base Bracket by angling the Post Bracket so that it is in 

line with the half circle notch, as illustrated in figure A. Push the ball into the Base 

Bracket opening until it snaps into place, being careful not to pinch the wires. The 

brackets can be easily connected or disconnected using this orientation.

5.  Insert the Tightening Screw and Nut into the Base Bracket as illustrated.
6.  Use the Reference Surface Angle to adjust the sensor for optimum coverage. 

When mounted at ten feet, the Reference Surface Angle should be parallel to the 

wall or the vertical (see figure C). (As the mounting height decreases, the sensor 

will be tilted up slightly; as the mounting height increases, the sensor will be tilted 

down slightly). 

7.  Tighten the Tightening Screw.

-XQFWLRQ%R[

ZLWK0XG5LQJ

-XQFWLRQ%R[

&RYHU3ODWH

&HLOLQJ

6ZLYHO%UDFNHW

3UHGULOOHG

+ROHV

Junction Box Cover Plate Installation

Wattstopper recommends using a 3.0" mudring 

with a 4" octagonal box.

Half-Circle

Notch

Base

Bracket

Reference

Surface

Angle

Post

Bracket

Tightening

Screw

Nut

Sensor Angle Adjustment

While watching the LEDs for flashes (Red LED indicates activation from the PIR sensor; Green LED indicates activation from the 

ultrasonic sensor), have a person walk back and forth at the far end of the space. Increase or decrease mounting angle as needed until 

the desired coverage is achieved.
Tighten the Tightening Screw to hold this position.

Service

To override all sensor functions, set the Ultrasonic Sensitivity trimpot to the fully counterclockwise (Service) position. This bypasses the 

occupancy control functions of the sensor, but still allows the lights to be manually controlled with a light switch, if one is installed.

Wall Mount

3$5$//(/

WR:$//

DWIRRW

PRXQWLQJ

KHLJKW

Reference Surface Angle

3$5$//(/

WR9(57,&$/

DWIRRW

PRXQWLQJ

KHLJKW

Reference Surface Angle

Ceiling Mount

Содержание Wattstopper DT-200

Страница 1: ...Frequency 40kHz DESCRIPTION AND OPERATION The Wattstopper DT 200 Dual Technology occupancy sensors combine advanced passive infrared PIR and ultrasonic technologies into one unit The combination of th...

Страница 2: ...W1 LVSW 101 Low Voltage Switch Input BZ 250 Power Pack must be grounded to ensure signal integrity not for safety ground Ground Fixture A A Auto ON Man ON Low Voltage Wires Control Output Blue Common...

Страница 3: ...the Reference Surface Angle to adjust the sensor for optimum coverage When mounted at ten feet the Reference Surface Angle should be parallel to the wall or the vertical see figure C As the mounting h...

Страница 4: ...s or until the detection LEDs turn ON and then OFF The LEDs flash rapidly for 10 seconds after the setting has changed SENSOR ADJUSTMENT The sensors are factory preset to allow for quick installation...

Страница 5: ...y occupied if no motion is detected after the first 30 seconds If motion continues beyond the first 30 seconds the selected time delay applies PIR Sensitivity Switch 5 Minimum forces a reduced detecti...

Страница 6: ...ctions to sensor while sensor is active If there is no voltage replace the sensor If there is voltage check for 24VDC between the blue and black wire at the power pack If 24VDC is present and the rela...

Страница 7: ...77VAC 50 60Hz 20A ballast or incandescent with Hold On and Hold Off capability BZ 200 Power Pack 120 277VAC 50 60 Hz 20A Ballast ELV MLV Incandescent LED 16A E Ballast CFL Plug Load BZ 250 Power Pack...

Страница 8: ...Port e ultrasonique normale 74 32 111 48 m 800 1 200 pi R glage de la sensibilit Minimum maximum potentiom tre Fr quence 40 kHz PORT E Le DT 200 a une port e elliptique La port e indiqu e dans le sch...

Страница 9: ...on Fonction du d tecteur DT 200 ver 3 DT 200 ver 2 BZ 50 PP 24 V c c ent Rouge Violet Rouge Relais commun au bloc d alimentation Noir Gris Noir Sortie de contr le Bleu Jaune Bleu Relais isol commun Ve...

Страница 10: ...ale Pour un montage 3 m tres 10 pieds l angle de surface de r f rence doit tre parall le au mur ou la verticale voir figure C Lorsque la hauteur de montage diminue le d tecteur sera l g rement redress...

Страница 11: ...us pour remettre la fonction de niveau de luminosit au r glage par d faut maximum Appuyez sur le bouton de r glage du niveau de luminosit et maintenez le enfonc pendant 5 secondes ou jusqu ce que les...

Страница 12: ...nement du d tecteur par rapport l interrupteur manuellement actionn est d termin par les r glages des interrupteurs DIP concernant la logique de pr sence Mode manuel option de d clenchement 6 ou 7 dan...

Страница 13: ...es RALLUME les lumi res D PANNAGE En cas de fonctionnement inattendu 1 V rifiez les r glages de l interrupteur DIP 2 Assurez vous que les interrupteurs sont r gl s d apr s les r glages d finis dans le...

Страница 14: ...cordement de l interrupteur manuel a t utilis Ne raccordez rien cette borne si vous n utilisez pas d interrupteur instantan basse tension entre le d tecteur et le bloc d alimentation La DEL rouge clig...

Страница 15: ...as nica t pica 74 111 m 800 1200 pies Ajuste de sensibilidad M nimo a M ximo potenci metro Frecuencia 40 kHz PERFILES DE COBERTURA El sensor DT 200 proporciona un perfil de cobertura el ptico La cober...

Страница 16: ...es el cable marr n Funci n del sensor DT 200 ver 3 DT 200 ver 2 BZ 50 PP Entrada de 24 V CC Rojo Violeta Rojo Com n a paquete de alimentaci n Negro Gris Negro Salida de control Azul Amarillo Azul Rel...

Страница 17: ...una cobertura ptima Cuando se monta a 3 metros diez pies el ngulo de superficie de referencia debe quedar paralelo a la pared o a la vertical consulte la figura C A medida que disminuye la altura de m...

Страница 18: ...r el bot n durante 5 segundos o m s se restablece la luz al valor predeterminado m ximo Presione y mantenga presionado el bot n de nivel de luz durante 5 segundos o hasta que las luces LED de detecci...

Страница 19: ...i n de presencia pueden encender la carga CONFIGURACI N DEL INTERRUPTOR DIP Tiempo de demora Interruptores 1 2 3 El sensor mantendr las luces encendidas mientras se detecta la presencia La cuenta regr...

Страница 20: ...idad ultras nica La posici n completamente contraria a las manecillas del reloj es la anulaci n del sensor Gire el potenci metro en el sentido de las manecillas del reloj hasta que la luz LED destelle...

Страница 21: ...e apagan 1 Controle todas las conexiones de cables del sensor y del paquete de alimentaci n 2 Desconecte el cable azul del paquete de alimentaci n Si las luces no se apagan verifique el cableado del p...

Отзывы: