Installing the Trimod® BATTERY

It is possible to connect external battery units to increase UPS 
autonomy.
If the configuration uses more than one battery it is necessary to 
position all the Trimod® Battery units on the same side of the UPS 
Trimod® and connect them in cascade with each other using the 
multicore cables supplied.

There are four different external battery cabinets for the Trimod® 
BATTERY units:
-  a modular model consisting of a cabinet with an internal structure 

that uses battery drawers for up to a maximum of 80 12V 7.2Ah or 
12V 9Ah batteries (16 drawers).

-  a modular model consisting of a cabinet with an internal structure 

that uses battery boxes for up to a maximum of 100 12V 7.2Ah or 
12V 9Ah batteries (20 drawers).

-  a compact, non modular, economical model that uses a shelf 

architecture instead and on which the batteries are placed.  
It can house 60 or 120 12V 7.2Ah or 12V 9Ah batteries.

-  a compact, non modular, economical model that uses a shelf 

architecture instead and on which the batteries are placed.  
It can house 20 12V 94Ah batteries.

A Trimod® BATTERY can be connected to several UPS Trimod® units.

 WARNING

 

The following instructions are of a prescriptive nature and it is 
imperative they be complied with.

Opening or removing the panels from the UPS Trimod® or Trimod® 
BATTERY you risk exposure to high and dangerous voltages! To 
guarantee protection of personnel during installation of the Trimod® 
BATTERY make sure that the connections are done under the 
following conditions: 

1. There must be no mains voltage
2. The loads are off and disconnected;
3. The UPS Trimod® is off with no voltage and all fuse carrier isolating 

switches on the UPS Trimod® and Trimod® BATTERY are open.

To ensure that the UPS Trimod® has stopped completely if you want 
to add a Trimod® BATTERY in an existing installation, follow the steps 
illustrated in the MAINTENANCE chapter.

The connection of a Trimod® BATTERY to the UPS Trimod® must be 
done according to the following diagram and the steps listed below:

 

1. Make sure that all the battery fuse carrier isolating switches are 

open;

2. Connect the UPS and the additional battery cabinet using the earth 

cable (yellow-green);

3. Use the wiring supplied with the Trimod® BATTERY to connect the 

positive and negative terminals of the UPS Trimod® to those of the 
Trimod® BATTERY.

The connection of a Trimod® BATTERY to the UPS Trimod® 40 - 60 
must be done accoring to the diagram above and the steps listed below:

1. Make sure that all the battery fuse carrier isolating switches are 

open;

2. In each Trimod® BATTERY remove the lower front panel;
3. In each Trimod® BATTERY remove the terminal block loosening the 

2 securing screws;

4. Connect the UPS and the additional battery cabinet using the earth 

cable (yellow-green);

5. Use the wirings supplied with the Trimod® BATTERY to connect the 

positive and negative terminals of the UPS Trimod® to those of the 
Trimod® BATTERY.

 WARNING

 

The connection of a Trimod® BATTERY to the UPS Trimod® 
40 must be done using BOTH wirings supplied with the 
Trimod® BATTERY.

 

The connection of a Trimod® BATTERY to the UPS Trimod® 
60 must be done using BOTH wirings supplied with the 
Trimod® BATTERY.

6. In each Trimod® BATTERY insert the terminal block securing it with 

the 2 screws provided;

7. In each Trimod® BATTERY secure the lower front panel.

uPS

Trimod

®

BATTERY

uPS

Trimod

®

BATTERY

uPS

Trimod

®

uPS Trimod

®

 40/60